5. Diagnosis and error treatment
5-13
Festo P.BE-VIFB13-03-EN en 0003c
Stopping the test routine
1. Switch off the operating and load voltage supplies of the
terminal (pins 1 and 2).
2. Set the address selector switch and the DIL switch el-
ements to their original positions.
Please note:
If the yellow LED of the valves does not light up, this may be
caused by the following:
–
The LED or the solenoid coil is defective.
Type 04-B only:
–
The internal 0.315 A fuse in the sub-base is burnt out (see
Chapter 5.8).
Display of the valve terminal configuration
The LEDs POWER V or BUS ERROR show the number of input
or output bytes with the setting “Display of configuration
data”.
–
Stopping the test routine:
Operating voltage OFF
–
The “display of the configuration data” is continual.
–
The sequence of flashing signals is shown in the following
diagram.
Содержание 174335
Страница 2: ......
Страница 4: ...Contents and general instructions II Festo P BE VIFB13 03 EN en 0003c...
Страница 17: ...Summary of components 1 1 Festo P BE VIFB13 03 EN en 0003c Chapter 1...
Страница 26: ...1 Summary of components 1 10 Festo P BE VIFB13 03 EN en 0003c...
Страница 27: ...Fitting 2 1 Festo P BE VIFB13 03 EN en 0003c Chapter 2...
Страница 37: ...Installation 3 1 Festo P BE VIFB13 03 EN en 0003c Chapter 3...
Страница 66: ...3 Installation 3 30 Festo P BE VIFB13 03 EN en 0003c...
Страница 67: ...Commissioning 4 1 Festo P BE VIFB13 03 EN en 0003c Chapter 4...
Страница 123: ...Diagnosis and error treatment 5 1 Festo P BE VIFB13 03 EN en 0003c Chapter 5...
Страница 162: ...5 Diagnosis and error treatment 5 40 Festo P BE VIFB13 03 EN en 0003c...
Страница 163: ...Technical appendix A 1 Festo P BE VIFB13 03 EN en 0003c Appendix A...
Страница 177: ...Index B 1 Festo P BE VIFB13 03 EN en 0003c Appendix B...
Страница 178: ...B Index B 2 Festo P BE VIFB13 03 EN en 0003c...