Fantech MUAS 1600 Скачать руководство пользователя страница 7

7

fantech

Makeup Air Controller and System Startup:

Prior to beginning the setup and startup procedure, verify that the 
makeup air system is completely installed and wired, and verify that the 
compensated exhaust system is completely installed and wired.

a. Install a clean panel filter into the makeup air system’s filter cassette.
b. Energize the power circuits to;

• Makeup air fan.
• Transformer. A power indicator and heart pulse LED will illuminate 

when the FMAC is energized and ready for programming.

• Electric heater (if included). 
• The compensated exhaust system.

c. Operate the compensated exhaust fan on high speed. 
d. Press “HI” Button on makeup air controller. 
e. Operate compensated exhaust fan on low speed.
f. Press “LO” Button on makeup air controller. 
g. Operate the compensated exhaust fan at high speed and adjust the 

makeup air fan controller “HT” trim pot to produce the desired CFM 
from the makeup air fan. If the desired max CFM is not known; just set 
the pot to max at this point. You will have an opportunity to fine tune 
later.

h. Operate the compensated exhaust fan at low speed and adjust the 

makeup air fan controller “LT” trim pot to produce the desired CFM 
from the makeup air fan. If the desired min CFM is not known; just set 
the pot to min at this point. You will have an opportunity to fine tune 
later.

The FMAC is now ready for tuning.

Once the estimated required CFM of makeup air has been set it is time 
to verify the house is correctly balanced. 

During setup and balancing it is necessary that all of the build-
ing's exterior openings are tightly closed. Openings include 
windows, doors, flue dampers, etc. Also, de-energize any 
systems that employ exhaust or supply air communication with 
the outdoors. Such systems include clothes dryers, heating ap-
pliances, HRV's or ERV's, and bathroom ventilation fans. 

Energize both the makeup air system and the compensated 
exhaust system. Operate the compensated exhaust system's fan 
on high speed.

Adjust the exhaust makeup air system airflow by following one of the fol-
lowing two methods:

1. Using a pressure differential gauge (either digital or analog, as used 

for blower door testing), measure the house pressure with respect to 
the outdoors across a door or window. If the house pressure is posi-
tive with respect to the outdoors, slow down the exhaust makeup air 
fan using the high speed trim pot "HT". If the house pressure is nega-
tive with respect to the outdoors, speed up the exhaust makeup air 
fan using the high speed trim pot "HT". Repeat this procedure with the 
compensated exhaust fan on low speed and using the  "LT" trim pot.

If a slightly positive or negative (recommended no more than 
5 Pa [0.02" w.g.] indoor pressure is desired, such a scheme can 
be employed by this method, balancing to the desired pressure 
scheme.

After adjusting the high and low speed trim the first time, repeat the pro-
cedure as necessary until the system automatically operates sufficiently 
according to the desired pressure scheme at low, high and all intermedi-
ate speeds.

2. If a pressure differential gauge is not available, slightly open a window 

approximately 1/2" (12mm) in the center of a building wall and check if 
the airflow is moving in or out. This can be done by feel, or by using a 
light piece of tissue or paper, or one could use an anemometer. If the 
flow is going out, the house is under positive pressure and the exhaust 
makeup air fan needs to be slowed down using the high speed trim pot 
"HT". If the airflow is coming in, the house is under negative pressure 
and the exhaust makeup air fan speed needs to be increased using the 
high speed trim pot "HT". Repeat this procedure with the compensated 
exhaust fan on low speed and using the "LT" trim pot. With both the 
"HT" and "LT" trim pots adjusted the air pressure in the house will be 
stabilized throughout the compensated exhaust fan range.

The FMAC is now ready for service. At this point the makeup air system 
is controlled by the FMAC. As the exhaust fan speed is changed depend-
ing on use, the makeup air fan will sense the current draw and supply the 
proper amount of filtered fresh air into the house to compensate for the 
exhaust air.  If the optional electric heater is installed, the supply air will 
be warmed to the desired set point.

Figure 4.

 FMAC Circuit Board

Содержание MUAS 1600

Страница 1: ...Technical Customer Support United States Tel 800 747 1762 Canada Tel 800 565 3548 Installation Manual MUAS Series Makeup Air System Controller Item 497868 Rev Date 2017 09 27...

Страница 2: ...cturer s manual Caution 1 Do not locate outside air inlet near hazardous materials or explosives 2 System shall not be installed to introduce air from crawlspaces garages attics adjacent dwelling unit...

Страница 3: ...on for delivery to the interior space The Fantech Makeup air system components and the system s duct work must be insulated to prevent the formation of condensation Fantech recommends that makeup air...

Страница 4: ...s document 1 Wall Intake Hood FML 2 Fast Clamp FC 3 Shut off Damper ADC 4 Filter cassette FGR HV 5 Makeup Air Fan prioAir EC or FKD EC 6 Silencer LD 7 Duct Heater Stelpro optional 8 Controller FMAC Fi...

Страница 5: ...D E H F G J MUAS 750 MUAS 1200 Model A B C D E F H optional G J K MUAS 1600 10 1 2 12 30 1 2 18 7 8 38 1 2 110 3 8 14 124 3 8 12 12 MUAS 2000 10 3 4 14 30 1 2 20 8 38 1 2 114 1 8 24 138 1 8 14 12 A B...

Страница 6: ...MK 1 12 10 kW heater is Stelpro model SDHR12 10K 240VIP CIR017 OTDD OEMK 12 20 kW heater is Stelpro model SDHR12 20K 240VIP CIR017 LOTDD OEMK 1 Default operating mode Setting is W1 Default temperature...

Страница 7: ...o methods 1 Using a pressure differential gauge either digital or analog as used for blower door testing measure the house pressure with respect to the outdoors across a door or window If the house pr...

Страница 8: ...ATER CONNECTIONS 10KW HEATER 41 7 Amp Load 24V WIRE W1 TO 10 24V COMMON WIRE TO 7 20KW HEATER 83 3 Amp Load 24V WIRE W1 TO 10 24V COMMON WIRE TO 7 Makeup Air Fan RED YEL BLU T S Ma Controller Operatio...

Страница 9: ...ACK OF THE MODULE AND MOUNT THE MODULE TO THE ENCLOSURE BACK PANEL USING THE 2 HOLES PROVIDED WALL MOUNTING PLATE NEMA 1 ELECTRICAL ENCLOSURE ELECTRICAL ENCLOSURE BACK PANEL 5 16 18 X 5 8 MOUNTING STU...

Страница 10: ...e CS650 10 aperture V output is approx 5 V DC Keeping the amperage reading close to 10 Amps will increase your systems accuracy Always monitor the neutral wire of the exhaust fan motor This will allow...

Страница 11: ...SOR INSTALLATION AIRFLOW FRONT DRILL O1 2 13mm 40 1016mm RECOMMENDED POSITION TEMPERATURE SENSOR DO NOT INSTALL THE SENSOR IN AN ELBOW OR A TRANSITION X X TEMPERATURE SENSOR INSTALLATION AIRFLOW FRONT...

Страница 12: ...ation for any breach of warranty WARRANTY VALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an applica...

Страница 13: ...13 fantech Notes...

Страница 14: ...14 fantech Notes...

Страница 15: ...15 fantech Notes...

Страница 16: ...Fantech reserves the right to make technical changes For updated documentation please refer to www fantech net Fantech...

Отзывы: