background image

4

Festo — CPX-AP-A-8DO-M12-5P — 2022-07

About this document

1

About this document

1.1

Applicable documents

All available documents for the product 

è

  www.festo.com/sp.

Document

Table of contents

Operating instructions for automation system
CPX-AP-A

Instruction manual and important information on
assembly, electrical installation and maintenance
tasks as well as description of the automation
system CPX-AP-A

Tab. 1: Applicable documents

1.2

Product version

This document refers to the following product versions:

Product

Version

CPX-AP-A-8DO-M12-5P

Digital output module CPX-AP-A-8DO-M12-5P from revision 1

Tab. 2: Product version

The product version can be determined from the product labelling.

There may be an updated version of this document for this or later product versions

è

  www.festo.com/sp.

1.3

Product labelling

The product labelling and the Data Matrix Code are printed on the housings of the modules. Scanning
the Data Matrix Code with an appropriate device opens the Festo Internet page with documents
appropriate for the product. Alternatively, the Product Key (11-digit alphanumeric code on the product
labelling) can be entered in the search field 

è

  www.festo.com/sp.

1.4

Specified standards

Version

IEC 60204-1:2016-10

IEC 61131-2:2017-08

IEC 60364-4-41:2005-12

Tab. 3: Standards specified in the document

Содержание CPX-AP-A-8DO-M12-5P

Страница 1: ...CPX AP A 8DO M12 5P Digital output module Operating instruc tions 8160729 2022 07 8160731...

Страница 2: ...Translation of the original instructions...

Страница 3: ...ns 5 2 2 Intended use 5 2 3 Training of qualified personnel 5 3 Additional information 5 4 Product overview 6 4 1 Structure 6 4 1 1 Product design 6 4 1 2 LED displays 6 4 1 3 Connecting elements 7 4...

Страница 4: ...tput module CPX AP A 8DO M12 5P from revision 1 Tab 2 Product version The product version can be determined from the product labelling There may be an updated version of this document for this or late...

Страница 5: ...ollows Use only in an industrial environment Outside industrial environments e g in commercial and residential mixed use areas it may be necessary to take measures to suppress radio interference Use o...

Страница 6: ...t design 1 Connection for outputs 0 1 X0 2 Connection for outputs 2 3 X1 3 Connection for outputs 4 5 X2 4 Connection for outputs 6 7 X3 5 LED displays 6 Inscription label optional 4 1 2 LED displays...

Страница 7: ...lly protected against short circuit or overload separately for each output If this fuse responds the power supply of the output is switched off the error is indicated by an LED on the module and repor...

Страница 8: ...scriptions specific to the host system ID Parameter Instances Data type Access1 Array size 246 Fieldbus serial number 1 UINT32 ro 791 Product key 1 CHAR ro 12 960 Firmware version 1 CHAR ro 30 20000 M...

Страница 9: ...Remedy Check connected load for correct function in particular for current consumption Check wiring Diagnos tics status Error 02 01 0016 33619990 Undervoltage in logic supply PS 24 V DC Undervoltage...

Страница 10: ...283556 Communication to AP master interrupted Diagnostics status Remedy Restart AP Master Check communication AP connecting cable Diagnos tics status Error 08 01 0130 134283568 Output process data wat...

Страница 11: ...fault clearance 11 ID hex dec Message Description 08 01 01A2 134283682 Device in emergency operation system state Remedy Restart system Update firmware to the latest version Contact Festo Service Dia...

Страница 12: ...g switching off load supply PL flashing red 0 5 Hz Module diagnostics active Degree of severity Warning e g parameterisation error Take appropriate remedial action e g check parameterisation red light...

Страница 13: ...active logic 1 Output sends logic 1 Off Output inactive logic 0 Output sends logic 0 Tab 9 LED status of output Diagnostics of output LED red Meaning Remedy Illuminated Short circuit overload at outp...

Страница 14: ...irect contact in accordance with IEC 60204 1 and IEC 60364 4 41 by the use of SELV PELV circuits Safe extra low voltage Protected extra low voltage Electromagnetic compatibility See declaration of con...

Страница 15: ...DC 1 Parallel connection of out puts Yes O0 to O3 O4 to O7 Protection against reverse voltage Max PL Limitation of inductive switch off voltage V Typically 16 Electrical isolation Between PS and PL Y...

Страница 16: ...2022 all rights reserved to Festo SE Co KG Copyright Festo SE Co KG 73734 Esslingen Ruiter Stra e 82 Deutschland Phone 49 711 347 0 Internet www festo com...

Отзывы: