SDE1−...
Festo SDE1−... 0511e English
56
11
Troubleshooting
Fault
Possible cause
Remedy
No display
No power supply or no
permitted operating voltage
Switch on power supply /
maintain permitted operating
voltage range
Connections swapped
(incorrect polarity)
Wire the SDE1−... as shown in
the circuit diagram
SDE1−... defective
Return SDE1−... to Festo
Incomplete display
Display defective
Return SDE1−... to Festo
Incorrect pressure
display
Pressure failure
Eliminate pressure failure
display
Pneumatic connections
swapped (only with ...−..Q4−..)
Connect tubing in accordance
with the chapter Pneumatic
installation".
SDE1−... operated with
non−permitted medium
Replace the SDE1−... and
operate only with
compressed air
Pressure indicator
flashes
Excess pressure
(within permitted range)
Keep to permitted pressure
range
Excess pressure over
maximum permitted value
(device damaged)
Replace SDE1−...
Outputs do not switch
according to settings
Short circuit/overload at
relevant output
Eliminate short circuit/
overload
SDE1−... defective
Return SDE1−... to Festo
Settings cannot be
edited (lock" on the
display)
Access protection active
Enter the security code
(if forgotten, reset as
described in Operation")
Fig.19
Содержание SDE1 Series
Страница 30: ...SDE1 Festo SDE1 0511e Deutsch 30 Bild 23 EDIT Modus ...
Страница 31: ...SDE1 Festo SDE1 0511e Deutsch 31 1 1 1 Nur bei Typ SDE1 L UP Taste A oder DOWN Taste B erneut drücken ...
Страница 32: ...SDE1 Festo SDE1 0511e Deutsch 32 Bild 24 TEACH Modus ...
Страница 60: ...SDE1 Festo SDE1 0511e English 60 Fig 23 EDIT mode ...
Страница 61: ...SDE1 Festo SDE1 0511e English 61 1 1 1 Only with type SDE1 L press UP button A or DOWN button B again ...
Страница 62: ...SDE1 Festo SDE1 0511e English 62 Fig 24 TEACH mode ...
Страница 63: ...SDE1 Festo SDE1 0511e 63 de Lochbilder Adapterplatte en Hole pattern on adapter plate ...