SFAM
Festo – SFAM – 1103a English
57
Set analogue filter [AnA.F]
7. Choose the value for the filter time constants (15 ms, 30 ms, 60 ms, 125 ms, 250 ms, 500 ms or
999 ms) with the A/B buttons.
8. Press the Edit button to confirm the set value.
[dIG.F] with the currently chosen value flashes. The digital filter can be set.
Set smoothing for the digital filter [diGF]
Note
A high filter time constant and high smoothing can result in a response time of several
seconds.
9. Select the value for dampening (d1 to d6 or d.OFF) with the A/B buttons.
10.Press the Edit button to confirm the set value.
[ConS] is displayed and the currently chosen value flashes.
The unit for the air consumption (m
3
, scf or l) can be set.
Set the physical unit for the air consumption [ConS]
11.Select the desired setting (m
3
, scfm or l) with the A/B buttons.
12.Press the Edit button to confirm the selection.
The currently set value [PnP] or [nPn] for the switching element output flashes. The switching ele-
ment output can be set.
Set switching output characteristic [PnP] or [nPn]
13.Select the desired setting (PNP or NPN) with the A/B buttons.
14.Press the Edit button to confirm the selection.
[Lock] flashes. The current setting is displayed.
Set security code
Note
Keep the security code in a safe place. If the security code has been forgotten see the
chapter 6Resetting SFAM to factory setting.
15.Use the A/B buttons to select between an inactive security code (OFF) or a maximum 4-digit secur-
ity code.
16.Press the Edit button to confirm the selection.
The SFAM is in RUN mode.