DIVAtop ST C
35
EN
Accessing electrical terminal block
After removing the boiler front panel (see fig. 22) the terminal block can be accessed for
connection of the external probe (detail 1 - fig. 19), the room thermostat (detail 3 - fig. 19)
or the remote timer control (detail 2 - fig. 19).
fig. 19 - Accessing the terminal block
3.6 Air/fume ducts
The diameter of the flue connection pipe must not be less than that of the connection on
the anti-backflow device. Starting from the anti-backflow device it must have a vertical
section at least 50 cm long. Current standards must be complied with regarding sizing
and installation of the flues and connection pipe.
B
The boiler is also equipped with a safety device (fume thermostat) that stops
operation of unit in case of inadequate draught of obstruction of the flue. This
device must never be tampered with or deactivated.
4. SERVICE AND MAINTENANCE
All adjustment, conversion, start-up and maintenance operations described below must
only be carried out by Qualified Personnel (meeting the professional technical require-
ments prescribed by current regulations) such as those of the Local After-Sales Techni-
cal Service.
FERROLI
declines any liability for damage and/or injury caused by unqualified and un-
authorised persons tampering with the unit.
4.1 Adjustments
Gas conversion
The unit can operate on natural gas or LPG and is factory-set for use with one of these
two gases, as clearly shown on the packing and on the dataplate. Whenever a different
gas to that for which the unit is preset has to be used, a conversion kit will be required,
proceeding as follows:
1.
Replace the nozzles at the main burner, fitting the nozzles specified in the technical
data table in , according sec. 5.3 to the type of gas used
2.
Modify the parameter for the type of gas:
•
put the boiler in standby mode
•
Press the
RESET
button (detail 8 -fig. 1) for 10 seconds: the display shows
"
TS
" flashing
•
press the
RESET
button (detail 8 - fig. 1): the display shows "
P01
.
•
Press the DHW buttons (details 01 or 2 -
fig. 1) to set parameter
00 (for nat-
ural gas) or 1 (for LPG).
•
Press the RESET button (detail 8 - fig. 1) for 10 seconds.
•
the boiler will return to standby mode
3.
Adjust the minimum and maximum pressures at the burner (ref. relevant para-
graph), setting the values given in the technical data table for the type of gas used
4.
Apply the sticker contained in the conversion kit, near the dataplate as proof of the
conversion.
TEST mode activation
Press the heating buttons
+/-
(details 3 and 4 - fig. 1
) at the same time for 5 seconds
to activate the
TEST mode. The boiler lights at the maximum heating power set as de-
scribed in the following section.
The heating symbol (detail 24 - fig. 1) and DHW symbol (detail 12 - fig. 1) flash on the
display; the heating power and lighting power will be displayed alongside.
fig. 20 - TEST mode (heating power = 100%)
To deactivate the TEST mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes.
Pressure adjustment at the burner
Since this unit has flame modulation, there are two fixed pressure settings: minimum and
maximum, which must be those given in the technical data table according to the type
of gas.
•
Connect a suitable pressure gauge to the pressure point
"B"
downstream of the
gas valve.
•
Remove the protection cap
"D"
.
•
Operate the boiler in
TEST
mode.
•
Adjust the maximum pressure setting by turning the screw
"G"
clockwise to in-
crease the pressure and anticlockwise to decrease it.
•
Disconnect one of the two fastons
"C"
from modureg
"F"
on the gas valve.
•
Adjust the minimum pressure setting by turning the screw
"E"
clockwise to increase
the pressure and anticlockwise to decrease it.
•
Turn the burner on and off, checking that the minimum pressure value remains sta-
ble.
•
Reconnect the faston
"C"
detached from the modureg
"F"
on the gas valve
•
Check that the maximum pressure has not changed
•
Refit the protection cap
"D
.
•
To end the
TEST
mode, repeat the activation sequence or wait 15 minutes.
A
After checking or adjusting the pressure, make sure to seal the adjust-
ment screw with paint or a specific seal.
fig. 21 - Gas valve
to
Pressure point upstream
B
Pressure point downstream
C
Modureg electrical connection
D
Protective cap
E
Minimum pressure adjustment
F
Modureg
G
Minimum pressure adjustment
I
Gas valve electrical connection
M
Pressure gauge
R
Gas outlet
S
Gas inlet
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons
(details 3 and 4 -
fig. 1) to increase or decrease the power (min. = 00
- max. = 100). Press the
RESET
button within 5 seconds and the max. power will remain
that just set. Exit TEST
mode (
see sec. 4.1).
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 4.1). Press the
DHW buttons
(details 1 and 2 -
fig. 1) to increase or decrease the power (min. = 00 -
max. = 60). Press the
RESET
button within 5 seconds and the ignition powerwill remain
that just set. Exit
TEST
mode (see sec. 4.1).
4.2 System start-up
B
Checks to be made at first ignition, and after all maintenance operations that
involved disconnecting from the systems or an intervention on safety devices
or parts of the boiler:
Before lighting the boiler
•
Open any on-off valves between the boiler and the systems.
•
Check the tightness of the gas system, proceeding with caution and using a soap
and water solution to detect any leaks in connections.
•
Check the correct preloading of the expansion tank (ref. sec. 5.3)
•
Fill the water system and make sure that all air contained in the boiler and the sys-
tem has been vented by opening the air vent valve on the boiler and any vent valves
on the system.
•
Make sure there are no water leaks in the system, hot water circuits, connections or
boiler.
•
Check the correct connection of the electric system and the functioning of the earth
system. l
•
Check that the gas pressure value for heating is as required.
•
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
eco
comfort
m
o
d
e
r e s et
eco
bar
+
M
D
E
G
C
F
F
I
B
A
R
S
cod. 354
0S161
- Rev. 00 -
10
/2013
Содержание DIVAtop ST C
Страница 78: ......
Страница 79: ......
Страница 80: ...FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona ITALY www ferroli it ...