Fantech MUAS 1600 Скачать руководство пользователя страница 8

8

fantech

 115 Vac Supply

CURRENT TRANSDUCER

NEUTRAL LINE

ONLY ONE CONDUCTOR

TO BE LOOPED THRU CENTER

 

SEE NOTE ON PAGE 9

HI VOLTAGE - SOLID LINES
LO VOLTAGE - DASHED LINES

Heater  (Oponal)

H

1

Exhaust Fan Current Sensor  +

0-5Vdc

2

L

WIRING DIAGRAM 

Makeup Air Controller (MUAC)

Exhaust fan

0-5Vdc

Set High Fan

Exhaust Fan Current Sensor -

0-10Vdc

Set Low Fan

3

Makeup Fan 0-10vdc

0-10Vdc

4

Makeup Fan  -

115/208-

230Vac 

Supply

24Vac

5

AC Common - Transformer

24Vac

6

AC Common - Damper

High Fan Speed Trim

HT

24v  

Transformer

Low Fan Speed Trim

LT

Aux. Relay Delay

AR

24Vac 7

AC Common - Heater

24Vac

8

24vac IN - Transformer

24Vac

9

24vac Out - Damper

Indicator Light Power

24Vac 10

24vac Out - Heater

11

AUX N/O

Flashing Light - Heartbeat

12

Aux COM

0-10V

NE

G

TO WIRE MUAC TO FAN REMOVE 

THE POTENTIOMETER 

FROM THE FAN CIRCUIT BOARD

AND USE TWO OF THE THREE 

TERMINALS 0-10V & NEG

115Vac 

Supply

240Vac 

Supply

Damper 

C

W1

               HEATER CONNECTIONS

10KW HEATER - 41.7 Amp Load

               24V  WIRE W1 TO #10

              24V COMMON WIRE TO #7

--------------------------------------------

20KW HEATER - 83.3 Amp Load 

           24V WIRE W1 TO #10

           24V COMMON WIRE TO #7

    

Makeup Air 

Fan

RED YEL BLU

T

S

Ma

Controller Operation and System Wiring

When the FMAC's controller receives a signal from the current transduc-
er that the compensated exhaust fan is operating, the FMAC controller's 
outputs will be activated.

The controller will provide a 24VAC signal to power the motorized 
damper to the open position.

The controller will provide a 0-10VDC signal to the makeup air supply fan 
to operate the fan at a speed proportional to the compensated exhaust 
fan's speed.

The controller will provide a 24VAC signal to enable the optional duct 
heater (if included).  Note that the duct heater includes its own operation-
al sequence, and will only operate if first enabled by the FMAC controller, 
and then only if the supply air temperature requires that heat be added.

Heater (Optional) Default Settings

Fantech recommends that the default mode be set on W1 and the default 
temperature be set at 60oF.

Figure 5.

 System Wiring Diagram

Содержание MUAS 1600

Страница 1: ...Technical Customer Support United States Tel 800 747 1762 Canada Tel 800 565 3548 Installation Manual MUAS Series Makeup Air System Controller Item 497868 Rev Date 2017 09 27...

Страница 2: ...cturer s manual Caution 1 Do not locate outside air inlet near hazardous materials or explosives 2 System shall not be installed to introduce air from crawlspaces garages attics adjacent dwelling unit...

Страница 3: ...on for delivery to the interior space The Fantech Makeup air system components and the system s duct work must be insulated to prevent the formation of condensation Fantech recommends that makeup air...

Страница 4: ...s document 1 Wall Intake Hood FML 2 Fast Clamp FC 3 Shut off Damper ADC 4 Filter cassette FGR HV 5 Makeup Air Fan prioAir EC or FKD EC 6 Silencer LD 7 Duct Heater Stelpro optional 8 Controller FMAC Fi...

Страница 5: ...D E H F G J MUAS 750 MUAS 1200 Model A B C D E F H optional G J K MUAS 1600 10 1 2 12 30 1 2 18 7 8 38 1 2 110 3 8 14 124 3 8 12 12 MUAS 2000 10 3 4 14 30 1 2 20 8 38 1 2 114 1 8 24 138 1 8 14 12 A B...

Страница 6: ...MK 1 12 10 kW heater is Stelpro model SDHR12 10K 240VIP CIR017 OTDD OEMK 12 20 kW heater is Stelpro model SDHR12 20K 240VIP CIR017 LOTDD OEMK 1 Default operating mode Setting is W1 Default temperature...

Страница 7: ...o methods 1 Using a pressure differential gauge either digital or analog as used for blower door testing measure the house pressure with respect to the outdoors across a door or window If the house pr...

Страница 8: ...ATER CONNECTIONS 10KW HEATER 41 7 Amp Load 24V WIRE W1 TO 10 24V COMMON WIRE TO 7 20KW HEATER 83 3 Amp Load 24V WIRE W1 TO 10 24V COMMON WIRE TO 7 Makeup Air Fan RED YEL BLU T S Ma Controller Operatio...

Страница 9: ...ACK OF THE MODULE AND MOUNT THE MODULE TO THE ENCLOSURE BACK PANEL USING THE 2 HOLES PROVIDED WALL MOUNTING PLATE NEMA 1 ELECTRICAL ENCLOSURE ELECTRICAL ENCLOSURE BACK PANEL 5 16 18 X 5 8 MOUNTING STU...

Страница 10: ...e CS650 10 aperture V output is approx 5 V DC Keeping the amperage reading close to 10 Amps will increase your systems accuracy Always monitor the neutral wire of the exhaust fan motor This will allow...

Страница 11: ...SOR INSTALLATION AIRFLOW FRONT DRILL O1 2 13mm 40 1016mm RECOMMENDED POSITION TEMPERATURE SENSOR DO NOT INSTALL THE SENSOR IN AN ELBOW OR A TRANSITION X X TEMPERATURE SENSOR INSTALLATION AIRFLOW FRONT...

Страница 12: ...ation for any breach of warranty WARRANTY VALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an applica...

Страница 13: ...13 fantech Notes...

Страница 14: ...14 fantech Notes...

Страница 15: ...15 fantech Notes...

Страница 16: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Отзывы: