Circuit breaker trip. This shall start the reclosing cycles. This start may arise either from the trip
itself, or from an external input if external protection is fitted.
When blocked, the recloser has are two possible paths, depending on if the locked mode is the result
of:
✓
Circuit breaker closing (from manual or remote control): it switches to Standby
✓
Unexpected condition from a reclose cycle: it switches to Safe time.
There are 4 logic outputs “79N# Start” in the configurable logic. Default configuration is as follow:
Reclose Condition
Default Configuration
79N1 Start
General Trip AND Standby
79N2 Start
General Trip AND 79 Reclose 1
79N3 Start
General Trip AND 79 Reclose 2
79N4 Start
General Trip AND 79 Reclose 3
8.1.1
Counter to record the number of reclosings
SILG relay has a counter that registry the reclosing actions.
8.2 Function 25. Synchronism check
The synchro-check function is designed to give a time window in which the voltage in both sides of the
switch are in sync. The voltage of both ends of the switchgear must comply three conditions that to
ensure that there is synchronization:
-
Same module
-
Same phase
-
Same frequency
Associated with the function, we have a line voltage and bar voltage monitoring unit, which will define
the state of the line and the bar, being able to give the following combinations:
-
Death Line - Dead Bar (DLDB)
-
Death Line - Live Bar (DLLB)
-
Live Line - Dead Bar (LLDB)
-
Live Line - Live Bar (LLLB)
This control function can be set by using the following parameters:
Function
Description
Minimum
Maximum
Step
Unit
Default
25
Synchronism check
Dead Tap
0.08
2.00
0.01
xUn
0.50
Live Tap
0.08
2.00
0.01
xUn
0.70
Voltage Supervision Time
0.060
300.000
0.001
s
3.000
Содержание SIL-G
Страница 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Страница 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Страница 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Страница 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Страница 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Страница 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Страница 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Страница 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Страница 28: ...www fanox com Rev 01 28 151...
Страница 46: ...www fanox com Rev 01 46 151 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 69: ...www fanox com Rev 01 69 151 General trip...
Страница 88: ...www fanox com Rev 01 88 151...
Страница 89: ...www fanox com Rev 01 89 151...
Страница 90: ...www fanox com Rev 01 90 151...
Страница 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Страница 150: ...www fanox com Rev 01 150 151 NOTES...
Страница 151: ...www fanox com Rev 01 151 151...