ALARMS
Space heating capacity shortage at low outdoor temperatures
POSSIBLE CAUSES
CORRECTIVE ACTION
Backup heater operation is
not activated.
Check that the "OTHER HEATING SOURCE/ BACKUP HEATER"is enabled, see "10.7 Field settings" Check whether or not the
thermal protector of the backup heater has been activated (refer to 9.2.3 Switch box main components (door 2), "Backup heater
thermal protector" for location of the reset button).Check if booster heater is running, the backup heater and booster heater can’t
operate simultaneously.
Too much heat pump
capacity is used for
heating domestic hot
water (applies only to
installations with a
domestic hot water tank).
Check that the 't_DHWHP_MAX' and “t_ DHWHP_RESTRICT” are configured appropriately:
• Make sure that the 'DHW PRIORITY' in the user interface is disabled.
• Enable the”T4_TBH_ON “in the user interface/FOR SERVICEMAN to activate the booster heater for domestic water heating.
When a safety device is activated, an error code will be displayed on the user interface.
A list of all errors and corrective actions can be found in the table below.
Reset the safety by turning the unit OFF and back ON.
In case this procedure for resetting the safety is not successful, contact your local dealer.
Table. 8 - ALARM TABLE - REMOTE CONTROL
Error
code
Malfunction or protection
Failure cause and Corrective action
E0
Flow switch error(E8 displa-
yed 3 times)
1.The wire circuit is short connected or open.
Reconnect the wire correctly.
2.Water flow rate is too low.
3. Water flow switch is failed, switch is open or close continuously, change the water flow switch.
E1
Phase sequence fault (only
for three-phase unit)
1.Check the power supply cables should be connected stable, to avoid phase loss.
2.Check the power supply cables sequence, change any two cables sequence of the three power supply cables.
E2
Communication error betwe-
en wired controller and unit
1.wire doesn’t connect between wired controller and unit. Connect the wire.
2.Communication wire sequence is not right.
Reconnect the wire in the right sequence.
3. Whether there is a high magnetic field or high power interfere, such as lifts, large power transformers, etc..
To add a barrier to protect the unit or to move the unit to the other place.
E3
The backup heater exchan-
ger outlet water temperature
sensor (T1) error
1. The T1 sensor connector is loosen. Reconnect it.
2.The T1 sensor connector is wet or there is water in. Remove the water, make the connector dry. Add waterproof
adhesive.
3.The T1 sensor failure, change a new sensor.
E4
The domestic hot water tem-
perature sensor (T5) error
1.The T5 sensor connector is loosen. Reconnect it.
2.The T5 sensor connector is wet or there is water in. Remove the water, make the connector dry. Add waterproof
adhesive.
3.The T5 sensor failure, change a new sensor.
E5
The condenser outlet refri-
gerant temperature sensor
(T3)error.
1. The T3 sensor connector is loosen. Reconnect it.
2.The T3 sensor connector is wet or there is water in. Remove the water, make the connector dry. Add waterproof
adhesive.
3. The T3 sensor failure, change a new sensor.
E6
The outdoor air temperature
sensor (T4) error.
1. The T4 sensor connector is loosen. Reconnect it.
2.The T4 sensor connector is wet or there is water in. Remove the water, make the connector dry. Add waterproof
adhesive.
3. The T4 sensor failure, change a new sensor.
E8
Water flow failure
Check that all shut off valves of the water circuit are completely open.
1 Check if the water filter needs cleaning.
2 Refer to "9.4 Charging water"
3 Make sure there is no air in the system (purge air).
4 Check on the manometer that there is sufficient water pressure. The water pressure must be >1 bar.
5 Check that the pump speed setting is on he highest speed.
6 Make sure that the expansion vessel is not broken.
7 Check that the resistance in the water circuit is not too high for the pump (refer to "Setting the pump speed" ).
8 If this error occurs at defrost operation (during space heating or domestic water heating), make sure that the
backup heater power supply is wired correctly and that fuses are not blown.
9 Check that the pump fuse and PCB fuse are not blown.
E9
Suction pipe sensor (Th)
error
1. The Th sensor connector is loosen. Re connect it.
2.The Th sensor connector is wet or there is water in. Remove the water, make the connector dry. Add waterproof
adhesive.
3. The Th sensor failure, change a new sensor.
Th intervention <15 ° C for 15 min, automatic reset Th> 27 ° C
Содержание OMNIA HYBRID C
Страница 34: ...34 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU 7 2 Menu structure ...
Страница 35: ...35 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU DHW mode is setting OFF ...
Страница 36: ...36 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU ...
Страница 51: ...51 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU ...
Страница 52: ...52 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU REMOTE CONTROLLER FOR SERVICEMAN MENU ...
Страница 53: ...53 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU U ...
Страница 100: ...100 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Principle scheme ...
Страница 101: ...101 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Electronic heat pump board ...
Страница 102: ...102 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Wiring board ...
Страница 113: ...113 EN Cod 3541T090 Rev 00 06 2019 ...
Страница 114: ...114 EN Cod 3541T090 Rev 00 06 2019 ...
Страница 115: ...115 EN Cod 3541T090 Rev 00 06 2019 ...