background image

5

fantech

Maintenance

Air Filter (Fig. 7)

The air filter should be checked regularly. Operating the dehu-

midifier with a clogged filter will reduce efficiency. The filter can be

vacuum cleaned to remove dust. To access the filter media, slide

the filter frame up until it clears the dehumidifier cabinet. Remove

the filter media from behind the frame and vacuum. Reverse pro-

cedure to re-install the filter and frame into the dehumidifier.

Storage

Freezing temperatures and biological growth must be considered

before  storing  the  dehumidifier.  The  dehumidifier  should  be

flushed with a biofungicide before storing. When storing the unit,

ensure  that  water  has  been  removed  from  the  reservoir  and

hose. This will prevent damage caused by freezing temperatures

and to prevent biological growth. Use the pump purge button to

remove water and biofungicide chemicals from the dehumidifier.

Stacking (Fig.9)

The dehumidifiers can be stacked on top of each other. The

wheels from the upper unit must be resting in the cradle of

the lower unit. 

DO NOT STACK MORE THAN TWO HIGH. 

External Cleaning

Use  a  non-flammable  mild,  non-abrasive  soap  and  clean

water solution to clean the dehumidifier. Wipe dry.

Internal Cleaning

Disconnect dehumidifier from power supply. 

Light cleaning:

Remove the air filter and spray evaporator

coil  with  water.Remove  the  two  upper  screws  from  the  front

hood. 

Heavy cleaning:

Remove two upper screws from front hood.

Open  hood.  Spray  water  at  coils.  Close  hood  and  replace

screws. (Fig. 8)

Fig. 7

Fig. 8

Electrical Shock Hazard

Plug into a grounded 3 prong outlet.
Do not remove ground prong.
Do not use an adapter.

WARNING

Disconnect power supply before cleaning.
Failure to follow these instructions can result in death,

fire, or electrical shock.

Venting / Ducting (Fig. 6)

Twin  rear  outlets  can  accommo-

date two individual 5” ducts or one

10”  lay  flat  duct  to  be  attached.

This allows for warm dry air to be

directed into different areas.

Fig. 6

Cleaning

Fig. 9

Service

A qualified refrigeration technician must service all refriger-

ant leaks. 
WARNING: The dehumidifier uses a high pressure refrigerant

system and high voltage circuitry which could present a health

hazard resulting in death, serious bodily injury, and/or property

damage. Only qualified service people should service this unit.

CAUTION:

Do not operate unit without the front hood secured in

place.
The serial data plate is located on the underside of the dehumid-

ifier. For service information contact 1-800-565-3548.

(2)

Figure 8

Troubleshooting

Service

A qualified refrigeration technician must service all refrigerant leaks.

The Unit is NOT working:

•  Has the breaker tripped? – Reset breaker
•  If in a wet area, is the unit plugged into a GFI protected circuit? – Excessive 

moisture will trip GFI. Remove from area.

•  Is the unit being run off a generator? - Check output does not fluctuate 

as the unit will not operate at low voltage.

•  If using an extension cord - Is the cord of the correct gauge for the 

distance run? (14 AWG up to 25’ and 12 AWG over 25’). Note: Verify 
voltage while unit is starting. Start up will cause the highest current draw 
and largest voltage drop. Even if plugged directly to outlet there can be 
a significant voltage drop. Never assume the voltage is ok without 
verifying.

The unit shuts down and displays an error code. 

ER 1: Overflow switch remaining closed for >2 minutes.
•  Plugged or kinked drain hose – Remove obstruction
•  Bad connection in pump circuit – Check connections
•  Defective condensate pump – Replace

ER 2: Internal pressure switch indicates refrigerant pressure is too high.
•  Air filter is dirty or plugged – Clean or replace air filter
•  The coil is dirty – Clean the coil
•  Loose or faulty electrical connections to pressure switch – check 

connections

•  Fan is not working – Replace
•  Defective pressure switch – replace

The unit continually ices up: Note that some ice buildup on the evaporator coil 
is normal but airflow should not be blocked.

•  Is warm air blowing out the back of the unit? - No warm air, ambient 

temperature may be too low. Raise temperature with supplementary 
source.

•  Is the air filter clean and airflow unobstructed? – Clean filter. Unit should 

have a minimum of 10” clearance all around it.

•  Dirty evaporator coil? – Clean coil.

Unit moves some water but not as much as expected:

•  Air filter dirty or airflow obstructed - Unit should have a minimum of 10” 

clearance all around it. Clean air filter and ensure adequate airflow/space 
around unit.

•  Evaporator coil dirty – Clean coil.
•  Restrictive or kinked exhaust ducting (if used) – Straighten out ducting.

Fan does not run. Compressor runs briefly but cycles on/off:

•  Loose connection in fan circuit – Check connections.
•  Fan obstructed and not turning – Remove obstruction.
•  Defective fan – Replace fan.
•  Defective control board – Replace control board.

Cleaning

Disconnect power supply before cleaning
Failure to follow these instructions can result in death, fire, or electrical shock

External Cleaning

Use a non-flammable mild, non-abrasive soap and water solution. Wipe dry.

Internal Cleaning

Disconnect dehumidifier from power supply.

Light cleaning: Remove the air filter and spray evaporator coil with water. 

Heavy cleaning: Remove two upper screws from front hood. Open hood. Spray water at coils. Close 
hood and replace screws. (figure 8)

Care must be taken to insure coil fins are not damaged, as damaged fins can restrict airflow 
and reduce the unit's ability to produce water. 

Storage

Freezing temperatures and biological growth must be considered before storing the dehumidifier. To 
prevent the biological growth, spray an evaporator cleaner on the coils and rinse into the drainage 
system. You must also purge the excess liquid from the pump using the manual purge function to 
prevent issues with freezing storage environments. 

Содержание EPD150LR

Страница 1: ...che NB E4S 3M5 Tel 800 565 3548 Fax 877 747 8116 EPD Series Industrial Dehumidifier Deshumidificador industrial Industrial Dehumidifier Déshumidificateur industriel Deshumidificador industrial Operating Instructions Guide d utilisation Instrucciones de uso Read and Save These Instructions Lisez et conservez ces instructions Lea y guarde estas instrucciones 1 3 5 405037 Fantech Ltd 1 800 565 3548 E...

Страница 2: ...cte a un contacto de pared de conexión a tierra de 3 terminales No quite la terminal de conexión a tierra No use un adaptador No use un cable elétrico de extensión No seguir estas instrucciones puede ocasional la muerte incendio o choque eléctrico ADVERTENCIA El deshumidificador utiliza un sistema de líquido refriger ante de alta presión y un circuito eléctrico de alto voltaje que podrían resultar...

Страница 3: ...te forming on the coil The unit will stay in run mode for variable length of time depending on the ambient conditions Pressing the power button figure 1 will send the unit in shut down mode see below Defrost Mode During the defrost mode the indicator light will turn on figure 2 the compressor will be off and the fan will continue to run The pump purge will be activated automatically The defrost cy...

Страница 4: ...ff by pressing the power button When the dehumidifier is started the hour meter will display the cumulative hours Pump Purge Button Fig 2 In normal operation the pump will automat ically empty the reservoir Pressing this but ton allows manual emptying of the reservoir Press once and the pump will operate for 20 seconds Press and hold the button and the pump will activate for 30 seconds Always manu...

Страница 5: ... area Is the unit being run off a generator Check output does not fluctuate as the unit will not operate at low voltage If using an extension cord Is the cord of the correct gauge for the distance run 14 AWG up to 25 and 12 AWG over 25 Note Verify voltage while unit is starting Start up will cause the highest current draw and largest voltage drop Even if plugged directly to outlet there can be a s...

Страница 6: ... E2 E3 E1 E5 E4 J1 J3 COMPRESSOR O L C R S CONDENSATE PUMP CAPACITOR BLOWER 14uF BLOWER WHITE THERMISTOR FLOAT CAPACITOR COMPRESSOR 60uF BLUE BROWN BLACK BROWN WHITE 2 78119 001 REV 01 WHITE BLACK BLUE BLUE WHITE BLACK WHITE BROWN BLACK RED WHITE WHITE J2 SWITCH PRESSURE ...

Страница 7: ...o apagado inmediatamente Modo de funcionamiento Durante el modo de funcionamiento el compresor está funcionando lo que hace que se enfríe el evaporador dando como resultado la formación de condensación en la bobina La unidad permanecerá en modo de funcionamiento durante una cantidad variable de tiempo dependiendo de las condiciones ambientales Si se pulsa el botón de encendido figura 1 se enviará ...

Страница 8: ...on Fig 1 The dehumidifier is turned on or off by pressing the power button When the dehumidifier is started the hour meter will display the cumulative hours Pump Purge Button Fig 2 In normal operation the pump will automat ically empty the reservoir Pressing this but ton allows manual emptying of the reservoir Press once and the pump will operate for 20 seconds Press and hold the button and the pu...

Страница 9: ...refrigerant system and high voltage circuitry which could present a health hazard resulting in death serious bodily injury and or property damage Only qualified service people should service this unit CAUTION Do not operate unit without the front hood secured in place The serial data plate is located on the underside of the dehumid ifier For service information contact 1 800 565 3548 2 Figure 8 Ca...

Страница 10: ...stá sucio u obstruido Límpielo o sustitúyalo La bobina está sucia Límpiela Conexiones eléctricas flojas o defectuosas hacia el interruptor de presión Verifique las conexiones El ventilador no funciona Sustitúyalo Interruptor de presión defectuoso Sustitúyalo La unidad se congela continuamente Tenga en cuenta que es normal la acumulación de cierta cantidad de hielo en el evaporador pero no debe blo...

Страница 11: ... J3 COMPRESSOR O L C R S CONDENSATE PUMP CAPACITOR BLOWER 14uF BLOWER WHITE THERMISTOR FLOAT CAPACITOR COMPRESSOR 60uF BLUE BROWN BLACK BROWN WHITE 2 78119 001 REV 01 WHITE BLACK BLUE BLUE WHITE BLACK WHITE BROWN BLACK RED WHITE WHITE J2 SWITCH PRESSURE Diagrama de cableado ...

Страница 12: ...anty form and retain it in the event warranty service is required 4 Proof of purchase date will be required for warranty claims Please retain bills of sale for proof 5 Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply to you This warranty gives specific legal rights and the purchaser may have other rights ...

Страница 13: ...arantía y conservarlo para poder utilizarlo en caso de que sea preciso dar servicio al producto 4 Para cualquier reclamación de garantía será preciso contar con una prueba de compra con fecha Recuerde guardar el recibo como comprobante de venta 5 En algunos estados no se permite la exclusión o limitación de daños consecuentes o secundarios en estos casos la limitación anterior podría no aplicar a ...

Страница 14: ...14 fantech NOTES ...

Страница 15: ...15 fantech NOTAS ...

Страница 16: ...technical changes For updated documentation please refer to www fantech net Fantech Fantech se reserva el derecho de hacer modificaciones técnicas en cualquier momento Para obtener la documen tación actualizada por favor consulte www fantech net ...

Отзывы: