Installation
34
Connection to the CANopen network
Fig. 16: Connection to the CANopen network
The maximum cable length is limited by the transfer rate and the signal propagation times:
If the CAN wiring is not laid in a straight line it may be necessary to individually opti-
mise the amount and location of the terminating resistors. For instance in a star net-
work a central 60 Ohm terminating resistor may be more suitable. When the optimum
arrangement of terminating resistors is fitted, no accumulation of error frames should
be evident.
Baud rate
Maximum cable length (including stub cable)
1 000 kBit/s
25 m
500 kBit/s
100 m
250 kBit/s
250 m
125 kBit/s
500 m
50 kBit/s
1 000 m
20 kBit/s
2 500 m
10 kBit/s
5 000 m
Node 1
CAN Bus Line
Node n
GND
CAN_H
CAN_L
120
120