BELOW ARE COMMON QUESTIONS ASKED
To resolve a problem, we need to identify whether it is a mechanical problem, or performance.
POOL NOT HEATING:
•
In and out difference too small
: Either the air humidity is too low, or the pool pump is
pushing too hard. Difference 0-4 degrees accepted. Higher the humidity ( 80% or higher),
higher the difference.
•
i
nitial heating takes time
. Allow a few days for the water to heat up, while leaving the pool
pump and heater on 24-7. And cover the pool with any type of cover.
•
Heater is not working:
there are 3 basic indicators of the heaters operation. 1- heater
blowing cold air 2- compressor pressure goes up by about 0.5 MPA 3- heater dripping water
from the condensation lines after 10-15 minutes. If any of these conditions are observed, the
heater is working. The problem is performance, not functionality
•
Heater is not leaking water from the bottom:
Heat pumps will create quite a bit
condensation, which will drain from the bottom of the heater.
•
The air is too dry:
Pool heat pumps are optimized for 80% humidity. If the humidity is much
less, best thing is to install a set of micron misters. A set can be purchased for about 20-30
dollars from hardware stores. Which screws into the garden hose and sprays mist . Place
the heads near the coils, this way the incoming air will draw moisture into the heater coils
and heat exchange rate will increase, thus resuting in better output
•
Pool pump's timer setting is too short:
Pool heaters need pool pumps circulation. If the
pump doesnt run long enough, neither will the heater. Please adjust the timer settings on
your pump or remove the timer for heating.
•
The fan is not coming on, the pressure is not going up on the pressure gauge:
When
the thermostat calls for heat, the fan will come on within 4 minutes, and within 45 seconds,
the compressor will kick in. If this doesnt happen, and the pool water temperature is much
lower than the desired temperature, there is a mechanical issue of an error message on the
screen. Be sure that there is no error messages on the screen. This may require a phone
call to us at Fibropool Co. 1.228.313.7874
•
Pool is too big for the heater, for your climate zone:
There is not much can be done,
except adding a second heater into the system.
•
Air is too cold:
Heat pumps absorb heat from the air. If the air too cold- below 60F, the
performance will be very little. Your only option is to wait for warmer weather.
HEATER IS GIVING WATER FLOW ERROR (PL)
•
Pool pump is OFF
•
Pool pump is really weak
•
Pool filter is dirty
•
Plumbing is connected backwards, cold water is connected to top
•
By pass valve is set incorrectly, not allowing water to flow thru the heater.
HEATER IS VIBRATING/ SHAKING HEAVILY
•
Loose or broken Fan blade
NO DISPLAY
•
Digital display is damaged. This happens mostly if the protective cover is broken or missing, making the
controller NOT weather proof.
•
The incoming power is not 220 volts. Reading between L1 and L2 should be between 208-240 volts.
•
Motherboard's fuse is blown.
V-2105 Fibropool Co LLC, Ms USA