-57-
7.5 Operating by I/O signals
7.5.1 Operating
The motor can be operated and stopped from the external signals.
Set and operate as follows after operation input (FWD input, REV input) connect to CN4.
• Setting the “External operation signal input” parameter
The “External operation signal input” parameter (Par -> ioEn -> on / oFF) is required to change
the setting when operating or stopping the motor externally. The factory setting is “OFF”
When “The “External operation signal input” parameter is ON, External I / O control is enabled,
but the front control of the drive is disabled. When “The “External operation signal input”
parameter is OFF, External I / O control is disable, but the front control of the drive is enabled.
Power ON
Setting to the external operation
Operation signals
Motor rotates
Motor deceleration stop
Change the “External operation signal
input” parameter
Turn the FWD or REV input ON.
Operation input change from ON to OFF
I/O signal operation
Motor
Drive
I/O Signal
AC power input
Содержание Ezi-SPEED ESD-30-C
Страница 1: ......
Страница 9: ...9 2 Characteristics 2 1 Part number...
Страница 15: ...15 3 2 Dimensions 30W 60W 120W Drive 200W 400W Drive...
Страница 18: ...18 ESM 90 H 120 ESM 104 H 200 ESM 104 H 400...
Страница 19: ...19 4 3 Characteristics of motor torque 30W 60W 120W...
Страница 20: ...20 200W 400W...
Страница 63: ...63 8 2 Setting and 7 segments display 1 Monitor mode...
Страница 64: ...64 2 Input Output setting mode...
Страница 65: ...65 3 Parameter setting mode 1page...
Страница 66: ...66 3 Parameter setting mode 2page...
Страница 67: ...67 3 Parameter setting mode 3page...
Страница 68: ...68 3 Parameter setting mode 4page...
Страница 69: ...69 4 NVM saving mode...