INP-TN512878-E
31
5.4.3 Smith’s dead time compensation control
Method for Smith compensation: By adding internal compensation circuit G1 (1 - e
-LS
) to a system
having dead time of GP • e
-LS
in the process, deformation to such a form that the system viewed from
the controller controls the system equivalently without dead time. Thus, the process can be
controlled as what is without dead time.