Selecting a location for the unit

Mounting on face of vertical return duct or side of
horizontal return duct

When mounting your humidifier on the face of a horizontal
return duct, or on the face of a vertical return duct, certain
conditions must be met for its proper operation:

•  Mount the humidifier on the vertical or horizontal cold air

return duct.

• Locate the humidifier at least four (4) linear feet upstream of

either the furnace fan and /or filter and any turn in the duct.
This will ensure that condensation does not collect within the
duct and cause oxidation (rust). 

• Mount the humidifier at least six (6) linear feet (preferably 10

feet) upstream from any electronic air cleaner. Failure to
follow this recommendation can cause excessive nuisance
arcing and or power supply failure.

• If the duct seams inside the duct are not flat, locate the

humidifier at least three (3) linear feet upstream from the
seam.

• If the humidification needs of the home require more than

one humidifier, each unit should be installed a minimum of (3)
linear feet apart. 

• DO NOT use this humidifier on the discharge or warm air

supply side of a forced air heating system. This will reduce the
efficiency of the humidifier and may cause operational
problems. 

• DO NOT mount the humidifier in a furnace jacket.

• DO NOT install the humidifier where freezing conditions could

occur.

• DO NOT install on gravity hot air systems.

Содержание Herrmidifier 707U

Страница 1: ...11 Maintenance 12 Unit Diagram and Parts List 14 Warranty Back cover Manual for Installation Operation Maintenance Duct Mount Centrifugal Atomizer Humidifier Table of Contents 256703 001 7 04 CAUTION...

Страница 2: ...into the home and heated When heated this air dries out and greatly increases its capacity to hold more moisture By using a humidifier a source of water is provided to satisfy this increased moisture...

Страница 3: ...turn the humidistat to the OFF position Sq Footage of Home 1000 1500 2000 2500 3000 4000 Tight Home GPD 0 5 3 0 5 0 7 5 10 0 14 5 Average Home GPD 5 0 10 0 14 0 19 0 23 5 33 0 Loose Home GPD 10 0 16...

Страница 4: ...at least six 6 linear feet preferably 10 feet upstream from any electronic air cleaner Failure to follow this recommendation can cause excessive nuisance arcing and or power supply failure If the duct...

Страница 5: ...rge nozzle should be at least two 2 feet below the ceiling and from a vertical wall along the side The discharge nozzle should be about six and a half 6 1 2 feet from the floor If this is not possible...

Страница 6: ...cturer s original warranty Remember to select a location that is readily accessible for periodic inspection and cleaning of your humidifier Allow a minimum of 2 clearance in front of the humidifier an...

Страница 7: ...position with 2 10 sheet metal screws and flat washers provided 10 The float and valve assembly have been factory adjusted to maintain 1 1 1 2 of water in the water reservoir pan at normal water pres...

Страница 8: ...II of the inside wall using a saber saw or equivalent Do NOT cut through the entire wall 8 Remove the template from the wall In the 6 5 16 diameter holes previously drilled into the inside wall insta...

Страница 9: ...sion nozzle provided will be 2 5 8 long PLUS the total wall thickness as determined in the previous step Cut the extension nozzle to length on the square end The opposite end of the extension nozzle i...

Страница 10: ...copper tubing to the float and valve assembly with the ferrule and compression nut provided Caution The float and valve assembly must not turn when tightening the copper tubing compression fittings to...

Страница 11: ...operation of the humidifier during the heating season 3 The humidifier will only operate when the furnace blower is in operation 4 It is recommended to install a humidistat provided with model 707U i...

Страница 12: ...hrow switch may be installed 4 Turn the humidistat to the highest level past 60 and the humidifier should begin to run The humidifier should stop when the humidistat is turned off 5 Set the furnace co...

Страница 13: ...ly therefore the frequency of cleaning the unit also varies During the heating season check for film or scale build up in the unit or any moving part Establish a proper cleaning schedule to ensure the...

Страница 14: ...Remove the pump from the end of the impeller shaft If the pump is stuck in the motor drive shaft run hot water over the end of the shaft for a few seconds to loosen the pump 8 Flush water through the...

Страница 15: ...SCREEN 6 1 1 D9P IMPELLER 7 1 1 M3 SCREW SET CUP 8 1 1 8A IMPELLER PUMP 9 4 4 90 VIBRATION DAMPER 10 1 1 35P CENTER PAN 11 4 4 23 CENTER PAN SUPPORT 12 2 2 27 DRIP TUBE 13 1 1 92P FLOAT VALVE ASM 14...

Страница 16: ...ders com Humidifiers which have been installed or become part of real estate cannot be returned CareCo will receive freight prepaid only removable parts or components of such defective humidifiers 6 T...

Отзывы: