10
InstallatIon
4.5:
Connection with 0-10V analog sensors
The 2-wire analog sensor requires pull-up resistor.
You can connect up to 4 analog sensors to IN1/IN2/IN3/IN4 terminals.
1. Disconnect power.
2. Connect with the diagram below:
VDD
GND
OUT
0-10V
0-10V
0-10V
0-10V
VDD
GND
OUT
GND
OUT
GND
OUT
12/24V DC
GND
IN3
IN4
IN1
GND
P
IN2
1
6
6
7
7
12V
8
Diagram 5: Example connection with 4 0-10V analog sensors
(1 – power supply, 6 – 3-wire 0-10V analog sensor,
7 – 2-wire 0-10V analog sensor, 8 – configurable pull-up
resistors)
3. Verify correctness of connection.
4. Power the device.
5. Add the device to the Z-Wave network.
6. Change values of parameters:
• Connected to IN1:
»
Does not require pull-up: change parameter 20 to 0
»
Requires pull-up: change parameter 20 to 1
• Connected to IN2:
»
Does not require pull-up: change parameter 21 to 0
»
Requires pull-up: change parameter 21 to 1
• Connected to IN3:
»
Does not require pull-up: change parameter 22 to 0
»
Requires pull-up: change parameter 22 to 1
• Connected to IN4:
»
Does not require pull-up: change parameter 23 to 0
»
Requires pull-up: change parameter 23 to 1