background image

   

 

 

 

 

 

 

     

    

Orion-M

 

 

3.4     FDC Orion-M 

 

 

 

 

 

 

 

 

 

 

 

 

                CONFIGURING THE UDC2500/3200 CONTROLLER 

3.4  Loop Permissions 

The Orion-M iSeries configuration provides permissions which can be set to allow the control loop set point, 
auto/manual and auto tune operations to be performed at the loop control itself as well as through the Orion-
M.  These can allow an operator to make changes at the loop control in cases where the Orion-M interface is 
located in a remote location. 
 
 

3.4.1 

Set Point Permission Exception 

If  the  control  loop  is  configured  to  operate  under  cascade  control  or  is  configured  as  an  RH  wet  bulb  loop 
type,  the  set  point  for  the  loop  is  generated  by  logic  within  the  Orion-M.    The  loop  will  not  function  as 
configured unless the se point is constantly set by the Orion-M.  Thus, any change made at the loop control 
will be overridden by the Orion-M.  If local adjustment at the loop control may be required for any reason, loop 
set point communications must be interrupted via a digital input to the Orion-M configured as ‘loop SP comms 
disable’. 
 
In  addition,  the  Honeywell  controls  will  enter  the  computer  set  point  mode  (CSP)  once  they  receive  any  set 
point  command  from  the  Orion-M.    This  will  lock  out  adjustments  from  the  keypad  at  the  controller.    The 
Orion-M is designed to send the ‘shed timer reset’ command to the UDC controller to take it out of computer 
set  point  control  when  the  set  point  permission  is  enabled.    This  allows  control  via  the  keypad  of  the 
controller.    However,  during  profile  operation  and  after  the  profile  completes,  the  UDC  will  remain  under 
computer set point control.  In order to deactivate CSP, a single set point must be sent from the Orion-M in 
order  to  unlock  it.    Triggering  a  digital  input  configured  as  ‘loop  SP  comms  disable’  will  also  take  the  UDC 
controls out of computer set point control. 
 
 

3.4.2 

Auto/Manual Permission Requirement 

The  Honeywell  controller  provides  the  ability  to  initiate  manual  mode  or  ‘failure  transfer  mode’  through  a 
digital input on the controller.  If this function is used, the loop permission for auto/manual operation must be 
enabled.  If this permission is not enabled, a communication error will occur at the Orion-M.  This is due to the 
fact that without the permission enabled, the Orion-M  will try and force the controller back to auto mode if it 
goes into manual operation via the digital input. 
 
Since  the  digital  input  on  the  UDC  controller  is  an  override  condition,  it  will  deny  the  auto  mode  command 
from the Orion-M.  The Orion-M then has to respond with a communication error, since the controller did not 
follow  the  command  given.    By  enabling  the  auto/manual  permission,  the  Orion-M  will  accept  the  manual 
mode force at the UDC controller. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание Orion-M

Страница 1: ...Orion M Honeywell UDC2500 3200 Series Controller System Guide Rev C February 7 2011 Supersedes Rev B March 25 2010 Orion M Honeywell UDC2500 3200 Controller System Guide...

Страница 2: ...ion to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the above you can get technical assistance by dialing 1...

Страница 3: ...1 1 Communications Wiring 2 1 3 Configuring the Honeywell UDC2500 3200 Controller 3 1 3 1 Assigning the Proper Communications Settings 3 1 3 2 Input Type Assignments 3 2 3 2 1 Input 1 Operation 3 2 3...

Страница 4: ......

Страница 5: ...No other control system on the market provides the flexibility functionality and configurability of the Orion M 1 1 Features The digital inputs of the Orion M can be configured as alarm inputs with a...

Страница 6: ...includes the following interface features Overview screen that displays all runtime information Profile run and monitor views Profile entry open save and download interface screens Current alarm and a...

Страница 7: ...ring to and form the UDC controllers be routed away from all high voltage and or output control wiring This will minimize the chances of electrical transients or spikes in the power control wiring fro...

Страница 8: ...UDC2500 or UDC3200 Product Manual for all other connections including power sensor and control wiring Since no two applications are the same it is up to the system designer to insure that the control...

Страница 9: ...munications link beginning with 1 up to the total number of controllers As control loops are enabled in the Orion M Configurator the Orion M will automatically use the Loop Input as the corresponding...

Страница 10: ...he Orion M Configurator the temperature units in the Orion M must match the UDC controllers for the drybulb wetbulb calculation to be performed correctly If the temperature units do not match the rela...

Страница 11: ...f the loop control is visible to the operator it is recommended that the Monitor Input Offset screen be hidden see Section 3 6 Orion Functions Startup View in the Orion M Configuration Manual or even...

Страница 12: ...M is designed to send the shed timer reset command to the UDC controller to take it out of computer set point control when the set point permission is enabled This allows control via the keypad of the...

Страница 13: ...Orion M APPENDIX FDC Orion M A 1 Appendix...

Страница 14: ...ter delivery to the first purchaser for use There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth Limitations Future Design Controls provides no warra...

Отзывы: