Fantech MUAS 1600 Скачать руководство пользователя страница 3

3

fantech

Application

The Fantech Exhaust Makeup Air System is a low voltage controlled 
assembly of components which provides the automatic supply of outdoor 
air into a building. When controlled by the current sensing Fantech 
Makeup Air Controller “FMAC”, the system is suitable as compensation 
for single speed, multi-speed, and variable speed exhaust fans. 

The FMAC initiates the makeup air system upon sensing the exhaust fan 
motor current, and controls the supply of outside air into the building in 
proportion to that being exhausted. 

This system may be used to replace air being removed by a kitchen hood 
exhaust fan or other continuously or intermittently operating powered 
exhaust system. Mechanical replacement of exhaust air allows an 
exhaust system to function more effectively, helps to maintain pressure 
equilibrium between the building interior and the exterior, and allows 
for management (quantity, cleaning, tempering and location) of the 
introduction of outside air to the building’s interior space. An electric 
heater (optional) may be included as a system component. The heater 
is not intended to provide heating to the interior space, but rather to 
temper the supply of cold outdoor air before it is delivered to the building.

Due to its component-based, field-assembled nature, the Fantech Makeup 
Air System offers flexibility as to where and how it can be installed 
into a building.  The installation location should be suitable for periodic 
inspection and maintenance.  It is not required that the individual system 
components be installed in a linear (straight line) arrangement. System 
components may be connected by duct work (by others) to permit 
lengths and elbows for accommodating the physical space available for 
installation.  It is important to adhere to all instructions included with 
each system component for proper installation, however, keeping service 
clearances and straight duct lengths upstream and downstream of 
components as required.

The air discharged from the Fantech Makeup Air System will almost 
always be contained in duct work (by others), so that the supply of 
makeup air may be routed to a suitable location for delivery to the interior 
space.

The Fantech Makeup air system components and the system's duct work 
must be insulated to prevent  the formation of condensation.

Fantech recommends that makeup air be ducted to the space from where 
the compensated exhaust is being removed. For example, makeup air 
used to compensate a kitchen exhaust hood should be delivered directly 
to the kitchen space. For this same example, it is advisable that the air 
be delivered to the kitchen in such a way as to not disturb the exhaust 
air pattern at the hood. In general, this can be accomplished by locating 
the makeup air supply grille at least a few feet away from the footprint of 
the kitchen hood, and ensuring that no streams of makeup air supply are 
directed toward the area between the range top and the hood. Depending 
on the makeup air flow rate, grilles might be suitably located above 
kitchen cabinets, behind refrigerators, or simply at a convenient location 
on a wall or the ceiling.

Depending upon the version of the building code that governs the 
installation, there are potentially many code-compliant methods of 
introducing the makeup air into the building. 

Realizing this, 

Fantech deems it unacceptable to use central HVAC system 

equipment and duct work for treatment and conveyance of makeup air. 

Reasons for this include:

• Furnace manufacturers often limit the temperature of air entering 

the heat exchanger to no less than 50-55ºF. The equipment warranty 
could be voided if the limit is broken.

• Residential HVAC heating and cooling systems typically cycle on/

off with one or two stages of capacity on a signal from the space 
thermostat. To put it another way, the central HVAC system is 
intended to maintain a condition in the living space, and it only 
operates when the living space condition becomes uncomfortable. 
Since makeup air comes directly from outdoors, it is often quite 
uncomfortable. The uncomfortable makeup air would be conditioned 
only when the space thermostat is calling for action.

• The temperature difference between the indoor condition and the 

outdoor condition can at times be significant. Cold makeup air 
could cause the formation of condensation on the exterior of poorly 
insulated duct work and equipment. Very humid makeup air could 
result in condensation on the interior of poorly insulated duct work 
and equipment.

Содержание MUAS 1600

Страница 1: ...Technical Customer Support United States Tel 800 747 1762 Canada Tel 800 565 3548 Installation Manual MUAS Series Makeup Air System Controller Item 497868 Rev Date 2017 09 27...

Страница 2: ...cturer s manual Caution 1 Do not locate outside air inlet near hazardous materials or explosives 2 System shall not be installed to introduce air from crawlspaces garages attics adjacent dwelling unit...

Страница 3: ...on for delivery to the interior space The Fantech Makeup air system components and the system s duct work must be insulated to prevent the formation of condensation Fantech recommends that makeup air...

Страница 4: ...s document 1 Wall Intake Hood FML 2 Fast Clamp FC 3 Shut off Damper ADC 4 Filter cassette FGR HV 5 Makeup Air Fan prioAir EC or FKD EC 6 Silencer LD 7 Duct Heater Stelpro optional 8 Controller FMAC Fi...

Страница 5: ...D E H F G J MUAS 750 MUAS 1200 Model A B C D E F H optional G J K MUAS 1600 10 1 2 12 30 1 2 18 7 8 38 1 2 110 3 8 14 124 3 8 12 12 MUAS 2000 10 3 4 14 30 1 2 20 8 38 1 2 114 1 8 24 138 1 8 14 12 A B...

Страница 6: ...MK 1 12 10 kW heater is Stelpro model SDHR12 10K 240VIP CIR017 OTDD OEMK 12 20 kW heater is Stelpro model SDHR12 20K 240VIP CIR017 LOTDD OEMK 1 Default operating mode Setting is W1 Default temperature...

Страница 7: ...o methods 1 Using a pressure differential gauge either digital or analog as used for blower door testing measure the house pressure with respect to the outdoors across a door or window If the house pr...

Страница 8: ...ATER CONNECTIONS 10KW HEATER 41 7 Amp Load 24V WIRE W1 TO 10 24V COMMON WIRE TO 7 20KW HEATER 83 3 Amp Load 24V WIRE W1 TO 10 24V COMMON WIRE TO 7 Makeup Air Fan RED YEL BLU T S Ma Controller Operatio...

Страница 9: ...ACK OF THE MODULE AND MOUNT THE MODULE TO THE ENCLOSURE BACK PANEL USING THE 2 HOLES PROVIDED WALL MOUNTING PLATE NEMA 1 ELECTRICAL ENCLOSURE ELECTRICAL ENCLOSURE BACK PANEL 5 16 18 X 5 8 MOUNTING STU...

Страница 10: ...e CS650 10 aperture V output is approx 5 V DC Keeping the amperage reading close to 10 Amps will increase your systems accuracy Always monitor the neutral wire of the exhaust fan motor This will allow...

Страница 11: ...SOR INSTALLATION AIRFLOW FRONT DRILL O1 2 13mm 40 1016mm RECOMMENDED POSITION TEMPERATURE SENSOR DO NOT INSTALL THE SENSOR IN AN ELBOW OR A TRANSITION X X TEMPERATURE SENSOR INSTALLATION AIRFLOW FRONT...

Страница 12: ...ation for any breach of warranty WARRANTY VALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an applica...

Страница 13: ...13 fantech Notes...

Страница 14: ...14 fantech Notes...

Страница 15: ...15 fantech Notes...

Страница 16: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Отзывы: