![FANOX SIL-G Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/fanox/sil-g/sil-g_user-manual_4588716045.webp)
Rev.01
45/151
Zone 2
: We supply the machine with the nominal current. Thermal image evolutions so as to get the
value of the thermal balance corresponding to one time the nominal current Th = (I/It)
2
= 82%. The time
that it takes in getting the thermal balance depends on the adjusted heating constant.
Zone 3
: Once reached the thermal image corresponding to the application of one time the nominal
current, we apply 1.2 times the nominal current. Therma image will evolution so as to get the thermal
balance corresponding to 1.2 times the nominal current Th = (I/It)
2
= 119%. This would occur if we had
the permission of the thermal function disabled. If the permission is disabled, 49 protection function
performs when the thermal image reaches the value of 100%. Once tripped, current stops and thermal
image is getting cool based on the cooling constant.
Zone 4
: Before getting totally cool, nominal current is applied again and thermal balance is reached
once passed the time determined by the heating thermal constant.
Thermal image protection alarm bit is active if the thermal image measurement is over the adjusted
alarm level.
Thermal image protection trip bit is active when the measurement of the thermal image is over 100%
and it is reset when the measurement of the thermal image is under the adjusted alarm level.
4.10.2 Thermal image with memory
Thermal image is stored in non-volatile RAM memory periodically every second. By this way, though
the relay loses the power supply, it will keep the thermal status of the machine.
4.10.3 Thermal image measurement display. Reset.
Thermal image measurement is displayed on Measurement menu. Thermal image value reset is
possible in Commands menu (Reset TI). This command reset the value of the thermal image to the
value set in the alarm level.
Содержание SIL-G
Страница 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Страница 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Страница 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Страница 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Страница 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Страница 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Страница 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Страница 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Страница 28: ...www fanox com Rev 01 28 151...
Страница 46: ...www fanox com Rev 01 46 151 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 69: ...www fanox com Rev 01 69 151 General trip...
Страница 88: ...www fanox com Rev 01 88 151...
Страница 89: ...www fanox com Rev 01 89 151...
Страница 90: ...www fanox com Rev 01 90 151...
Страница 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Страница 150: ...www fanox com Rev 01 150 151 NOTES...
Страница 151: ...www fanox com Rev 01 151 151...