1.3.1 Basic rules of addressing
– A CP node provides four strings with a total of 64
input addresses and 64 output addresses.
CP node
– A string occupies 16 input addresses and 16 output
addresses.
– The addresses are assigned fixed to the individual
strings and in ascending order.
String
number
Input addresses
(E = Input)
Output addresses
(A = Output)
0
E0...E15
A0...A15
1
E16...E31
A16...A31
2
E32...E47
A32...A47
3
E48...E63
A48...A63
– The assignment of addresses to the individual mo-
dules is therefore determined by the string to which
they are connected.
– The addresses of an unoccupied string at the end of
the complete address range can be used by other
fieldbus nodes, providing this supports the fieldbus
protocol used. Other unused addresses remain
reserved for later extensions to the CP system.