User’s Manual Series TAS-1

FEMA ELECTRÓNICA - Page 6

Input

Code

M e s s a g e

0/650 Vdc

11

24

0/100 Vdc

11

23

0/10 Vdc

11

22

0/1 Vdc

11

11

0/100 mVdc

11

12

0/20 mVdc

11

13

4-ADVANCED CONFIGURATION

4.5- ALARM CONFIGURATION

4.2- INPUT SIGNAL : AC VOLTAGE

Codes : 11 XX

Menu : Hysteres and SM

Parameters configured on this menu apply to the 4 alarms

Input

Code              Message

0/650 Vac

11

32

0/100 Vac

11

31

0/1 Vac

11

14

0/100 mVac

11

15

The alarm configuration menu list several parameters to which we
must assign a value.

Numerical values are assigned with the number pads. Predefined
values (such as ON/OFF) are selected by selecting available
options with keys ‘

1

’, ‘

2

’ or ‘

3

’.

Validate with key ’

↵↵

↵↵

’ in order to access next parameter.

Hysteresis is applied to the
process of alarm deactivation*

Band alarm. Hysteresis is applied
to the process of alarm activation
and deactivation*

Hysteresis is applied to the
process of alarm activation.*

*The hysteresis points are defined on parameter HYST
for each alarm.

Security Mode activated on alarms
acting as «minimum»**

Securty Mode deactivated

**Output relay are inactive until the set point is

reached for the first time.

Parameters

    Values

Function

Menu : Alarm Parameters

Alarm Number

CODE

M e n u

Alarm 1

13

11

Alarm Parameters

Alarm 2

13

12

Alarm Parameters

Alarm 3

13

13

Alarm Parameters

Alarm 4

13

14

Alarm Parameters

General

13

15

Hysteresis and SM

Alarm1 working
Alarm1 not working

Alarm1 working as «maximum»
Alarm1 working as «minimum»

Setpoint for Alarm1
(expressed in display points)

Hysteresis value (max. 255)
(expressed in display points)

Delay on relay activation
(expressed in seconds)

Led is active when alarm is active
Led is active when alarm is inactive

Alarm text active
Alarm text inactive

Text associated with alarm led

Parameters     Values

  Description

4.1- INPUT SIGNAL : DC VOLTAGE

Codes : 11 XX

4.3- INPUT SIGNAL : DC CURRENT

Codes : 11 XX

Input

Code              Message

0/5 Adc

11

35

0/100 mAdc

11

33

4.4- INPUT SIGNAL : AC CURRENT

Codes : 11 XX

Input

Code              Message

0/5 Aac

11

41

0/100 mAac

11

34

Содержание TAS-1-IAC

Страница 1: ...CA Page 1 FEMA ELECTR NICA INTELLIGENT PANEL METERS Series TAS 1 Intelligent Panel Meters info fema es www fema es USER S MANUAL AC Current DC Current AC Voltages DC Voltages TAS 1 IAC TAS 1 IDC TAS 1...

Страница 2: ...ration 6 4 6 Manual Adjustment 7 4 7 Dealing with Errors 7 4 8 Advanced Indication 7 4 9 Blocking the Keypad 7 4 10 Resetting the system Default values 7 4 11 Messages and Errors 8 5 Configuring with...

Страница 3: ...Level Input Signal correction Key DP Decimal Point Position Key PROG Allows the introduction of the PROGRAMMING codes 4 digit codes as shown on page 4 These codes when validated activate different inp...

Страница 4: ...t 14 14 INPUT ONERR OFF ON 1 1 Visualization 14 13 DISPLAY NULL LAST 1 1 ON OFF 1 1 OFF ON 3 2 1 FIL 2 FIL 3 FIL 1 FILT A D Q N AVERA REAL 1 1 INPUT STEP XXXXX Alarm 1 Alarm 2 Alarm 3 Alarm 4 13 11 AL...

Страница 5: ...ion XXXX X 1 Press DP 2 message DP during 1 second Press 2 to fix decimal point position 2 To fix at other positions press 1 2 3 4 or 5 3 Validate changes pressinf message INPUT shows the configuratio...

Страница 6: ...m activation The hysteresis points are defined on parameter HYST for each alarm Security Mode activated on alarms acting as minimum Securty Mode deactivated Output relay are inactive until the set poi...

Страница 7: ...Code 14 11 Function Code 14 22 Function Resets the unit to the default manufacturing values It is needed to reconfirm the action by pressing INTRO after the message Acquisition Mode Real STEPValue 10...

Страница 8: ...recovers the normal working state when situation clears Errors Errors are associated with critical situtations which disable the hability to measure the signal The error remains active on display unt...

Страница 9: ...tion 32 000 points ENVIRONMENTAL DATA Working Temperature 0 50 C Storage Temperature 20 85 C Humidity 0 85 non condensaded MECAHNICALDATA Dimensions Standard 1 8 DIN 96 x 48 x 124 mm 3 78 x 1 89 x 4 8...

Страница 10: ...ot need to be readjusted most of the times in case of trouble with the input signal such as loop break or sensor break the analog output signal will exhibit always the same behaviour predefined by the...

Страница 11: ...essage ERROR Informs that at least one of the values is not correct and the whole configuration could not be applied Repeat the process from the begining 7 2 INSTALLING THE OPTION BOARDS The Option Bo...

Страница 12: ...mposed of 1 4 bits b0 0 Value contained on register 00 00H is an indication number b0 1 Value contained on register 00 00H is not an indication Word b4 b3 b2 b1 0 Reserved 3 Ovr 6 Con 9 MErr1 12 Reser...

Страница 13: ...acion MASTER and SLAVE ADDRESS 1 CHARACTER Instrument Address FUNCTION 1 CHARACTER Function 04H register read READING STARTREGISTER 2 CHARACTERS Register 00 00H Display Value NUMBER OF REGISTERS TO RE...

Страница 14: ...tering the Menu Introduce the programming code 14 23 Message E INP TEK board recognized Configuring the external contacts Parameter INP_1 Contact 1 ON Active OFF NotActive Parameter FUN_T Function ass...

Страница 15: ...unit to control a machine or process where injury to personnel or damage to equipment or process may occur as a result of failure of the unit External Protection Fuse to be added for 230 Vac 80mA fuse...

Страница 16: ...YS COUNTERS PROCESS SIGNALS TEMPERATURES TACHOMETERS SERIAL RSREPEATERS CLOCKS CHRONOMETERS PANEL METERS AC ELECTRICAL SIGNALS DC ELECTRICAL SIGNALS TEMPERATURES LOADCELLS PROCESS SIGNALS TACHOMETERS...

Отзывы: