3.1.2 Selecting the power unit
WARNING
Use only power packs which guarantee reliable
electrical isolation of the operating voltages as per
IEC 742/EN 60742/VDE 0551 with at least 4 kV
isolation resistance. Switch power packs are per-
mitted, providing they guarantee reliable isolation as
per EN 60950/VDE 0805.
The current consumption of a CP system depends on
the number and type of components connected.
Recommendation.
•
Use a closed-loop power unit.
•
When selecting the power unit, check that it has suf-
ficient output. Calculate the total current consumption
according to the following table.
•
Connect the operating voltage for the valve coils
(pin 2) via EMERGENCY STOP.
The following table shows how to calculate the com-
plete current consumption for a CP system. The values
specified have been rounded up. Please refer to the
appropriate technical specifications for the current con-
sumption of the valves and modules.
Calculating
the current
consumption
3. Installation
3-8
CP... 9806A
Содержание Compact Performance System
Страница 1: ...Compact Performance CP system Installation and commissioning...
Страница 3: ...Part no 165 226 Title Manual Designation P BE CPSYS GB II CP 9806A...
Страница 12: ...Chapter 1 System overview 1 System overview CP 9806A 1 1...
Страница 33: ...1 System overview 1 22 CP 9806A...
Страница 34: ...Chapter 2 Fitting 2 Fitting CP 9806A 2 1...
Страница 46: ...Chapter 3 Installation 3 Installation CP 9806A 3 1...
Страница 64: ...Chapter 4 Commissioning 4 Commissioning CP 9806A 4 1...
Страница 82: ...Appendix A Technical appendix A Technical appendix CP 9806A A 1...
Страница 91: ...V Voltage connecting 3 14 selecting the cable 3 16 A Technical appendix A 10 CP 9806A...