FENWAL
Protection Systems
FSS/MC-519 Rev BC
Page 17
INDICATOR
TROUBLE
TROUBLE REPORTED
AC
AC power lost or outside range
PCB
Any of 12 possible PCB failures detected – see Table 3
DET 1 TBL*
Open circuit detected or trouble reported by FAB-3
DET1 SHT
en programmed for AND condition and using
.
Short circuit detected (wh
contact type detectors)
EED OPN
Open circuit detected
GFI
Ground fault detected
DET 3 TBL*
Open circuit detected due to opening of vent or low pressure switch
DET 2 TBL*
Open circuit detected or trouble reported by FAB-3
DET 2 SHT
en programmed for AND condition and using
Short circuit detected (wh
contact type detectors).
BAT
Low battery voltage, charger circuit failure or battery disconnected
FAB-13 AL*
k
Ω
missing across terminals 36 and 37
FAB-13 trouble reported or 1.2
BAT REV
Battery connections reversed
* Indicator may also illuminate if the control panel is disarmed.
Table 2: Trouble Indicators Definitions
T
CO E
TROUBLE AREA/COMPONENT
ROUBLE
D
1
Analog-to-Digital (A/D) Converter
2
50 V Power Supply
3
Detector 3 Alarm Test
4
5 V Power Supply
5
Detector 1 Alarm test
6
Detector 2 Alarm test
7 Front
Panel
8 EED
Current
9 EED
Capacitor
10
24 V Power Supply
11 Battery
Charger
12
0 V Reading Error by A/D converter
Table 3: PCB Trouble Code Definitions