DOMINA PLUS F 24 - 30 E
FERELLA EXTRA F 24 - 30 MEL
Version - 09.2002
Position
Post-circulation time adjustment.
Setting: 6min.
(range 1 to 255 min.)
5
6
This parameter makes it possible to keep the timer-thermostat functions of the remote control even with zone
systems. The sliding temperature adjustment is set and controlled via the boiler control panel and the main card.
The remote control loses its room modulation function.
If the boiler is used without the remote control the boiler operation corresponds to selecting 1. But it will not
be necessary to set the value to 1.
Position
Selection of modulating timer-thermostat/
timer-thermosat On/Off for zone systems
0 = Modulating
1 = On/Off zone systems
2
0
Position
Natural gas / LPG selection
0 = Natural gas
1 = LPG
3
0
Selecting the "post-circulation" parameter, after a call for heating, the pump continues to work for the post-
circulation time (6 min.).
Whereas, selecting "continuous pump," after a call for heating, the pump works constantly.
The pump is always turned off during tap water operation.
Position
Pump post-circulation / pump continuous
operation selection
0 = Post-circulation
1 = Continuous pump
4
0