cod. 3541V691 - Rev. 00 - 04/2022
b29
Restore Factory Values
See ”* Restore Factory Values” on page 37 .
0
P30
Heating ramp
10÷80
(ex. 10=20°C/min, 20=12°C/min, 40=6°C/min, 80=3°C/min)
40
P31
Heating standby time
0 ÷ 10 minutes
4
P32
Heating Post-Circulation
0 ÷ 255
(Multiply the value by 10. Example
15 x 10 = 150 seconds
)
15
P33
Pump operation
0
= Continuous pump (active only in winter mode)
1
= Modulating pump
1
P34
Pump modulation DeltaT
0 ÷ 40°C
20
P35
Modulating pump min. speed
30 ÷ 100%
30
P36
Modulating pump start speed
90 ÷ 100%
90
P37
Modulating pump max. speed
90 ÷ 100%
100
P38
Pump deactivation temperature
during Post-Circulation
0 ÷ 100°C
55
P39
Pump activation hysteresis tem-
perature during Post-Circulation
0 ÷ 100°C
25
P40
Heating user max. setpoint
20 ÷ 90°C
80
P41
Max. output in heating
0 ÷ 100%
24 kW =
80
28 kW =
85
34 kW =
90
P42
Burner shutdown in DHW
0
= Fixed
1
= Linked to setpoint
2
= Solar
0
P43
Comfort mode activation tempe-
rature
0 ÷ 80°C
40
P44
Comfort mode deactivation hys-
teresis
0 ÷ 20°C
20
P45
DHW standby time
30 ÷ 255 seconds
120
P46
DHW user max. setpoint
40 ÷ 65°C
55
P47
DHW pump Post-Circulation
0 ÷ 255 seconds
30
P48
Max. output in DHW
0 ÷ 100%
100
P49
Not implemented (b01=2)
--
--
P50
Not implemented (b01=2)
--
--
P51
Burner shutdown in DHW
(P42=2)
0 ÷ 100
OFF = DHW user se P51
10
P52
Burner ignition in DHW (P42=2)
0 ÷ 100
ON = DHW user setpoint - P52
10
P53
Solar standby time
0 ÷ 255 seconds
10
P54
System pre-circulation time in
heating
0 ÷ 60 seconds
30
P55
System filling mode
0
= Disabled
1
= Automatic
0
P56
Minimum system pressure limit
value
0-8 bar/10 (Only for boilers with water pressure sensor)
4
P57
System nominal pressure value
5-20 bar/10 (Only for boilers with water pressure sensor)
7
P58
Maximum system pressure limit
value
25-35 bar/10 (Only for boilers with water pressure sensor)
28
P59
Circulating pump deactivation
with OpenTherm
0 =
Circulating pump activated in heating
1 =
Circulating pump deactivated in heating with request from Open-
Therm only
0
P60
Frost protection power
0 ÷ 50% (0 = minimum)
0
P61
Minimum power
0 ÷ 50% (0 = minimum)
0
Index
Description
Range
Default