Installation, Operating & Maintenance Manual
_________________________________________________________________________________________
2
In considering a purchase of this steam-
bath system, please note that if users are pregnant,
have a coronary condition, are in poor health, are being
treated for any other medical condition, or are using
medication or drugs, MrSteam recommends that you
obtain the approval of their physician before use.
For information about this product and safety issues,
please call us at 1-800-76-STEAM or log onto
www.mrsteam.com
IMPORTANT NOTES:
• The guidelines for selecting the steambath generator is
a recommendation only. Because of variables in con-
struction, these sizing instructions and specifications
should be considered as guidelines only. MrSteam will
review the model selected provided we receive com-
plete information, including working drawings, specifi-
cations, and pertinent electrical and construction
details. Otherwise, the manufacturer disclaims respon-
sibility for the sizing of a model selected.
• For steam rooms constructed of acrylic or synthetic
materials, select next lower-rated CT model.
• The total adjusted room volume allows for up to 60
feet of insulated steam piping from the CT generator
to the steam room. If the 60 feet piping is exceeded
consult with factory. When locating the steam gener-
ator consideration of the control and external tem-
perature probe must be taken into account. The max-
imum length for a control cable is 60 feet. The maxi-
mum length of the MSTS is 60 feet. MSTS connects
to the steam generator and is required to be installed
inside the steam room when the control is mounted
outside the steam room.
Steam Generators Specification Chart
Amps (for
Total Adj
Wire Water Usage
Shipping
Model No.
KW 240v/1PH)† Room Vol.
Size‡
gallons††
Dimensions*
Wt. (lbs)**
CT6E
6
25
150
8
0.80
17"L x 18½"H x 7
7
⁄
8
"D
40
CT9E
9
38
360
8
1.2
17"L x 18½"H x 7
7
⁄
8
"D
40
CT12E
12
50
575
6
1.6
17"L x 18½"H x 7
7
⁄
8
"D
40
CT15E
15
63
675
4
2.0
17"L x 18½"H x 7
7
⁄
8
"D
40
IMPORTANT NOTES:
• Add C1 suffix to Model No. for 240V/1Ph; Add B1 suffix to Model No. for 208V/1Ph.
• All CT MS Models are cUL us Listed and CE; approved.
All CT Generators available in 240v/1PH, 208v/1PH and other voltages/phases.
† Amps are for 240/1PH rated units.
‡Wire size (AWG) based on minimum 90˚C rated THHN copper conductors. Refer to the
National Electrical Code for other types of conductors.
*Dimensions are for generator only, with-
out AutoFlush
®
or plumbing features.
**Shipping weight and pricing are for
generator only, without control or
steamhead.
†† Water usage based on 20 minutes of
operation.
Materials of construction, room size and special design features such as
large glass areas, all affect the steam generator model selection.
1. Measure length, width & height in feet of the steam/shower or tub/shower
Multiply the Length ____ x Width____ x Height _____
=
2. Construction Materials:
For natural stones: natural marble,
Add 110%
stone, shale, glass block or concrete
For ceramic or porcelain tile on
Add 40%
cement board or mortar bed
3. Ceiling Height: For each foot above 8 feet
(max. of 10 feet)
Add 15%
4. Add all figures above to obtain
the Total Room Volume required
ROOM
VOLUME
TOTAL ADJUSTED
ROOM VOLUME
Select Your Club Therapy Model
Compare your TOTAL ADJUSTED ROOM VOLUME to the Specification Chart
below and select the appropriate model.
Visit www.mrsteam.com to size your generator automatically.