4. Commissioning
4-56
Festo P.BE-VIFB13-03-EN en 0003c
Examples
Example 1:
Valve terminal with 60 inputs and 26 solenoid coils. Configur-
ation:
Configured
I/Os
Number of
bytes
Consistency
Identifier
60 inputs
8 (DI)
1 Byte
023
32 outputs
4 (DO)
1 Byte
035
Example 2:
Valve terminal with 44 inputs, 16 solenoid coils, 8 electrical
outputs. Configuration:
Configured
I/Os
Number of
bytes
Consistency
Identifier
44 inputs
+ 4 status bits
6 (DI)
1 Byte
021
16 solenoid
coils
8 outputs
3 (DO)
1 Byte
034