background image

blank page

Содержание PS600 SelecTone

Страница 1: ...255314D Rev D1 0315 Printed in U S A Model PS600 SelecTone Standby Battery Backup Power Supply Installation and Maintenance Instructions ...

Страница 2: ...arning Systems are warranteed for two years on parts and one year on labor No agent employee representative or distributor of Seller has any authority to bind the Seller to any representation affirmation or warranty concerning the goods and any such representation affirmation or warranty shall not be deemed to have become a part of the basics of the sales contract and shall be unenforceable THE FO...

Страница 3: ...Installing the Batteries and Wiring the PS600 10 Determining the Total Ampere Hour Capacity 11 Determining the Maximum Load Discharge 12 Setting Up the PS600 for Your System 18 For Battery Backup 18 For a Supervised Power Supply 18 Getting Repair Service or Technical Assistance 19 Safety Message to Maintenance Personnel 19 Maintaining the PS600 20 Testing the Output Voltage 20 Testing the Battery ...

Страница 4: ...unction of discharge current 13 Figure 2 Interior of PS600 cabinet 14 Figure 3 Transformer connections 16 Figure 4 PS600 Wiring schematic 17 Tables Table 1 Power supply circuit board LED indicators 7 Table 2 Switch 1 output voltage settings 18 Table 3 Replacement parts 20 ...

Страница 5: ...precautions you should follow Read and understand all instructions before installing or operating this equipment The nameplate should NOT be obscured as it contains cautionary and or other information of importance to maintenance personnel Ensure the nameplate remains readable if the housing exterior is painted Do not connect this unit to the system when power is on After installation ensure that ...

Страница 6: ...zed access The unit is intended for indoor use only Certifications This power supply is intended for use in applications requiring UL certification for fire protection signaling and access control The power supply must be installed in accordance with National Electric Codes and in accordance with NFPA 72 protective signaling systems The PS600 meets these additional certifications UL certifications...

Страница 7: ...e battery package and the red dc power and green ac power LED indicators See Table 1 Table 1 Power supply circuit board LED indicators Red dc Green ac Description ON ON Normal function ON OFF Battery backup is powering output OFF ON No dc output OFF OFF System off no battery Charger Logic Circuits Diagnostics The charger logic circuits consist of battery charging circuitry This part of the circuit...

Страница 8: ... models 50GC SelecTone Audible Signaling Device 300GC SelecTone Audible Signaling Device 300GCX SelecTone Hazardous Location Audible Signaling Device 300X SelecTone Explosion Proof Audible Signaling Device 302GC SelecTone Audible Signaling Device 302GCX SelecTone Hazardous Location Audible Signaling Device 302X SelecTone Explosion Proof Audible Signaling Device Product Specifications Operating Vol...

Страница 9: ...rging Current 1 25 A maximum Physical Dimensions HWD 15 50 in x 12 50 in x 4 50 in Weight 13 lb without batteries Operating Temp Range 0 C to 49 C Battery current capacity changes throughout the operating temperature range Unpacking the PS600 After unpacking the PS600 examine it for damage that may have occurred in transit If the unit has been damaged do not attempt to install or operate it File a...

Страница 10: ...0 mounting screws To mount the PS600 1 Before installing the batteries use the power supply enclosure as a template to mark the location of the three mounting holes on the mounting surface 2 Mount the cabinet with the appropriate hardware Make sure that the unit is firmly secured to the mounting surface 3 Terminate the conduit for the 120 Vac or 240 Vac power at one of the two knockouts located at...

Страница 11: ...ed 24 Vdc or 12 Vdc output conductors Use one of the two knockouts in the top either the middle or the left side of the cabinet or the knockout in the middle of the left side Make sure that all power limited fire protective signaling conductors are segregated from electric light power Class I or non power limited fire protective signaling conductors by more than 0 25 inch inside the power supply c...

Страница 12: ... hours x alarm current amperage useful battery capacity Capacity Required 24 x 0 200 5 60 x 6 0 85 4 80 0 5 0 85 5 30 0 85 6 23 Ah In this example a 24 Vdc 6 A power supply with 24 V 12 Ah battery can operate the signaling device Determining the Maximum Load Discharge Determining the maximum load discharge current from a specific battery size over a specific amount of time can be tricky Batteries ...

Страница 13: ...rge timeline Find the intersection as circled Follow this intersection point vertically down to find the maximum discharge current In this case 2 A is the maximum discharge current Figure 1 Discharge time as a function of discharge current 80 60 50 40 30 20 10 9 8 7 6 5 4 3 2 1 8 9 7 6 5 4 3 2 1 1 2 3 4 5 6 8 1 DISCHARGE CURRENT AMPS DISCHARGE TIME HOURS 2 3 4 5 6 8 10 BATTERY SIZE IN AMPERE HOUR ...

Страница 14: ...C C NO AC FAIL AC TROUBLE DELAY OPTION DC AC DC BAT PS600 PCB H I G F E C D O P P P Q Q Q A A 12 V 12 Ah battery J Green B Transformers K Red C dc Terminal blocks L Black D ac Terminal blocks M White E Battery terminal blocks N To 120 240 Vac F dc red LED O Ground Green G ac green LED P Yellow H Battery fail terminal blocks Q Blue I ac fail terminal blocks ...

Страница 15: ...th the connector If you are using stranded wire be sure that there are no loose strands outside of the connector plug that could touch the adjacent lead and cause a short circuit 4 Connect the 12 Vdc or 24 Vdc output circuits of the device to be powered to the two position terminal block labeled DC in the upper left side of the power supply PC board Observe the correct polarity A wiring terminal s...

Страница 16: ...the black negative terminal of the first battery 9 Connect the red positive wire of the battery terminal block to the red positive terminal of the second battery and close the cabinet door Figure 3 Transformer connections 120 Vac INPUT 240 Vac INPUT 290A4306B LINE NEUTRAL BLACK 5 GREEN RED WHITE 4 3 2 1 BLACK 5 GREEN 4 3 RED 2 WHITE 1 ...

Страница 17: ...re 4 PS600 Wiring schematic PS600 PCB YELLOW BLUE YELLOW BLUE BLUE YELLOW YELLOW BLUE WHITE RED GREEN BLACK BLACK WHITE GREEN RED 10 6 5 4 2 1 BLACK RED YELLOW BATTERIES 290A4307B P C BOARD ASSEMBLY TRANSFORMERS TO 120 240VAC SUPPLY TO 120 240VAC SUPPLY DC BAT 10 6 5 4 2 1 ...

Страница 18: ...output set voltage 3 Make sure the red and green LEDs turn on Red indicates the presence of dc power and the green indicates the presence of ac power For a Supervised Power Supply To set up the PS600 for a supervised power supply 1 Set the voltage See Table 2 2 For battery backup connect the battery to the battery terminals BAT Carefully observe polarity and match the battery voltage to the set ou...

Страница 19: ...ty Message to Maintenance Personnel Listed below are some important safety instructions and precautions you should follow Read and understand all instructions before operating this system Any maintenance to the system must be done with power turned off Any maintenance to the system must be performed by a trained electrician who is thoroughly familiar with all applicable national and local codes in...

Страница 20: ...as follows Testing the Output Voltage Under normal load conditions the dc output voltage should be checked for proper voltage level Testing the Battery Under normal load conditions check that the battery is fully charged Check specific voltages at both the battery terminals and at the board terminals marked BAT Battery life is five years However changing batteries in four years or less is recommen...

Страница 21: ...ons are met Product is resalable and in the original cartons Product has not been previously installed Product is the current revision Product has not been previously repaired Product is a standard product Product is not a service part All returns are subject to a re stock fee Defective products that are returned within the warranty period will be repaired or replaced at Federal Signal s sole disc...

Страница 22: ...22 Installation and Maintenance Instructions Selectone Model PS600 NOTES ...

Страница 23: ...blank page ...

Страница 24: ...Industrial Systems 2645 Federal Signal Drive University Park IL 60484 3167 Tel 708 534 4756 Fax 708 534 4852 Email elp federalsignal com www federalsignal indust com ...

Отзывы: