Orion-M

  

 

 

 

 

 

 

      

       

 

 

GETTING STARTED 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

       

 

 FDC Orion-M  2.1 

 

2  Getting Started 

The  Orion-M  requires  one  Honeywell  UDC2500  or  UDC3200  for  each  control  loop  required  in  the  system.  
Since  the  Orion-M  is  capable  of  interfacing  to  more  than  one  brand  of  controller,  refer  to  the  Orion-M  part 
number  matrix  for  the  operating  system  to  be  sure  that  the  HWSL,  CM  application  software  has  been 
provided.  The Orion-M will not operate correctly if any other version of CM application software is used with a 
Honeywell UDC2500 or UDC3200 controller.  
 
 

2.1  Installing the UDC2500/3200 Controller 

For applications requiring several loops of control or more, proper planning and arrangement of the Honeywell 
UDC  controllers  prior  to  mounting  is  critical  for  optimum  routing  of  the  controller  wiring.    For  applications 
requiring  frequent  access  to  the  controllers,  panel  mounting  provides  direct  access.   For  applications  where 
operator access to the controllers is not required, or is desired to be kept at a minimum, the controllers can be 
mounted directly inside of an enclosure.  This also reduces wiring concerns by eliminating the need to run the 
sensor, communication and control wiring for each controller to and from an enclosure door. 
 
Refer  to  the  Honeywell  UDC2500  or  UDC3200  Controller  Product  Manual  for  dimensions,  appropriate 
mounting  and  operating  conditions,  including  proper  electrical  connections.    Connect  sensor  and  control 
wiring  as  required,  paying  close  attention  to  all  wiring  precautions  and  guidelines  as  noted  in  the  controller 
manual.    It  is  recommended  that  all  sensor  and  communication  wiring,  to  and  form  the  UDC  controllers,  be 
routed  away  from  all  high  voltage  and/or  output  control  wiring.    This  will  minimize  the  chances  of  electrical 
transients or spikes in the power/control wiring from causing communications or sensor reading errors.  
 
 

2.1.1 

Communications Wiring 

Each  UDC2500/3200  control  used  in  the  Orion-M  system  is  its  own  independent  loop  control.    However,  in 
order  for  the  controllers  to  work  as  part  of  the  system,  they  must  communicate  with  the  Orion-M  control 
module  using  RS485  serial  communications.    Therefore,  each  UDC2500/3200  used  must  be  equipped  with 
the RS485 Modbus RTU communications option or they will not operate as part of the Orion-M system: 
 

DC250X-XX-

2

XXX-XXX-XX000-XX-0 

 

DC320X-XX-

2

XXX-XXX-XX000-XX-0 

 

 

 

 

 

 

 

 

 

 

 

 

Order code 

2

 designates RS-485 Modbus serial communications 

(see Honeywell UDC Product Manual for model number interpretation) 

 
Communications wiring must be run using a minimum of 24 AWG twisted-pair, copper conductors.  For short 
runs  (<  50  feet  total),  non-shielded  wiring  can  be  used  as  long  as  proper  separation  from  power/control 
conductors  is  maintained.    For  communications  wiring  where  the  total  length  will  exceed  50  feet,  up  to  the 
maximum allowed length of 650 feet, shielded twisted-pair must be used.    

 

NOTE:

 

FDC recommends the use of shielded wire for all installations regardless of the total length in order 
to maintain optimum performance and minimize the possibility of communications errors. 

 
When  using  shielded  twisted-pair,  be  sure  to  ground  the  shield  at  only  one  end,  preferably  at  the  Orion-M 
control module.  Allowing any other portion of the cable shield to come in contact with ground, or grounding 
both  ends,  will  allow  ground  loop  currents  to  flow  in  that  section  of  the  cable  shield  which  can  disrupt 
communications. 
 

Содержание Orion-M

Страница 1: ...Orion M Honeywell UDC2500 3200 Series Controller System Guide Rev C February 7 2011 Supersedes Rev B March 25 2010 Orion M Honeywell UDC2500 3200 Controller System Guide...

Страница 2: ...ion to verify that your selections are consistent with your application inputs outputs alarms limits etc If the problem persists after checking the above you can get technical assistance by dialing 1...

Страница 3: ...1 1 Communications Wiring 2 1 3 Configuring the Honeywell UDC2500 3200 Controller 3 1 3 1 Assigning the Proper Communications Settings 3 1 3 2 Input Type Assignments 3 2 3 2 1 Input 1 Operation 3 2 3...

Страница 4: ......

Страница 5: ...No other control system on the market provides the flexibility functionality and configurability of the Orion M 1 1 Features The digital inputs of the Orion M can be configured as alarm inputs with a...

Страница 6: ...includes the following interface features Overview screen that displays all runtime information Profile run and monitor views Profile entry open save and download interface screens Current alarm and a...

Страница 7: ...ring to and form the UDC controllers be routed away from all high voltage and or output control wiring This will minimize the chances of electrical transients or spikes in the power control wiring fro...

Страница 8: ...UDC2500 or UDC3200 Product Manual for all other connections including power sensor and control wiring Since no two applications are the same it is up to the system designer to insure that the control...

Страница 9: ...munications link beginning with 1 up to the total number of controllers As control loops are enabled in the Orion M Configurator the Orion M will automatically use the Loop Input as the corresponding...

Страница 10: ...he Orion M Configurator the temperature units in the Orion M must match the UDC controllers for the drybulb wetbulb calculation to be performed correctly If the temperature units do not match the rela...

Страница 11: ...f the loop control is visible to the operator it is recommended that the Monitor Input Offset screen be hidden see Section 3 6 Orion Functions Startup View in the Orion M Configuration Manual or even...

Страница 12: ...M is designed to send the shed timer reset command to the UDC controller to take it out of computer set point control when the set point permission is enabled This allows control via the keypad of the...

Страница 13: ...Orion M APPENDIX FDC Orion M A 1 Appendix...

Страница 14: ...ter delivery to the first purchaser for use There are no expressed or implied Warranties extending beyond the Warranties herein and above set forth Limitations Future Design Controls provides no warra...

Отзывы: