Rev.01
140/151
Timing accuracy: ±0.5% or ±30 ms (greater of both)
Function 59N/G-1
Function 59N/G-2
Function enable: No/Alarm/Trip
Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Time delay: 0.020 to 300.000 s (step 0.001 s)
Reset time: 0.020 to 300.000 s (step 0.001 s)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Timing accuracy: ±0.5% or ±30 ms (greater of both)
Function 47
Function enable: No/Alarm/Trip
Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Time delay: 0.020 to 300.000 s (step 0.001 s)
Reset time: 0.020 to 300.000 s (step 0.001 s)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Timing accuracy: ±0.5% or ±30 ms (greater of both)
Function 59L (*)
Function enable: No/Alarm/Trip
Voltage tap: 0.08 to 2.00 xUn (step 0.01xUn)
Time delay: 0.020 to 300.000 s (step 0.001 s)
Reset time: 0.020 to 300.000 s (step 0.001 s)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Timing accuracy: ±0.5% or ±30 ms (greater of both)
Function 32-1
Function 32-2
Function 32-3
Function 32-4
Function enable: No/Alarm/Trip
Activation level: 0.08 to 2.00 xSn (step 0.01xSn)
Operating angle: 0 to 359º (step 1º)
Time delay: 0.020 to 300.000 s (step 0.001 s)
Activation level: 100%
Deactivation level: 95%
Instantaneous deactivation
Timing accuracy: ±0.5% or ±30 ms (greater of both)
Function 81-1
Function 81-2
Function 81-3
Function 81-4
Function enable: No/Alarm/Trip
Type: Underfrequency or overfrequency
Activation level: 45.000 a 65.000 Hz (step 0.001 Hz)
Time delay: 0.020 a 300.000 s (step 0.001 s)
Reset time: 0.020 a 300.000 s (step 0.001 s)
Function blocked if phase B voltage is lower than 20 volts
Activation level: 100%
Underfrequency reset level: activation level + 50mHz
Overfrequency reset level: activation level - 50 mHz
Temporized deactivation
The frequency measurement is an average value of the frequency measured during 8 cycles.
The accuracy of the Time Delay is the adjusted value plus the necessary time to achieve the
measurement during 8 cycles.
Function 81R-1
Function 81R-2
Function enable: No/Alarm/Trip
Type: Increase/Decrease
Activation level: 0.100 to 5.000 Hz/s (step 0.001 Hz/s)
Содержание SIL-G
Страница 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Страница 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Страница 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Страница 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Страница 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Страница 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Страница 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Страница 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Страница 28: ...www fanox com Rev 01 28 151...
Страница 46: ...www fanox com Rev 01 46 151 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 69: ...www fanox com Rev 01 69 151 General trip...
Страница 88: ...www fanox com Rev 01 88 151...
Страница 89: ...www fanox com Rev 01 89 151...
Страница 90: ...www fanox com Rev 01 90 151...
Страница 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Страница 150: ...www fanox com Rev 01 150 151 NOTES...
Страница 151: ...www fanox com Rev 01 151 151...