8
Installation and Maintenance Instructions
Selectone Model PS600
negative (
▬
) terminal and the positive meter lead to the positive
(
+
)
terminal.
For more information on system maintenance, see “Maintaining
the PS600” on page 20.
NOTE:
With no ac present and the battery wires connected, the
dc output circuits read approximately 1 volt lower than the actual
battery voltage.
Related Signaling Devices
The PS600 is used with these UL listed, 24 Vdc models:
• 50GC SelecTone Audible Signaling Device
• 300GC SelecTone Audible Signaling Device
• 300GCX SelecTone Hazardous Location Audible Signaling
Device
• 300X SelecTone Explosion Proof Audible Signaling Device
• 302GC SelecTone Audible Signaling Device
• 302GCX SelecTone Hazardous Location Audible Signaling
Device
• 302X SelecTone Explosion Proof Audible Signaling Device
Product Specifications
Operating Voltage
120 Vac, 50/60 Hz
240 Vac, 50/60 Hz
Current Requirement
120 Vac, 1.90 A
240 Vac, 0.95 A
dc Output (Non-Power-Limited, Supervised)
ac Power Applied
Voltage
24.8 Vdc no load
23.1 Vdc full load
Current
6 A maximum
Ripple
0.5 Vrms maximum