Wiring Procedure

Step 1.

Remove the screws securing the terminal box cover plate located on the 
side of the fan. All fan motor connections are prewired to an electrical 
terminal strip. A 3/8" romex type cable restraint connector will be 

needed to secure the wiring through the knockout provided on the side of 
the terminal box. 

Step 2.

Bring incoming electrical service through the romex connector and the 
fan knockout. Be sure to place the connector nut over the wiring coming 
into the terminal box. There are three open ports on the terminal strip. 
Using a small regular screwdriver, tighten the Neutral (White) wire of the 
incoming supply under the open terminal labeled "N". Tighten the Line 
(Black) wire of the incoming supply under the open terminal labeled "L". 
Tighten the Ground (Green) wire of the incoming supply under the open 
terminal marked "     ". For reference, a wiring diagram is included on 
the inside of the terminal box lid.

Step 3.

Secure the romex connector. Secure the incoming supply with the romex 
connector. Replace the fan terminal box cover.

Illustration 5

DBF110 Wiring – Fan and Pressure Switch

Blue

Brown

Power
to Fan

Red

White

Black

Green

Terminal block in 

fan wiring box

Neutral

115V Line (Supply)  Electrical supply, 115V

Ground

Capacitor

Motor 

Leads

Brown (Z2)

Blue (U2)

Black (TK)

Capacitor

Neutral side of 

115V supply

Line side of 

115V supply

Fan Only Wiring (Reference for Troubleshooting Step 8c)

Black

N

L

Maintenance

Prior to performing Steps 1 - 4, be certain that the electrical 

supply to the fan/switch is turned off.

If fan fails to start when the dryer cycle begins, please follow the 
procedure listed below:
1.  Check the incoming supply for proper voltage.
2.  Consult schematic shown above (also included on inside of fan wiring 

terminal lid) to ensure proper connection.

3.  If possible, use a meter to test for continuity across the fan motor 

leads. In order to do this, the capacitor and pressure switch must be 
disconnected (do not test the capacitor - it will not meter continuity). 
If motor leads show continuity, rewire the fan, capacitor and 
pressure switch.

4.  Turn on the electrical supply and restart the dryer cycle. Check to be 

certain that fan starts.

If fan still fails to start after performing Steps 1 – 4, continue following 

the procedure as listed below: 

5.  Verify that the pressure switch diaphragm is vertical as shown in 

Illustration 2 of these instructions. If the diaphragm is not vertical, 

reposition the pressure switch and check for fan operation against 
another dryer cycle. 

6.  Verify that the tubing is not crimped and that the tubing connector 

nipples are not obstructed.

7.  If switch diaphragm is vertical and fan still fails to start, with the 

electrical supply on: 

a.  Remove the tubing from the nipple on the fan and blow gently 

into the tubing; 

b.  If fan starts, consult Fantech for additional technical support.

8.  If fan fails to start after blowing into the tubing:

a.  Disconnect incoming power supply at the source.
b. Remove the pressure switch leads from the wiring terminal 

block

c.  Connect the incoming power supply directly to the fan motor 

as shown in "FR110 Wiring" diagram below.

d.  Turn on power to fan.

9.  If fan fails to start, please consult Fantech for additional technical 

support.

Recommended Maintenance
1. Since fan bearings are sealed and provided with an internal lubricating 

material, no additional lubrication is necessary.

2. Fan impeller may accumulate lint. Periodic inspection, based upon 

dryer usage, should be performed to ensure that the fan impeller is 
not obstructed or loaded with lint. Under normal conditions, fan should 
be inspected a minimum of every Six (6) Months. Note: Excessive 

booster fan noise or vibration may be an indication of lint buildup on the 
impeller. To inspect and clean the impeller:

  a.  Disconnect the incoming power supply at the source.
  b. Remove the duct from the fan inlet and remove any lint buildup on the 

impeller.

  c. Reconnect the duct to the fan. Turn power supply on.

Troubleshooting

Содержание DBF4XL

Страница 1: ...ficateur de séchoir Booster Secadora DBF110 Kit Includes Dryer Booster Fan 1 pc Fan Mounting Bracket and Hardware 1 pc Small Wall Sign Indicating Proper Operation Procedure 1 pc La trousse du DBF110 inclus Ventilateur en ligne 1 pc Support de montage pour le ventilateur avec quincaillerie 1 pc Petit panneau indiquand la bonne procédure d opération 1 pc El DBF110 incluye Ventilador de Refuerzo de l...

Страница 2: ...d tiene piezas rotativas hay que tomar precauciones de seguridad durante la instalación operación y mantenimiento 3 PRECAUCION Sólo para Ventilación en General No trate de Utilizarse como Extractor de materiales y Vapores Peligrosos o Explosivos 4 El motor el capacitor y el interruptor de presión del ventilador vienen cableados de fábrica Veillez à lire et conserver ces instructions pour leur cons...

Страница 3: ...foulements Suivez les instructions données et les normes de sécurité communiquées par le fabricant telles que celles publiées par l Association nationale de protection contre les incendies National Faire Protection Association NFPA l Association américaine des ingénieurs en chauffage réfrigération et climatisation American Society of Heating Refrigeration and Air Conditioning ASHRAE et les autorit...

Страница 4: ...sitive pressure sensing switch which recognizes dryer operation and activates the booster fan from an independent electrical circuit This eliminates connections through the dryer circuit which may void the manufacturers warranty as well as manual systems which require the attention of the operator or costly current temperature sensing systems The electricity to the booster fan is connected in seri...

Страница 5: ...o isolate any vibration and prevent the transmission of sound through the structure Be careful not to overtighten Fan mounting can be in any angle see ill 2 however vertical mounting is recommended to reduce condensation buildup in the fan If a horizontal installation is necessary and condensation buildup may pose a problem a hole drilled in the bottom of the housing along with an NPT insert by ot...

Страница 6: ... do this the capacitor and pressure switch must be disconnected do not test the capacitor it will not meter continuity If motor leads show continuity rewire the fan capacitor and pressure switch 4 Turn on the electrical supply and restart the dryer cycle Check to be certain that fan starts If fan still fails to start after performing Steps 1 4 continue following the procedure as listed below 5 Ver...

Страница 7: ...du rupteur de détection de la pression Le DBF110 est equipepé avec le mano contact DB10 breveté de Fantech Le DB10 de Fantech est un rupteur de détection de pression positive qui identifie le fonctionnement du séchoir et active le ventilateur d amplification à partir d un circuit électrique indépendant Cela élimine non seulement les connexions transitant par les circuits du séchoir ce qui peut en ...

Страница 8: ...éduire l accumulation de condensation dans le ventilateur Si un montage vertical s avère nécessaire et que l accumulation de condensation se révèle être un problème potentiel le perçage d un trou d environ 1 cm pouces dans le fond du boîtier accompagné d un embout fileté NPT fourni par autre et d une conduite d écoulement permettra l écoulement de la condensation 3ème Étape Le montage du ventilate...

Страница 9: ...ité n y sera mesurée Si les fils d amenée indiquent une continuité recâblez le ventilateur le capaciteur et le rupteur de pression 4 Rebranchez l alimentation électrique et redémarrez le cycle du séchoir Vérifiez que le ventilateur démarre Si le ventilateur ne démarre toujours pas après que vous êtes passés par les étapes 1 4 continuez la procédure telle qu indiqué ci dessous 5 Vérifiez que le dia...

Страница 10: ...nexiones deben sellarse adecuadamente para impedir fugas y pérdida de rendimiento del ventilador Las conexiones flexibles del conducto entre la conexión de la secadora y el conducto de escape se deben estirar para que queden lo más lisas posible Operación del Interruptor Sensor de Presión El DBF110 de Fantech está equipado con un interruptor de presión DB10 patentado por FanTech El DB10 de Fantech...

Страница 11: ...servicio Vea las ilustraciones anteriores Paso 2 Soporte para Montaje Utilice los tornillos tirafondo para fijar el soporte de montaje a una viga en el sitio seleccionado El soporte está provisto de anillos protectores para aislar cualquier vibración y evitar la transmisión de ruidos a través de la estructura Tenga cuidado de no apretar los tornillos en exceso Aunque el ventilador se puede instala...

Страница 12: ... los contactos del motor del ventilador Para esto hay que desconectar el capacitor y el interruptor de presión No compruebe el capacitor ya que el mismo no da continuidad Si los contactos del motor tienen continuidad vuelva a conectar el ventilador el capacitor y el interruptor de presión 4 Conecte la alimentación eléctrica y reactive el ciclo de la secadora Compruebe la activación del ventilador ...

Страница 13: ...tallation for any breach of warranty WARRANTY VALIDATION The user must keep a copy of the bill of sale to verify purchase date These warranties give you specific legal rights and are subject to an applicable consumer protection legislation You may have additional rights which vary from state to state This warranty does not apply to any Fantech product or part which has failed as a result of faulty...

Страница 14: ... d usine en matière de qualité d exécution ou de matériau Il sera peut être nécessaire de retourner le produit à l usine Fantech accompagné d une copie du contrat de vente et du numéro d autorisation de retour POUR RETOURNER UN PRODUIT À L USINE VOUS DEVEZ Obtenir un numéro d autorisation de retour pour ce faire communiquer avec Fantech aux États Unis au numéro 1 800 747 1762 ou au Canada au numér...

Страница 15: ...instalación o reinstalación por incumplimiento de la garantía VALIDACIÓN DE LA GARANTÍA El usuario debe conservar una copia de la constancia de compraventa para verificar la fecha de compra Estas garantías le otorgan derechos legales específicos y están sujetas a una legislación aplicable para protección del consumidor Usted puede tener derechos adicionales que varían de estado en estado Esta gara...

Страница 16: ... net Fantech Fantech se réserve le droit de faire des changements techniques Pour de la documentation à jour s il vous plaît se référer au www fantech net Fantech se reserva el derecho de hacer modificaciones técnicas en cualquier momento Para obtener la documen tación actualizada por favor consulte www fantech net ...

Отзывы: