INP-TN512878-E
9
When it is wanted to hold the output value (MV), it can be accomplished by the following methods.
3.1 Method to input external signal (forced manual SMAN)
Forcibly produce the M-mode by inputting a DI signal of “SMV” from outside.
(The mode lamp on the front face changes to “M”, and the MV operation button becomes valid.)
In this case, call the ALARM CONNECT screen out of the OUT CONNECT screen, and register DI
terminal mode in “SMAN-REQ”.
3.2 Method to input external signal (EX-MV)
Input a DI signal of “EX-MV” specified opening mode from outside.
Figure 3-1
(When an output signal is input through the input terminal of EX-MV, the then output value is held.)
3.3 Method to stop addition of
∆
MV value
Figure 3-2
(When integration value
∆
M integration of speed type of 2ND • PID wafer (42) Y
1
is stopped, MV of
the then value is held.)
3. How to hold output value (MV)