3.0 SYSTEM COMPONENTS
UL S2203
Cheetah Xi 50 Installation Manual
3-21
FM
P/N: 06-369
Rev 6, 09/2015
3.9.4.2
MASTERBOX INTERFACE, P/N 10-2413
The Masterbox Interface (See Exhibit 3-43) provides the Cheetah Xi
50 control panel with the ability to activate a Local Energy Type
Auxiliary Fire Alarm System as defined by NFPA 72. The Masterbox
Interface
must
be used in conjunction with a Supervised Control
Module (P/N 55-042/55-047).
Refer to Fike document 06-229 for more information.
3.9.5
RELAY MODULE, P/N 55-043
RELAY MODULE WITH ISOLATOR, P/N 55-048
The Relay Module (See Exhibit 3-44) provides two Form C dry
contact relays configurable for single operation via the intelligent
addressable loop. It contains a wide range of operating modes
including multi-zone operation of up to 4 different states and multi-
state programming. Optional feedback or independent contact
closure input available for use on non-critical input such as
monitoring the relay closure or closure from the device that it is
monitoring. The isolator version provides complete short circuit
isolation for NFPA Class X wiring. A module cover plate (not shown)
is included with module.
3.9.6
RELEASING CONTROL MODULE, P/N 55-052
RELEASING CONTROL MODULE WITH ISOLATOR,
P/N 55-053
The Releasing Control Module (See Exhibit 3-45) provides an
interface between the suppression system solenoid, agent release
module (ARM), or impulse releasing module (IRM) and the
addressable loop. The module requires 24VDC continuous output
power from the panel to power the selected releasing device(s). The
module provides two different output connections (solenoid or
release module) of which ONLY ONE can be used per module.
It contains a wide range of operating modes including multi-zone
operation of up to 4 different states and multi-state programming.
The isolator version provides complete short circuit isolation for
NFPA Class X wiring. A module cover plate (not shown) is included
with module.
Refer to Fike document 06-106, “Agent Release Module (ARM)
Manual” and 06-552, “Impulse Release Module (IRM) Manual” for
proper connections to ARM(s) or IRM(s).
Note:
ARM’s and IRMs may be intermixed on the same releasing
circuit.
3.9.6.1
SOLENOID PROTECTION ASSEMBLY, P/N 10-2360
The RCM can be connected to a single releasing solenoid rated up
to 2 amps maximum at 24VDC. The Solenoid Protection Assembly
(See Exhibit 3-46)
must
be used when connecting a solenoid to the
RCM. Refer to Fike document 06-186 for compatible releasing
solenoids.
Refer to Fike document 06-344 for more information.
Exhibit 3-44: Relay Module
Exhibit 3-43: Masterbox Interface
Exhibit 3-45: Releasing Control
Module
Exhibit 3-46: Solenoid
Protection Assembly