4. Unit self-diagnosis
Fault Diagnosis
The boiler is equipped with an advanced self-diagnosis system. In the event of trouble with the boiler, the display
will show the fault code. There are faults that in order to restore operation it suffices to press RESET
; if
the boiler fails to start, it is necessary to resolve the fault indicated by the operating LEDs (faults from 1 to 25);
other faults cause temporary shutdowns that are automatically reset as soon as the value comes back within
the boiler's normal working range (faults from 30 to 39). When the boiler starts functioning normally again, the
display stops blinking and the fault code disappears.
Boiler shutdown
Low system pressure
LED
Make sure that the gas cocks ahead of the boiler and on the
meter are open.
Press button 1 "Reset".
In case of repeated shutdowns, contact the nearest assistance
centre
Fill the system to 1-1.5 bar cold by means of the specific cock
located in the boiler.
Close the cock after use.
Fault
Cure
DISPLAY
steady light
Steady light
Blinking light
steady light
Fault
Possible cause
No burner ignition
No gas
Detection or ignition
electrode fault
Defective gas valve
Card trouble
Interference caused by the
electric mains
Card microprocessor
damaged
Safety thermostat trips
Damaged thermostat
No water circulation in the
system
Air pressure switch (with
contacts closed before
turning on the fan)
Air pressure switch contact
closed
Incorrect wiring to the air
pressure switch
Display
Air pressure switch (fails to
close the contacts within
60 sec. of turning on the fan)
Air pressure switch contact
open
Incorrect wiring to the air
pressure switch
Wrong diaphragm
Flue not correctly sized
No burner ignition
Incorrect gas valve
connection
Broken wiring of gas valve
From
to
Fault on the flame control
circuit
Interference caused by
the electric mains
Card microprocessor
damaged
Air pressure switch (closes
and opens the contacts
5 times within 60 sec. of
the ignition phase)
Wrong diaphragm
Flue not correctly sized
Fault
Possible cause
Heating sensor fault
Sensor damaged
Incorrect wiring
(short-circuit)
Heating sensor fault
Sensor damaged
Incorrect wiring
(broken)
Tap water sensor fault
Sensor damaged
Incorrect wiring
(short-circuit)
Display
Tap water sensor fault
Sensor damaged
Incorrect wiring
(broken)
Mains voltage
The mains voltage is
under 185 VAC
Mains frequency
The frequency exceeds the
tolerance of +/- 5%
Card trouble
Defective hardware
Low system pressure
System empty
Water pressure switch not
connected or damaged
RESET key jammed
ON/OFF button
damaged
External sensor fault
Damaged sensor
Sensor wiring
shorted
List::