User’s Manual Series TAS-1

FEMA ELECTRÓNICA - Page 12

The R485M board adds Modbus communication capabilities
to the TAS-1 units, for retransmission of visualized data to a
remote element. The board is isolated and is completely
configurable from frontal keypad.

Protocols

ModBus RTU and ModBus ASCII selectable

Bus

RS485 Half Duplex

(EIA-RS485)

shielded twisted pair cable, in line,
closed with terminator

Speed

2400, 4800, 9600, 19200, 38400 bauds

Addresses

from 0 to 99

Distances

1200 meters per BUS segment
4800 meters with repeaters

Isolation

2 KV with inputsignal
3.5 KV with power signal

7.3- MODBUS OUTPUT - R485M OPTION BOARD

↵↵

↵↵

Prot

1

M Asc

Bauds

↵↵

↵↵

↵↵

↵↵

Dir

2

M rtu

1

2400

2

4800

3

9600

4

19200

5

38400

n bit

↵↵

↵↵

1

8 bit

2

7 bit

55 11

  - - - - - -   IC 485    Menu

↵↵

↵↵

Input   IC OFF

t Par

↵↵

↵↵

1

n Par

2

Even

3

Odd

Note2 : The length of all registers is 2 bytes, defined as LSB and MSB.
MSB (Most Significant Byte) is the first to be transmitted
LSB (Least Significant Byte) us the second to be transmitted

7.3.2- ACCEPTED FUNCTIONS

04 Hex

Registry read

(«Input Register» on the standard)

7.3.3- REGISTER MAP

00 00 Hex

Display Value
Type : Integer
Value : from -32768 to 32767

00 01 Hex

Decimal Point Position
Type : Integer
Value : 0, 1, 2, 3 or 4

00 02 Hex

Status
Type : Integer
Word composed of 1+4 bits

b0=0

Value contained on register 00 00H is an indication (number)

b0=1

Value contained on register 00 00H is not an indication

Word b4,b3,b2,b1

0.- Reserved

3.- +Ovr

6.- Con

9.- MErr1

12.- Reserved

15.- Others

1.- Low

4.- DErr0

7.- Open

10.- Reserved

13.- Reserved

2.- -Ovr

5.- Brk

8.- MErro0

11.- Reserved

14.- Reserved

00 03 Hex

Alarms
Type : Integer

b0=0 AL1 in OFF state

b2=0

AL3 in OFF state

b0=1 AL1 in ON  state

b2=1

AL3 in ON state

b1=0 AL2 in OFF state

b3=0

AL4 in OFF state

b1=1 AL2 in ON state

b3=1

AL4 in ON state

Note1 : If there is no numeric value on display (but a text value), register
0000Hex offers value 32767 or -32768. And bit b0 of register 0002Hex
show the display status.

0  = no decimal

2 = 2 digits decimal

4=4 digits decimal

1 = 1 digit decimal

3 = 3 digits decimal

5=5 digits decimal

     Not Used

b3

b2

b1

b0

     Not Used

b4

b3

b2

b1

b0

Introduce te programming code «55 11»
Message «IC 485»

RS485 board recognized

Message «MENU»

Entering the programming menu

Parameter «PROT» Protocol

Select Modbus ASCII or Modbus RTU

Parameter «DIR»

Address

Input instrument address

Parameter «BAUDS» Speed in Bauds

Parameter «n BIT»

Number of Bits
Select 8 or 7 bits per character

Parameter «t PAR»

Parity
«Even»  «Odd»

«nPar»

Message «INPUT» .- confirms that the parameters have been
accepted

Message «ERROR» .- informs that at least one of the values
is not correct, and the whole configuration could not be applied.
Repeat the process from the begining.

7.3.1- CONFIGURATION

Содержание TAS-1-IAC

Страница 1: ...CA Page 1 FEMA ELECTR NICA INTELLIGENT PANEL METERS Series TAS 1 Intelligent Panel Meters info fema es www fema es USER S MANUAL AC Current DC Current AC Voltages DC Voltages TAS 1 IAC TAS 1 IDC TAS 1...

Страница 2: ...ration 6 4 6 Manual Adjustment 7 4 7 Dealing with Errors 7 4 8 Advanced Indication 7 4 9 Blocking the Keypad 7 4 10 Resetting the system Default values 7 4 11 Messages and Errors 8 5 Configuring with...

Страница 3: ...Level Input Signal correction Key DP Decimal Point Position Key PROG Allows the introduction of the PROGRAMMING codes 4 digit codes as shown on page 4 These codes when validated activate different inp...

Страница 4: ...t 14 14 INPUT ONERR OFF ON 1 1 Visualization 14 13 DISPLAY NULL LAST 1 1 ON OFF 1 1 OFF ON 3 2 1 FIL 2 FIL 3 FIL 1 FILT A D Q N AVERA REAL 1 1 INPUT STEP XXXXX Alarm 1 Alarm 2 Alarm 3 Alarm 4 13 11 AL...

Страница 5: ...ion XXXX X 1 Press DP 2 message DP during 1 second Press 2 to fix decimal point position 2 To fix at other positions press 1 2 3 4 or 5 3 Validate changes pressinf message INPUT shows the configuratio...

Страница 6: ...m activation The hysteresis points are defined on parameter HYST for each alarm Security Mode activated on alarms acting as minimum Securty Mode deactivated Output relay are inactive until the set poi...

Страница 7: ...Code 14 11 Function Code 14 22 Function Resets the unit to the default manufacturing values It is needed to reconfirm the action by pressing INTRO after the message Acquisition Mode Real STEPValue 10...

Страница 8: ...recovers the normal working state when situation clears Errors Errors are associated with critical situtations which disable the hability to measure the signal The error remains active on display unt...

Страница 9: ...tion 32 000 points ENVIRONMENTAL DATA Working Temperature 0 50 C Storage Temperature 20 85 C Humidity 0 85 non condensaded MECAHNICALDATA Dimensions Standard 1 8 DIN 96 x 48 x 124 mm 3 78 x 1 89 x 4 8...

Страница 10: ...ot need to be readjusted most of the times in case of trouble with the input signal such as loop break or sensor break the analog output signal will exhibit always the same behaviour predefined by the...

Страница 11: ...essage ERROR Informs that at least one of the values is not correct and the whole configuration could not be applied Repeat the process from the begining 7 2 INSTALLING THE OPTION BOARDS The Option Bo...

Страница 12: ...mposed of 1 4 bits b0 0 Value contained on register 00 00H is an indication number b0 1 Value contained on register 00 00H is not an indication Word b4 b3 b2 b1 0 Reserved 3 Ovr 6 Con 9 MErr1 12 Reser...

Страница 13: ...acion MASTER and SLAVE ADDRESS 1 CHARACTER Instrument Address FUNCTION 1 CHARACTER Function 04H register read READING STARTREGISTER 2 CHARACTERS Register 00 00H Display Value NUMBER OF REGISTERS TO RE...

Страница 14: ...tering the Menu Introduce the programming code 14 23 Message E INP TEK board recognized Configuring the external contacts Parameter INP_1 Contact 1 ON Active OFF NotActive Parameter FUN_T Function ass...

Страница 15: ...unit to control a machine or process where injury to personnel or damage to equipment or process may occur as a result of failure of the unit External Protection Fuse to be added for 230 Vac 80mA fuse...

Страница 16: ...YS COUNTERS PROCESS SIGNALS TEMPERATURES TACHOMETERS SERIAL RSREPEATERS CLOCKS CHRONOMETERS PANEL METERS AC ELECTRICAL SIGNALS DC ELECTRICAL SIGNALS TEMPERATURES LOADCELLS PROCESS SIGNALS TACHOMETERS...

Отзывы: