BlueHelix HiTech RRT C
26
EN
cod. 3541V691 - Rev. 00 - 04/2022
Connection with separate pipes
fig. 35- Examples of connection with separate pipes (
= Air /
= Fumes)
Table 6- Typology
For the connection of separate ducts, fit the unit with the following starting accessory:
fig. 36- Starting accessory for separate ducts
Before installation, make sure the maximum permissible length has not been exceeded by means of a simple calcula-
tion:
1. Establish the layout of the system of split flues, including accessories and outlet terminals.
2. Consult table 8 and identify the losses in m
eq
(equivalent m) of every component, according to the installation posi-
tion.
3. Check that the sum total of losses is less than or equal to the maximum permissible length in table 7.
Table 7- Max. length separate ducts
Type
Description
C1X
Wall horizontal exhaust and intake. The inlet/outlet terminals must be concentric or close enough to be subjected to similar wind
conditions (within 50cm)
C3X
Roof vertical exhaust and intake. Inlet/outlet terminals like for C12
C5X
Separate wall or roof intake and exhaust and in any case in areas with different pressures. The exhaust and intake must not be
located on opposite walls
C6X
Intake and exhaust with separately certified pipes (EN 1856/1)
B2X
Intake from installation room and wall or roof exhaust
IMPORTANT- THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
Max. permissible length
BlueHelix HiTech RRT 24 C =
80 m
eq
BlueHelix HiTech RRT 28 C =
70 m
eq
BlueHelix HiTech RRT 34 C =
70 m
eq
C
5x
C
3x
B
2x
C
1x
max 50 cm
80
100
80
60
cod. 041082X0