10
Festo — CPX-AP-A-8DO-M12-5P — 2022-07
Diagnostics and fault clearance
ID hex (dec)
Message
Description
02 | 01 | 0106
(33620230)
Switch off load supply
PL 24 V DC
A switch-off of the load supply PL was detected. The cause
can be a deliberate shutdown by the emergency stop.
Remedy
–
Check if the emergency stop was activated.
–
Check load supply PL.
Diagnos-
tics
status
Information
02 | 01 | 013F
(33620287)
Overvoltage in load
supply PL 24 V DC
Overvoltage in load supply PL 24 V DC
Remedy
–
Check load supply PL.
Diagnos-
tics
status
Error
08 | 01 | 0124
(134283556)
Communication to AP
master interrupted
Diagnostics status
Remedy
–
Restart AP Master.
–
Check communication AP connecting cable.
Diagnos-
tics
status
Error
08 | 01 | 0130
(134283568)
Output process data
watchdog of the AP
module expired
Output process data watchdog of the AP module expired
Remedy
–
Restart AP system.
–
Check the cable.
Diagnos-
tics
status
Error
08 | 01 | 0131
(134283569)
Input process data
watchdog of the AP
module expired
Input process data watchdog of the AP module expired
Remedy
–
Restart AP system.
–
Check the cable.
Diagnos-
tics
status
Error
08 | 01 | 01A2
(134283682)
Device in emergency
operation system
state
System initialisation (module detection) has failed. The
system is in maintenance mode. There is no I/O function
available.