7.1.4- CONFIGURING THE ANALOG OUTPUT
Entering the Menu
Introduce the programming code «55 11»
Message «IC ANG»
Analog Output board recognized
Message «MENU»
Entering the programming menu
Message «4_20» or «0 10»
Shows the operating mode selected by jumpers
(Vdc or mA)
Adjusting the Analog Output
*Note .- The values for the following 4 parameter are setable using keys 1,2,3,4,5
Parameter «d_LO»
(Display Low)
Display value associated with the low level analog
output
Parameter «o_LO»
Output Low
Analog output value associated with the «d_LO»
value *
Parameter «d_HI»
Display High
Display value associated with the high level
analog output
Parameter «o_HI»
Output High
Analog output value associated with the «d_HI»
value*
Note .- values for «d_LO» and «d_HI» are in microVolts or microAmperes
Behaviour when Error
Parameter «OnErr» .-
Behaviour of the analog output when an «error»
occurs (section 4.11 describes «errors»)
«DIR» -
Analog Output rises up to Full Scale (11Vdc or
21mA aprox)
«INV» .-
Analog Output sinks down to zero ( -0.5 Vdc or
0mA aprox)
Exiting the Menu
Mesage «INPUT»
Confirms that the parameters have been accepted
Message «ERROR»
Informs that at least one of the values is not
correct, and the whole configuration could not
be applied. Repeat the process from the begining.
7.2- INSTALLING THE OPTION BOARDS
The Option Boards are inserted onto the vertical pins of the Expansion
Modules. These modules are AL2 or EXP.
Note .- Both AL2 and EXP are optional themselves and are not included in the
standard units
The board has to be firmly inserted onto the vertical pins of the expansion
module. Once inserted, reconnect the expansion module to the fron-
tal of the instrument and insert the whole into the box.
The instrument automatically recognizes the pressence of an inserted
board.
Note1 : The expansion module is included with those instruments TAS-1 with the
AL2 option built in or the EXP option. The AL2 or the EXP modules can be also added
to those instruments who were acquired without any of these two options.
Note2 : The TEK board can share the expansion bus with the TSAT option of with
the R485M option, or can be directly connected to the bus alone.
Nota3 : Boards TSAT for Analog Output and R485M for Modbus output can not be
integrated simultaneously on the same instrument.
M ódulo de Expansión
Option Board (Analog Output,
Modbus or TEK)
Expansion Module
55 11
4_20 ó 0_10
- - - - - - IC ANG Menu
↵
↵↵
↵↵
o_LO
d_LO
d_HI
o_HI
↵
↵↵
↵↵
1
DIR
2
INV
INPUT or ERROR
onErr
IC_OFF
↵
↵↵
↵↵
↵
↵↵
↵↵
↵
↵↵
↵↵
↵
↵↵
↵↵