8.13

Teach switching points (TEACH mode)

The Teach process is the same for configuring the switching outputs for OutA and
OutB. In the following, the process is described using the switching output OutA.
The Teach function is only available for flow monitoring.

Requirement: The sensor is ready for operation (RUN mode).
If the security code is activated, the parameter entry option is blocked: [Lock]
flashes.
1. Enter the security code 

è

 8.5 Enter the security code (EDIT mode).

2. Establish the switching function in EDIT mode

è

 8.6 Configuring switching output (EDIT mode).

3. Apply signal value 1.
4. Press the A pushbutton and Edit button.

Ä

The current signal value will then be adopted as the first Teach point
(TP1). [t-IN] flashes.

5. Apply signal value 2.
6. Press the A pushbutton and Edit button.

Ä

The current signal value will then be adopted as the first Teach point
(TP2). Switch to the RUN mode.

8.14

Zero point synchronisation (Zero Adjust)

Requirement:

The sensor is ready for operation (RUN mode).

The operating pressure is present, but no flow rate exists.

[Z.AdJ] is set to [ON] (

è

 8.7 Change device settings (EDIT mode)).

The measured value lies in the range 0 l/min ± 3 %FS.

Press the A and B pushbuttons and Edit button simultaneously.

Ä

If [OK] appears: the zero point synchronisation was successful.

If [FAIL] appears: the zero point synchronisation was not successful.
Check requirements.

If [Z.AdJ] [OFF] is set for a later time, the sensor takes over the factory setting cal-
ibration values.

9

Operation and use

After the supply voltage is switched on, the SFAH needs a warm-up time of
10 minutes until it achieves the specified accuracy. 
The flow rate displayed by the SFAH refers to the standard conditions that were
set under Options in the Special menu.

9.1

Restoring factory settings (restore)

By resetting to the factory settings, the current settings are lost. If required, make
a note of these settings before resetting.

1. Switch off operating voltage.
2. Keep the A and B pushbuttons pressed down simultaneously.
3. Switch on the operating voltage.
4. Additionally, press the Edit button.

Ä

[RSto PArM] appears. All parameters are reset to the factory settings.

10

Maintenance and care

1. Turn off energy source and compressed air.
2. Clean sensor with non-abrasive cleaning agents.

11

Fault clearance

Fault description

Cause

Remedy

No operating voltage or imper-
missible operating voltage

Apply permissible operating
voltage.

Electrical connections swapped

Connect the device in accord-
ance with the circuit diagram.

Device defective

Replace device

No display

Eco mode on

Press pushbutton or switch off
Eco mode

Short circuit or overload at the
output

Eliminate short circuit/over-
load.

Incorrect switching point taught
(e.g. at 0 l/min)

Repeat teaching.

Incorrect standard condition set
for volumetric flow rate

Correct standard condition

Device defective

Replace device

Indicator or switching output
does not react as expected

Parameter incorrect

Reset to factory settings.

[Er01] / [FAIL]

1)

Device defective

Replace device

[Er02] / [ASIC]

1)

Device defective

Replace device

[Er03] / [SEnS]

1)

Device defective

Replace device

[Er09] / [UndR]

Below sensing range

Maintain sensing range

[Er10] / [OVER]

Sensing range exceeded

Maintain sensing range

[Er17] / [SUPL]

2)

Undervoltage

Maintain permissible operating
voltage

Fault description

Cause

Remedy

[Er20] / [t.Hi]

2)

Temperature fault

Check operating condi-
tions

Check ambient temperat-
ure

Check wiring

Replace device

[Er21] / [SHRt]

2)

Short circuit at OutA/“Puls”

Eliminate short circuit

[Er22] / [SHRt]

2)

Short circuit at OutB

Eliminate short circuit

[Err] / [bUSY]

OutA/“Puls” is switched active
in the device sensor

Check device settings

[Err] / [Id]

Device ID error, devices do not
have the same design

When replicating, use sensor
with the same type flow rate
measurement range (same
device ID)

[Err] / [COM]

IO-Link® communication error

Check settings of the
device sensor

Check line

1) Display flashes red
2) Display illuminates red

Tab. 18

12

Disassembly

1. Turn off energy source and compressed air.
2. Separate connections from the sensor.
3. Loosen the mountings.

13

Disposal

ENVIRONMENT!

Send the packaging and product for environmentally sound recycling in accord-
ance with the current regulations 

è

 www.festo.com/sp.

14

Technical data

General

Approvals

RCM compliance mark

CE marking (declaration of conformity

è

 www.festo.com/sp)

In accordance with EU EMC Directive
In accordance with EU RoHS Directive

Information on materials

RoHS-compliant

Tab. 19 General

Input signal/measuring element

Measured variable

Volumetric flow rate, mass flow rate

Flow direction

Unidirectional, bidirectional

Measuring principle

Thermal

Warm-up time

[min]

10

Method of measurement

Heat transfer

Operating pressure

[bar]

–0.9 … 10

Operating pressure

[kPa]

–90 … 1000

Operating medium

Compressed air according to ISO 8573-1:2010 [6:4:4],
nitrogen, argon

Temperature of medium

[°C]

0 … 50

Ambient temperature

[°C]

0 … 50

Nominal conditions for determination of
the accuracy specification.

Operating pressure at output: 0 kPa relative

Medium and ambient temperature: 23°C

Analogue output: voltage with 20 kΩ load

Switching output: load current in the switched
status 5 mA

Mounting position: horizontal, display upwards

Inflow: 

è

 7.2 Inlet situation

Tab. 20 Input signal/measuring element

Flow rate measuring
range [l/min]

­0.1

­0.5

­1

­5

­10

­50

­100

­200

Start value

0.002

0.01

0.02

0.1

0.2

1

2

4

End value

0.1

0.5

1

5

10

50

100

200

Tab. 21 Flow rate measuring range unidirectional or bidirectional

Flow rate measuring
range [l/min]

­0.1B ­0.5B ­1B

­5B ­10B ­50B ­100B ­200B

Start value

–0.002

–0.01

–0.02 –0.1

–0.2

–1

–2

–4

End value

–0.1

–0.5

–1

–5

–10

–50

–100

–200

Tab. 22 Flow rate measuring range bidirectional, additional

Содержание SFAH

Страница 1: ...dustry sector 3 Further information Accessories www festo com catalogue Spare parts www festo com spareparts 4 Service Contact your regional Festo contact person if you have technical questions www fe...

Страница 2: ...of a signal value for constancy If the applied sig nal is constant in the range between SP Lo and SP Hi the reference signal qRef is automatically determined The result is a switching operation at the...

Страница 3: ...mounting Secure the SFAH to the plate by using screws of suitable length Hole diameter max 3 mm Tightening torque 0 5 Nm Lateral plate mounting Fig 5 Lateral plate mounting 1 Mount H rail mounting on...

Страница 4: ...Commissioning 8 1 LCD display 1 Main display e g measurement value 2 Status information 3 Lower display e g unit 4 Output display Fig 9 LCD display Example for LCD display Meaning Output display OutA...

Страница 5: ...ss the A pushbutton twice The first parameter set is displayed Fctn flashes for OutA or SP flashes for Puls 2 To display each of the following parameters press the A pushbutton Fig 10 The averaged flo...

Страница 6: ...n regarding the para meters same device ID The master sensor is connected with the device sensor Fig 11 Parameterisation of the device sensor must not be blocked via IO Link The device sensor is in an...

Страница 7: ...Repeat teaching Incorrect standard condition set for volumetric flow rate Correct standard condition Device defective Replace device Indicator or switching output does not react as expected Parameter...

Страница 8: ...ical connections Tab 27 Electronics Electromechanics M8 L1 Connection type Plug Connection technology M8x1 A coded according to EN 61076 2 104 L1J Number of pins wires 4 Max connecting cable length m...

Отзывы: