Notes
All wiring is by others. Wiring terminations for each component are
contained in their respective installation instructions.
Placement of components is up to the discretion of the installing
contractor.
For applications with small current loads (such as less than 2 Amps),
wrap the monitored conductor through the sensor aperture several times
to increase the current measured by the sensor.
Example:
Exhaust fan amperage rating of 2 amps.
One pass through the CS650-10 aperture V output is approx. 1Vdc
Five passes through the CS650-10 aperture V output is approx. 5 V DC
Keeping the amperage reading close to 10 Amps, will increase your
systems accuracy.
Always monitor the neutral wire of the exhaust fan motor. This
will allow proper amperage readings of variable as well as multi-
speed exhaust fans.
Optional Heater
Installation Configuration & Clearances
BLOWER
ELBOW
TRANSITION
FILTER
24''
610mm
MINIMUM
FROM
TOP
Minimum distance to avoid overheating of the elements
Clearance
Vertical Flow
Horizontal Flow
X
X
X
FRONT
Do not install an access panel in the duct any closer than 24” before or after the heater element. Follow local codes for installing this heater.
WALL, CEILING OR OBSTRUCTION
ZERO CLEARANCE
[BOTTOM, BACK & SIDES]
1/2''
13mm
MINIMUM
6''
152mm
MINIMUM
SIDE