4.3 Maintenance
Opening the front panel
To open the boiler casing:
1.
Partially undo the screws
A
(see fig. 24).
2.
Pull the panel
B
outwards and release it from the upper fastenings.
B
Before carrying out any operation inside the boiler, disconnect the power and
close the gas cock upstream
fig. 24 - Front panel opening
B
On this unit, the casing also acts as a sealed chamber. After any opera-
tion involving opening the boiler, carefully check the correct refitting of
the front panel and its seal.
Proceed in reverse order to refit the front panel. Make sure it is correctly hooked to the
upper fastenings and is correctly positioned at the sides. When tightened, the head of
screw "A" must not be below the lower fold (see fig. 25).
fig. 25 - Correct position of front panel
Periodical check
To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly inspection, providing for the following checks:
7KHFRQWURODQGVDIHW\GHYLFHVJDVYDOYHIORZPHWHUWKHUPRVWDWVHWFPXVWIXQF
tion correctly
7KHIXPHH[KDXVWFLUFXLWPXVWEHSHUIHFWO\HIILFLHQW
7KHVHDOHGFKDPEHUPXVWEHWLJKW
7KHDLUIXPHHQGSLHFHDQGGXFWVPXVWEHIUHHRIREVWUXFWLRQVDQGOHDNV
7KHEXUQHUDQGH[FKDQJHUPXVWEHFOHDQDQGIUHHRIGHSRVLWV)RUSRVVLEOHFOHDQLQJ
do not use chemical products or wire brushes
7KHHOHFWURGHPXVWEHSURSHUO\SRVLWLRQHGDQGIUHHRIVFDOH
7KHJDVDQGZDWHUV\VWHPVPXVWEHWLJKW
7KHZDWHUSUHVVXUHLQWKHFROGZDWHUV\VWHPPXVWEHDERXWEDURWKHUZLVHEULQJ
it to that value
7KHFLUFXODWLQJSXPSPXVWQRWEHEORFNHG
7KHH[SDQVLRQWDQNPXVWEHILOOHG
7KHJDVIORZDQGSUHVVXUHPXVWFRUUHVSRQGWRWKDWJLYHQLQWKHUHVSHFWLYHWDEOHV
7KHFRQGHQVDWHHYDFXDWLRQV\VWHPPXVWEHHIILFLHQWZLWKQROHDNDJHRUREVWUXF
tions
7KHWUDSPXVWEHIXOORIZDWHU
4.4 Troubleshooting
Diagnostics
In case of operation faults or problems, the display flashes and the fault identification
code appears.
There are faults that cause permanent shutdown (marked with the letter “
A
”): to restore
operation just press the
reset
button (detail 6 -fig. 1) for 1 second or RESET on the op-
WLRQDOUHPRWHWLPHUFRQWUROLILQVWDOOHGLIWKHERLOHUIDLOVWRVWDUWLWLVQHFHVVDU\WRILUVWO\
eliminate the fault.
Faults marked with the letter “
F
” cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 8 - List of faults
A
A
B
A
OK
NO
Fault code
Fault
Possible cause
Cure
A01
No burner ignition
No gas
Check the regular gas flow to the
boiler and that the air has been elimi-
nated from the pipes
Ignition/detection elec-
trode fault
Check the wiring of the electrode and
that it is correctly positioned and free
of any deposits
Faulty gas valve
Check the gas valve and replace it if
necessary
Insufficient gas supply
pressure
Check the gas supply pressure
Trap blocked
Check the trap and clean it if neces-
sary
A02
Flame present signal
with burner off
Electrode fault
Check the ionisation electrode wiring
Card fault
Check the card
A03
Overtemperature pro-
tection intervention
Heating sensor damaged
Check the correct positioning and
operation of the heating sensor
No water circulation in
the system
Check the circulating pump
Air in the system
Vent the system
A04
)XPHH[WUDFWLRQGXFW
safety device interven-
tion
Fault F07 generated 3
times in the last 24 hours
See fault F07
A05
Fan protection activated
Fault F15 generated for 1
hour (consecutive)
See fault F15
A06
No flame after ignition
stage (6 times in 4 min-
utes)
Ionisation electrode fault Check the position of the ionisation
electrode and replace it if necessary
Flame unstable
Check the burner
Gas valve Offset fault
Check the Offset adjustment at mini-
mum power
air/fume ducts obstructed
Remove the obstruction from the flue,
IXPHH[WUDFWLRQGXFWVDQGDLULQOHW
and terminals
Trap blocked
Check the trap and clean it if neces-
sary
F07
High fume temperature
The fume probe detects
DQH[FHVVLYHWHPSHUD
ture
&KHFNWKHH[FKDQJHU
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F12
DHW sensor fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F13
Fume probe fault
Probe damaged
Check the wiring or replace the fume
probe
Wiring shorted
Wiring disconnected
F14
Delivery sensor 2 fault
Sensor damaged
Check the wiring or replace the sen-
sor
Wiring shorted
Wiring disconnected
F15
Fan fault
No 230V power supply
Check the 3-pin connector wiring
Tachometric signal inter-
rupted
Check the
-pin connector wiring
Fan damaged
Check the fan
F34
Supply voltage under
170V
Electric mains trouble
Check the electrical system
F35
Faulty mains frequency
Electric mains trouble
Check the electrical system
F37
Incorrect system water
pressure
Pressure too low
Fill the system
Water pressure switch
damaged or not con-
nected
Check the sensor
42
EN
BLUEHELIX PRO S 32C
cod. 3541F842 - Rev. 00 - 11/2018