28
R410A PROTECTION DEVICES
Protection devices HIGH PRESSURE
LEVEL
1
Device
High pressure automatic switch
Trip out (barg)
41.0
Trip in (barg)
29.5
connected to
electronic controller
effect
stop the compressors and the fans of that circuit
reset *
YES by keyboard if the high pressure switch has trip-in and after the solution of the problem that generates the alarm
*: For more details refers to section monitoring basic system.
LEVEL
1
Device
Low pressure automatic switch
Trip out (barg)
4 bar (IR, IP unit in cooling mode) 2 bar (BR,BP, IP unit in heating mode)
Trip in (barg)
6 bar (IR, IP unit in cooling mode) 4 bar (BR,BP, IP unit in heating mode)
connected to
electronic controller
effect
stop the compressors of that circuit
reset *
YES by keyboard if the low pressure switch has trip-in and after the solution of the problem that generates the alarm
Protection devices LOW PRESSURE
*: For more details refers to section monitoring basic system.