Running Test
Inspection Before Running Test
1.
Check electrical connecors, terminal screws. Be sure all are tight
2.
Check voltage at the power supply, 208-240 volts must be observed.
3.
Check Bonding wire's tightness and attachment to the ground rod.
4.
Check plumbing connections, make sure all glued, tight and In from BOTTOM, OUT from TOP
Turn on the pump
Wait about 1 minute, for all the air to purge from the system
Turn on the heater
Push the ON OFF button on the heater, Making sure the SUNSHINE sign is on top.
ALLOW ABOUT 5 MINUTES, FOR THE FAN TO START BLOWING COLD AIR, CONDENSATE
WATER TO START DRIPPING.
This is the indication of the heater working.
If all is well, leave your heater running. Your heater will only be on while your pump is ON
In and out temperatures maybe very close or even the same, but this depends on many
factors including a strong pump pushing the water too fast to register. Real indication of heating
is cold air and condensation.
V-2105 Fibropool Co LLC, Ms USA