Detector Bases (2- and 4-Wire)

for Smoke and Electronic Heat Detectors

Installation Instructions

70.104

PURPOSE

This document provides instructions for mounting and wiring 2-Wire and 4-Wire Detector Bases that are used with the Smoke and Heat Detectors
listed in the table below. The table also indicates the Detector UL Compatibility Identifier Number in the CID column:

Model 

CID 

Description 

CPD-7051 

I51FE1 

Ionization Smoke Detector

 -

discontinued !! 

CPD-7051D 

I51FE1 

Ionization Smoke Detector

 -

discontinued !! 

CPD-7054 

I51FE1 

Ionization 

Advanced

 Smoke Detector (Open Area, Air Velocities 0-300 fpm)

 -

discontinued  !! 

CPD-7054D 

I51FE1 

Ionization 

Advanced

 Smoke Detector (Open Area, Air Velocities 0-500 fpm)

 -

discontinued  !! 

PSD-7155 

P55FE1 

Photoelectric Smoke Detector 

PSD-7155P 

P55FE1 

Photoelectric Smoke Detector 

PSD-7155D 

P55FE1 

Photoelectric Smoke Detector 

PSD-7156 

P56FE1 

Photoelectric Smoke Detector with 135°F Thermal Sensor 

PSD-7157

 

P55FE1 

Photoelectric

 Advanced

 Smoke Detector (Open Area, Air Velocities 0-300 fpm)

 - our standard !! 

PSD-7157D 

P55FE1 

Photoelectric

 Advanced

 Smoke Detector (Open Area, Air Velocities 0-4000 fpm) 

THD-7052 

P56FE1 

Heat Detector (135°F Fixed Temperature & 15°F Rate-Of-Rise) 

THD-7053 

P56FE1 

Heat Detector (135°F Fixed Temperature) 

Models CPD-705X

 are dual chamber Ionization Smoke Detectors that sense visible and invisible products of combustion.

Models PSD-715X

 are optical Photoelectric Smoke Detectors that respond to a broad spectrum of both flaming and smoldering fire conditions.

Models THD-705X

 are thermistor-based electronic Heat Detectors with a 135°F (57°C) Fixed Temperature set point. The Model THD-7052 has a

Rate-Of-Rise of temperature detection feature rated at 15°F (8.3°C) per minute.
All detectors are designed for 2-Wire and 4-Wire installation using the appropriate Detector bases. The Smoke and Heat Detectors are UL Listed for

Open Area Protection applications per UL 268 and UL 521 respectively. Detectors may also be installed in systems intended for Releasing Device

Service through use of a compatible Fire Alarm Control Panel.

DETECTOR BASES

MODELS
All the smoke and heat detector models identified above can be mounted on any base listed in the following table. The table also indicates the Base
UL Compatibility Identifier Number in the CID column.

Part No. 

Model 

CID 

Description 

70-501000-001 

2-WIRE 

FE51A 

2-W Base (Connects to circuit via screw terminals) 

70-501000-002 

2WRLT 

FE52A 

2-W Base w/ Remote LED & Test capabilities.  Connects to detection circuit via screw terminals. 
Minimum Alarm Current 15 mA @ 24 VDC. 

70-501000-005 

2WRB 

FE55A 

2-W base w/ 2WRM, Remote LED & Test capabilities. Connects to detection circuit via pigtail leads. 
Minimum Alarm Current 19 mA @ 24 VDC. 

70-501000-101

 

4WRB

 

N/A 

4-W base w/ 4WRM, Remote LED & Test capabilities. Connects to detection circuit via pigtail leads. 

Minimum Alarm Current 35 mA @ 24 VDC. 

70-500000-004 

2WRM 

N/A 

SPDT Relay for 2WRB Bases. Contacts rated 1.0 A, 30 VDC / 0.5 A, 125 VAC. 

70-500000-102 

4WRM 

N/A 

SPDT Relay for 4WRB Bases. Contacts rated 1.0 A, 30 VDC / 0.5 A, 125 VAC. 

70-501000-003 

MA-001 

MAFE1 

Mechanical Adapter allows CPD-705X & PSD-715X Detectors to physically connect to Base P/Ns 
70-201000-001, -002, -003, -005 & DH-22. 

ACCESSORIES

Accessories available for the bases identified above are listed in the following table.

Part No. 

Model 

CID 

Description 

29-116788-001 

-

N/A 

EOL Supervisory Relay 24 VDC 

06-117883-001 

-

N/A 

Smoke Detector Test Magnet 

70-200000-911 

RA-911 

N/A 

Remote Alarm Indicator 

70-200000-914 

RA-914 

N/A 

Remote Alarm Indicator w/ Smoke Detector Test Switch 

Содержание PSD Series

Страница 1: ...www fenwal direct eu www prevent a fire eu Smoke Detector PSD 2 4 Wire Units ...

Страница 2: ...re detection feature rated at 15 F 8 3 C per minute All detectors are designed for 2 Wire and 4 Wire installation using the appropriate Detector bases The Smoke and Heat Detectors are UL Listed fo Open Area Protection applications per UL 268 and UL 521 respectively Detectors may also be installed in systems intended for Releasing Devic Service through use of a compatible Fire Alarm Control Panel D...

Страница 3: ...iling obstructions high air exchange rates etc reduced spacing must be used to achieve adequat protection Computer rooms and other such installations may require spacing with a maximum of 200 square feet 18 6 m2 due to high air exchang rates For additional information consult NFPA 72 and the Fenwal Automatic Fire Detection Application Engineering Manual MC 402 Per UL Listing open area smoke detect...

Страница 4: ...m is required 6 Locate detectors on the downstream side of filters to sense fires in the filters However it should be noted that should the filters block the ai flow sufficient air flow may no longer be present for proper operation of the duct detector 7 Locate detectors whenever possible where they can be conveniently observed and readily serviced 8 Locate detectors in return air ducts ahead of m...

Страница 5: ...EST SWITCH 3 6 5 4 RA 914 REMOTE LED TEST SWITCH 3 6 5 4 END OF PANEL LINE DEVICE CIRCUIT Figure 3 Detector Using 2 Wire 2WRLT Base with Remote Indicator and Remote Test Switch Optio FIRST DETECTOR BASE LAST DETECTOR BASE AUX RELAY AUX AUX RELA RELAY Y RA 914 CONTACTS RA 914 RA 914 CONT CONTACTS ACTS REMOTE LED FORM C REMOTE REMOTE LED LED FORM FORM C C TO CONTROL PANEL INITIATING CIRCUIT 8 7 3 6 ...

Страница 6: ... been activated insert a smal screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counterclockwise see Figure 6 Use small bladed screwdriver 1 to push locking tab Test magnet 4 position 7 5 BREAK PLASTIC TAB BY TWISTING TOWARD CENTER OF BASE 1 BODY 2 CONTACT ARM 3 2 6 3 CONTACT SPRING 4 TERMINAL PLATE 5 JUMPER WIRE remove before installation...

Страница 7: ...ING FENWAL SERIES 70 201000 XXX BASE RETROFIT ADAPTER MA 001 P N 70 501000 003 CPD 705x PSD 715x THD 705x Figure 8 Installing Mechanical Adapter MA 00 DETECTOR TESTING AND SENSITIVITY METERIN FREQUENC Testing shall be performed upon installation of the detector and once a year thereafter as stated in NFPA 72 latest edition Smoke Detector sensitivit shall be metered within one year of installation ...

Страница 8: ... should alarm as indicated by stead illumination of the alarm indicator LEDs To return each detector to normal operation reset the control unit 4 Failure to alarm in test 3 indicates a defective detector requiring service 5 After taking appropriate corrective action re engage Alarm Signal Devices Releasing Devices and Extinguishing Systems and ensure that th entire system is returned back to norma...

Страница 9: ...y Module 70 500000 102 4WRM Spare 4 Wire Relay Module DETECTOR ACCESSORIE Part No Model Description 06 117883 001 Test Magnet 29 116788 001 EOL Supervisory Relay 70 200000 911 RA 911 Remote Alarm Indicator 70 200000 914 RA 914 Remote Alarm Indicator w Smoke Detector Test Switch 70 500000 002 ST 001 Smoke Detector Sensitivity Tester 70 500000 003 DST 003 Wireless Infrared Smoke Detector Sensitivity...

Отзывы: