Festo — CPX-AP-A-8DO-M12-5P — 2022-07
Technical data
15
Digital outputs
Number of outputs
8
Type in accordance with
IEC 61131-2
0.5 (24 V DC)
Cable length
[m]
Max. 30
Design
Positive logic (PNP)
Reverse polarity protection
Yes
Output current per channel
[A]
Max. 0.5
Lamp load per channel
channel
[W]
Max. 12
Voltage drop via output
[V DC]
£
1
Parallel connection of out-
puts
Yes, O0 to O3/O4 to O7
Protection against reverse
voltage
Max. PL
Limitation of inductive
switch-off voltage
[V]
Typically –16
Electrical isolation
Between PS and PL
Yes
Between the channels
No
Output short-circuit protection
Short-circuit protection
Electronic
Trigger level
[A]
,
0.5
Characteristic
Slow-blowing
Response after end of over-
load
No automatic recovery
Output delay with resistive load
Signal change from 0 to 1
[µs]
.
200
Signal change from 1 to 0
[µs]
.
200
Tab. 13: Digital outputs