background image

 

- 6 - 

 

PRE-INSTALLATION PROCEDURES 

 

Inspection for Shipping Damage 

You are responsible for filing all freight claims with the delivering truck line.  Inspect all cartons 
and crates for damage as soon as they arrive.  If damage is noted to shipping crates, cartons, or if a 
shortage is found, note this on the bill of lading (all copies) prior to signing. 

 

If damage is discovered when the case is uncrated, immediately call the delivering truck line and 
follow up the call with a written report indicating concealed damage to your shipment.  Ask for an 
immediate inspection of your concealed damage item.  Crating material must be retained to show 
the inspector from the truck line. 

 

GENERAL ELECTRICAL & GROUNDING 

 

 

DANGER: 

Improper or faulty hookup of electrical components in the 

 

display case can result in severe injury or death.

 

 

Permanent Connected (OPTION)

 

-Only a licensed electrician must perform all case electrical connections. 
-All electrical wiring hookups must be done in accordance with all applicable local, regional, or national 
  electrical standards. 
-A separate circuit for each display case is required to prevent other appliances on the same circuit from 
  overloading the circuit and causing malfunction. 
-The electrical service must be grounded upon installation. 
-See the electrical data plate located at the rear of the case for proper circuit size and wire ampacity. 
-The electrical connection box is accessible from the rear of the case with rear grill removed. 

REAR BASE PANEL

(6) REAR PANEL SCREWS

CONDUIT OR 
POWER CORD 
CONNECTION .875

O

FIELD CONNECTION BOX

FLOOR CONDUIT
CONNECTION .875

O

 

 

Cord Connected (OPTION)  

-A factory installed optional power cord is properly sized to the amperage requirements of the case. See the 
electrical data plate located on the rear exterior of the case for the proper circuit size for each case.  
- The cord is factory installed protruding from the rear corner of the case. 
-A separate circuit for each display case is required to prevent other appliances on the same circuit from 

overloading the circuit and causing malfunction.  

All manuals and user guides at all-guides.com

Содержание SSRC2452

Страница 1: ...RC MODELS KEEP THIS MANUAL FOR FUTURE REFERENCE Engineering and technical data are subject to change without notice FEDERAL INDUSTRIES 215 FEDERAL AVE Belleville WI 53508 Toll Free 1 800 356 4206 WI P...

Страница 2: ...op Section Rear Sliding Doors Removal 14 Top Section Rear Swinging Doors Removal 15 Bottom Section Rear Doors Removal Option 16 NIGHT CURTAIN SSRC OPTION 17 Opening 17 Closing 17 SECURITY NIGHT COVER...

Страница 3: ...ESSRC3652 w Fluorescent Lights 36 Self Contained SSRC5052 5952 7752 ESSRC5052 5952 7752 w Fluorescent Lights 36 Self Contained SSRC2452 w LED Lights Mfg d After 12 1 19 37 Self Contained SSRC3652 ESSR...

Страница 4: ...alified to perform electrical work DANGER Improper or faulty hookup of electrical components in the case can result in severe injury or death All electrical wiring hookups must be done in accordance w...

Страница 5: ...ou ignore the message WARNING Severe injury or death can occur if you ignore the message CAUTION Minor injury or damage to your case can occur if you ignore the message NOTICE This is important instal...

Страница 6: ...ust be done in accordance with all applicable local regional or national electrical standards A separate circuit for each display case is required to prevent other appliances on the same circuit from...

Страница 7: ...60 1 14 5 20 120 60 1 15 SSRC7752 ERSSC7752 230 60 1 14 5 20 120 60 1 15 MODEL VOLTAGE TOTAL AMPS CORD STYLE SSRC2452 120 60 1 11 3 20AMP NEMA 5 20 SSRC3652 120 60 1 14 3 20AMP NEMA 5 20 SSRC5052 ERS...

Страница 8: ...in the pre installation procedures outlined above 2 Move the case as near as possible to the final location and before removing it from the shipping skid 3 Remove the 4 brackets that secure the case...

Страница 9: ...tect from system failure causing too high of system pressure The high side of the pressure control is factory set to 400psi and is not adjustable Low side setting for the R404a cases are set at 40psi...

Страница 10: ...Refrigeration Instructions 1 Mount condensing unit indoors as close to the remote display case as practical The refrigeration line should be as short as possible 2 All refrigeration and or electrical...

Страница 11: ...stall the brackets so they are farthest spread apart at the front of the case 0v NOTCH 6v NOTCH 4 1 2 3 4 INSTALLATION REMOVAL 2 3 1 TOP HOOK BOTTOM TAB SHELF BRACKET SHELF STANDARD 1 Place shelf brac...

Страница 12: ...then on the rear notch of the shelf bracket on the opposite side NOTE If the bottom open section shelf is supplied instead of step risers the bottom rear support is not the same as the top rear suppo...

Страница 13: ...glass shelf 2 For first time installation attach 1 product stop to each glass shelf as shown in detail above Align the product stop edge with the edge of the glass and push the U portion of the produc...

Страница 14: ...the door upward until the bottom edge of door clears the lower track and then swing the bottom of the door outward and down out of upper track 2 After the outer door is removed repeat the procedure f...

Страница 15: ...located under the door at the pivot point of the lower hinge It is not necessary to remove the 2 screws that secure the lower hinge bracket to the case 3 With the door still in the open position use a...

Страница 16: ...move the outer inside door using the same procedure 3 The inner door set can then be removed using the same procedure starting with the inner outside door followed by the inner inside door 4 Reverse t...

Страница 17: ...e and down the front 2 Attach the snap located under the night curtain strap on to the snap located on the front trim Closing 1 Grasp the night curtain strap and detach the snap from the snap located...

Страница 18: ...security cover down against the top glass handle 4 Turn the lock handles so they engage the lock handle catches and use the key to lock them in place IMPORTANT Cleaning the Acrylic plastic security ni...

Страница 19: ...TCH LIGHT SWITCH Power Switch The unit has a power switch that turns off power to the entire unit including the condensate evaporator and the lights Light Switch The unit has a light switch that turns...

Страница 20: ...in the on mode when shipped from factory To turn refrigeration control power to off press and hold for approx three seconds The display will read Off while the button is depressed When the control po...

Страница 21: ...normal operation and will automatically clear the codes from the display Carel Control EO Air sensing probe Open or shorted E1 Evap coil probe Open or shorted Error codes may be encountered if either...

Страница 22: ...6 F 3 3 C at the coldest setting 9 and 36 F 2 2 C at the warmest setting 1 See Error Reference source not found on page Error Bookmark not defined for more details on using the control Defrost Cycle T...

Страница 23: ...0 1 10 9 9 212 F 100 C 1 0 97 0 94 INITIAL STARTUP After all the checks outlined in the installation section of this manual have been made the case is ready to be put into service Turn on the Power at...

Страница 24: ...is required for potentially hazard food the air control louver must be completely open A half open louver will not allow sufficient air flow to top section Placing Product into Case Do not exceed 75 p...

Страница 25: ...caps Reinstall bulb assembly in the same manner as described in the Bulb Removal Procedure Be sure bulb is secure in bulb receptacles Note Be sure to use a direct equivalent to the original bulb Top...

Страница 26: ...frequently FAILURE TO CLEAN CONDENSER COIL WILL VOID COMPRESSOR WARRANTY 1 Disconnect power to the unit 2 Remove the back base panel located on the back bottom of unit by removing the 6 front panel r...

Страница 27: ...SSRC cases only the upper front glass can be tilted open to allow easier access to clean the upper section interior Tilt the front glass up by standing in front of the case and grabbing the handle at...

Страница 28: ...w sufficient time for the unit to reach room temperature before proceeding with cleaning NOTICE Remove all product from case before proceeding with cleaning procedure NOTICE Acrylic front air deflecto...

Страница 29: ...ass retainer The glass can then be cleaned with common window cleaners 5 Remove interior shelving from unit as described in the Shelving Installation and Removal section of this manual Remove both she...

Страница 30: ...e thoroughly and allow to dry 5 Lift the display deck s up and out of evaporator tub 6 Remove the fan shroud assembly There are either 2 retainer latches or 2 thumbscrews located at each end at the fr...

Страница 31: ...ft wet cloth or chamois The cloth or chamois must be kept free of grit by frequently rinsing in clean water Grease and oil can be removed with kerosene Do not use window cleaners or kitchen scouring c...

Страница 32: ...8188 Special Service Situations There are rare occasions when the refrigerant charge must be evacuated from a case in order to perform service work In those situations Federal Industries recommends t...

Страница 33: ...ght in the sockets Plug unused light sockets with socket cap provided with socket Case Temperature Too Warm Check that the cold air inlet and outlet slots are not blocked Be sure that the rear doors a...

Страница 34: ...tment at Federal Industries at 800 356 4206 The customer service department at Federal Industries should be contacted at the time of sale or disposal of your case so records may be kept of its new loc...

Страница 35: ...35 MAIN WIRING DIAGRAMS SELF CONTAINED SSRC2452 W FLUORESCENT LIGHTS All manuals and user guides at all guides com...

Страница 36: ...36 SELF CONTAINED SSRC3652 ESSRC3652 W FLUORESCENT LIGHTS SELF CONTAINED SSRC5052 SSRC5952 SSRC7752 ESSRC5052 ESSRC5952 ESSRC 7752 W FLUORESCENT LIGHTS All manuals and user guides at all guides com...

Страница 37: ...37 SELF CONTAINED SSRC2452 W LED LIGHTS MFG D AFTER 12 1 19 All manuals and user guides at all guides com...

Страница 38: ...RC5952 ESSRC 7752 W LED LIGHTS MFG D AFTER 12 1 19 OPTIONAL CORD PLUG R CONDENSATE PAN OR PUMP BLK EVAP FAN BLK RIB BLK RIB BLK BLK BLK W G BLK BLK M BLK EVAP FAN BLK RIB BLK RIB BLK BLK BLK M PLUG DA...

Страница 39: ...39 REMOTE SSRC2452 SSRC3652 W FLUORESCENT LIGHTS REMOTE SSRC5052 SSRC5952 SSRC7752 W FLUORESCENT LIGHTS All manuals and user guides at all guides com...

Страница 40: ...WIRING ALTERNATE CONTROL RANCO W W 4 7 10 9 5 9 6 7 10 SEE CAREL WIRING CAREL CONTROL W 5 8 8 W 6 R BLK TEMP PROBE DEFROST PROBE 4 BLK TEMP DEFROST EVAP FAN QTY MAY VARY DARK LINES REPRESENT 3 CONDUCT...

Страница 41: ...ling Light 42 20871 18C35 LED Top Shelf Light 42 20871 18C35 LED Bottom Shelf Light Optional 42 20871 18C35 LED Top Light Wiring Harness LED Btm Ceiling Light Wiring Harness Shelf Light Receptacle 5 P...

Страница 42: ...nner Solid Btm Section Opt 53 18211 1 Rear Door Outer Solid Btm Section Opt 53 18212 1 CatchDoor Inner Inside Btm Section Opt Catch Outer Inside Btm Section Opt Rear Door Inner Inside Btm Section Opt...

Страница 43: ...re 12 18 LED Power Supply after 12 18 LED Top Light after 12 15 18 42 20871 42C35 42 20871 72C35 LED Bottom Ceiling Light after 12 15 18 42 20871 42C35 42 20871 72C35 LED Top Shelf Light 12 15 18 42 2...

Страница 44: ...Door Inner Solid Btm Section Opt 53 19147 3 X Rear Door Outer Solid Btm Section Opt 53 19148 3 X CatchDoor Inner Inside Btm Section Opt Catch Outer Inside Btm Section Opt Rear Door Inner Inside Btm S...

Страница 45: ...ct can expose you to chemicals including chromium which is known to the State of California to cause cancer and birth defects or other reproductive harm For more information go to www P65Warnings ca g...

Страница 46: ...REV CHANGE RECORD APP D DATE ECN B REVISED PARTS LIST SES 5 10 19 C ADDED DUAL PRESSURE CONTROL INFO ADC 8 6 19 3506 D ADDED EEV WIRING DIAGRAMS KMC 1 21 20 All manuals and user guides at all guides...

Отзывы: