Page 90 of 91
Rev. 4.20
GENERAL
Case size:
1 loop model: B x H x P 325x440x90mm.
2,4 loop models: B x H x P 410x510x90mm.
Case material:
Painted steel.
Fixing:
At wall, with installation fixed.
Protection degree:
IP40.
Weight:
10Kg (without batteries).
Operating Temperature:
- 5 = + 45°C.
Relative humidity:
<95% relative humidity, no condensed.
Control panel keypad cleaning
It is possible to clean the control panel keypad with a with a humid cloth. Not to
use aggressive agents.
LOOP
Detection circuit:
1-2-4 loop. Every loop supports the communication with 127 elements
(detectors, buttons, input/output modules and isolators).
Maximum points number for
loop:
120 between detectors, buttons and modules;
7 addressable isolators;
100 passive isolators.
Point types:
Into the loop it is possible to install: detectors (smoke, heat e smoke-heat),
buttons, I/O modules and isolators.
Definable zone:
Up to 63 configurable zones per loop.
LOCAL POWER SUPPLY
Power supply voltage:
10% - 15%, 50Hz.
Power supply:
< 50VA.
Power supply fuse:
T 400mA 250V (delayed).
Power supply output:
30Vdc.
Battery charger output
27.6Vdc nominal at 20°C.
Battery charger fuse:
F 1.6A L 250V (fast).
Battery:
Loop1: at Pb 2x 12V – 7.2Ah
Loop2: at Pb 2x
12V – 18Ah
Loop4: at Pb 2x
12V – 18Ah.
Aux. power supply:
27.6Vdc.
Aux. power supply fuse:
F 1.6A L 250V (fast).