4.11  Function 37. Instantaneous phase undercurrent 

This protection function can be set by using the following parameters: 

Function 

Description 

Minimum 

Maximum 

Step 

Unit 

Default 

37 

Instantaneous phase undercurrent 

Function Enable 

No/Alarm/Trip 

No 

Current Tap 

0.010 

30.000 

0.001 

xIn 

0.500 

Minimum Level 

0.000 

1.000 

0.001 

xIn 

0.000 

Time delay 

0.060 

300.00 

0.001 

0.200 

 

The setting “Minimum level” indicates the minimum level of current it is necessary to measure to work 
with the function. This is, if the measured current is lower than the “Minimum Level” setting, the function 

will not trip although this current is lower than the tap.  

The  time  delay  is  independent  from  the  operating  current  flowing  through  the  relay,  so  if the  phase 
current drops below its predetermined value for an equal or greater amount of time than this preset 
value, the protection function activates (trips) and does not reset itself until the average value of the 
phase exceeds the point of current pick-up. 

The function activates at 100% of the preset input and deactivates at 105%. The reset is instantaneous. 

The accuracy of the Time Delay is equal to the set time delay ±30ms or ±0.5% (whichever is greater). 

 

4.12  Function AFD. Arc Flash Detection 

This protection function can be set by using the following parameters: 

Function 

Description 

Minimum 

Maximum 

Step 

Unit 

Default 

AFD 

Arc Flash Detection 

Function Enable 

No/Alarm/Trip 

No 

Current Tap 

20 

xIn 

Time delay 

samples 

 

The setting “Time delay” indicates the number of samples of the measurement that the relay will take 

before the trip. 

The arc flash can be detected by two different methods: 

 

By current: When the current of the line is higher than the one set in “current tap” the protection 

will trip. 

  By light: When arc flash sensor connected to the relay detects the light due to the arc appeared 

in the circuit breaker, it will trip. 

To activate the high-speed output, it is necessary to apply minimum 35Vdc. 

 

Содержание SIL-G

Страница 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...

Страница 2: ...NCTIONS 30 4 1 Function 50 Instantaneous phase overcurrent 30 4 2 Function SOTF Switch On To Fault 31 4 3 Function 67 Inverse time directional phase overcurrent 31 4 4 Function 50G Instantaneous measu...

Страница 3: ...unction 79 AC Reclosing device 61 8 1 1 Counter to record the number of reclosings 64 8 2 Function 25 Synchronism check 64 8 2 1 Synchronism 25 and AC Reclosing Device 79 65 8 2 2 Synchronism 25 and C...

Страница 4: ...ts 118 12 9 Function 86 Trip output lockout 118 12 10 Configurable Leds 118 12 11 Programmable Logic Control PGC 119 12 12 Self diagnosis 133 12 13 Test menu 134 12 14 Power Supply 135 13 TECHNICAL SP...

Страница 5: ...electronic components can cause serious damage to electronic circuits It is possible that this damage may not be detected straight away but the electronic circuit reliability and life will be reduced...

Страница 6: ...this connection allows high frequency noise to be evacuated directly to earth The following checks must be performed before the equipment is supplied The rated voltage and polarity The power rating of...

Страница 7: ...www fanox com Rev 01 7 151 2 DIMENSIONS AND CONNECTION DIAGRAMS 2 1 Equipment front view 2 2 Equipment dimensions...

Страница 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...

Страница 9: ...e Phase configuration residual voltage 2VT Phase Phase configuration residual voltage Connecting the relay directly to Low Voltage line Un 200 480 V Phase to neutral configuration Phase to phase confi...

Страница 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...

Страница 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...

Страница 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...

Страница 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...

Страница 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...

Страница 15: ...www fanox com Rev 01 15 151 Connecting the relay directly to Low Voltage line Un 260 480 V Phase neutral connection...

Страница 16: ...com Rev 01 16 151 Phase phase connection NOTE Voltage Neutral protections 50N 67N and 59N voltage ground protections 50G 67G and 59G and voltage sequence protection 47 are not available with this conf...

Страница 17: ...Neutral voltage B10 Neutral voltage B11 Line Phase B voltage B12 Line Phase B voltage Depending on number of Inputs Outputs chosen by model following configurations are available 2 4 1 SILGxxxxxA0xxx...

Страница 18: ...s 1 2 3 and 4 AFD1 Arc Flash Detector input 1 C6 Digital input 5 AFD2 Arc Flash Detector input 2 C7 Digital input 6 AFD3 Arc Flash Detector input 3 C8 Digital input 7 AFD4 Arc Flash Detector input 4 C...

Страница 19: ...5 6 7 and 8 E10 NO contact output 4 D11 D12 Digital input 9 Common of digital input 9 E11 NC contact output 4 D13 D14 Digital input 10 Common of digital input 10 E12 Common point output 4 D15 D16 Digi...

Страница 20: ...can be powered with an auxiliary voltage equal to depending on model 24 48 Vdc 48 230 Vac dc 24 230 Vac dc 48 230Vdc ac Self powered through VTs The following protection functions are available on the...

Страница 21: ...ence current and negative sequence current Second harmonic current per phase Simple voltages phase to phase voltages neutral voltage calculated and measured maximum voltage line voltage positive seque...

Страница 22: ...functions are Status of the circuit breaker Status of the recloser Status of the communication Local control or Remote control The remaining 8 LEDs can be configured to show alarms and states The equ...

Страница 23: ...DNP 3 0 TCP selectable by general settings IRIG B WiFi 2 Ethernet ports RJ45 1 RJ45 port for IEC 61850 1 RJ45 port Modbus TCP and DNP 3 0 TCP selectable by general settings IRIG B WiFi 2 rear ports 1...

Страница 24: ...ltage 1 27L Line Instantaneous undervoltage 1 Optional 59 Phase Instantaneous overvoltage 2 59N G Neutral Instantaneous overvoltage measured calculated 2 47 Negative sequence overvoltage Phase balance...

Страница 25: ...ings IRIG B 2 Ethernet ports RJ45 1 RJ45 port for IEC 61850 1 RJ45 port Modbus TCP or DNP 3 0 TCP IRIG B 3 rear ports 2 Fiber Optic port HSR IEC61850 1 Ethernet port RJ45 Modbus TCP or DNP 3 0 TCP sel...

Страница 26: ...Vac Self powered through VTs Monitoring and Recording Events stored in the non volatile RAM memory 3072 Oscillographic logs DFR in the non volatile FRAM memory 1500 cycles at 32 samples cycle Number o...

Страница 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...

Страница 28: ...www fanox com Rev 01 28 151...

Страница 29: ...www fanox com Rev 01 29 151 3 4 Selection Ordering codes Not all combinations are possible Please confirm with Fanox chosen model...

Страница 30: ...nic is the responsible of the pickup the trip is blocked 4 1 Function 50 Instantaneous phase overcurrent This protection function can be set by using the following parameters Function Description Mini...

Страница 31: ...lowing through the relay so if the phase current exceeds its predetermined value for an equal or greater amount of time than this preset value the protection function activates trips and does not rese...

Страница 32: ...s If the unit operates as defined time the function is activated at 100 of the set tap value and it deactivates at 95 If the unit operates with a curve the function is activated at 110 of the set tap...

Страница 33: ...table shows the operating and polarization magnitudes used for each phase Those magnitudes are displayed graphically below the table Phase Operating magnitude Polarization magnitude Phase A IA Curren...

Страница 34: ...delay is independent from the operating current flowing through the relay so if the phase current exceeds its predetermined value for an equal or greater amount of time than this preset value the prot...

Страница 35: ...es at 100 of the preset input and deactivates at 95 The reset is instantaneous The accuracy of the Time Delay is equal to the set time delay 35ms or 0 5 whichever is greater 4 6 Function 67G Inverse t...

Страница 36: ...the unit operates with a curve the function is activated at 110 of the set tap value and it deactivates at 100 The reset is instantaneous in both cases If the unit operates as defined time the accurac...

Страница 37: ...nt higher than 3 of operating area limits is required The following table shows the operating and polarization magnitudes used for this function Those magnitudes are displayed graphically below the ta...

Страница 38: ...www fanox com Rev 01 38 151 FORWARD REVERSE OPERATING ANGLE 90 HALF CONE ANGLE 60 V polarization OPERATING ANGLE 90 HALF CONE ANGLE 60 HALF CONE ANGLE 60 V polarization...

Страница 39: ...90 Un will be Nominal V P P setting available in general settings regardless the VT connection type 1 Definite time and 8 curves are included to be selected by the user TYPE NAME DT Definite Time IEC...

Страница 40: ...ent as an operating magnitude The intervention sector is defined in the following way the operating angle is rotated anticlockwise from the polarization voltage which gives us the maximum torque direc...

Страница 41: ...www fanox com Rev 01 41 151 FORWARD REVERSE OPERATING ANGLE 90 HALF CONE ANGLE 60 V polarization OPERATING ANGLE 90 HALF CONE ANGLE 60 HALF CONE ANGLE 60 V polarization...

Страница 42: ...Inverse 2 The range of the time Multiplier setting will depend on the curve The range of this setting for each curve family is as follows TIME DIAL TMS Description Minimum Maximum Step Unit Default I...

Страница 43: ...age If the measured relation between I2 and I1 is higher in percentage than the setting in the function during the adjusted time the function will trip The function activates at 100 of the preset inpu...

Страница 44: ...the adjusted tap cooling thermal constant is applied Overload function trips when thermal image reaches the value of 100 This value is got when the flow current is equal to the adjusted tap for the th...

Страница 45: ...hermal image is getting cool based on the cooling constant Zone 4 Before getting totally cool nominal current is applied again and thermal balance is reached once passed the time determined by the hea...

Страница 46: ...www fanox com Rev 01 46 151 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...

Страница 47: ...function activates trips and does not reset itself until the average value of the phase exceeds the point of current pick up The function activates at 100 of the preset input and deactivates at 105 Th...

Страница 48: ...3 HSO 4 AND_PULSE AFD Input 4 AFD TestOK 4 The accuracy of the trip time depends on the method used to supervise the arc flash Supervised by light maximum trip time will be 1 4ms Supervised by curren...

Страница 49: ...Single phase current 1 2 2 4 6 8 10 Three phase current ms 4 3 5 3 5 3 4 3 4 3 4 3 1 3 2 3 3 3 4 3 5 3 6 3 7 3 8 3 9 4 4 1 Trip time ms AFD supervised by current 1 2 2 4 6 8 10 Single phase current 6...

Страница 50: ...m level of voltage it is necessary to measure to work with the function This is if the measured voltage is lower than the Minimum Level setting the function will not trip although this voltage is lowe...

Страница 51: ...01 xUn 0 50 Minimum Level 0 00 1 00 0 01 xUn 0 00 Time delay 0 060 300 000 0 001 s 0 200 Reset time 0 020 300 000 0 001 s 0 200 Un will be Nominal V P P setting available in general settings when the...

Страница 52: ...not reset itself until the measured value of the phase voltage drops below the voltage pick up The function activates at 100 of the preset input and deactivates at 95 The reset time is configurable Th...

Страница 53: ...phase neutral This function is only available for models provided with synchronism function Its working principle is the same as ANSI 59 but it considers the voltage measured in the line instead of t...

Страница 54: ...gardless the connection type due to the negative sequence voltage is always calculated in a phase neutral system The time delay is independent from the negative sequence voltage if the negative sequen...

Страница 55: ...time than this preset value the protection function activates trips and does not reset itself until the measured value of the phase apparent power drops below the activation level pick up The function...

Страница 56: ...stic angle Description Address 0 Active overpower Direct 180 Active overpower Inverse 90 Reactive overpower Direct 270 Reactive overpower Inverse Note Q y P se consume P y Q Q y P Se consume P y se ge...

Страница 57: ...ur functions can be independently configured as overfrequency or underfrequency units If the unit is set as overfrequency activation of the function occurs at 100 frequency level set and its reset whe...

Страница 58: ...activation it takes a minimum of 20 volts P N 35 volts P P for 81R functions to be operational If the measured phase voltage is less than 15 volts P N 26 volts P P it activates a state bit Busbar Fre...

Страница 59: ...1 degree or 10 whichever is greater The reset time is configurable 7 4 Function 24 Overfluxing This protection function detects overfluxing of transformer or generator magnetic circuits by calculating...

Страница 60: ...fficiently quickly to reduce the overvoltage The device measures the Un fn ratio which is proportional to the excitation level of the generator or transformer The calculation is based on the ratio bet...

Страница 61: ...e is initiated another permission logic signal 79Enable can be used to indicate that the recloser must wait another period of time Hold time before closure During this waiting time usually an external...

Страница 62: ...ed with the next options From the HMI There are two specific keys marked 79 Block and Unblock plus a specific signal led allowing recloser operation blocking or unblocking it From the HMI This command...

Страница 63: ...able conditions here Standby and Lockout the other conditions are transient On Standby the recloser can leave this mode via two conditions Manual or remote control opening of the circuit breaker In th...

Страница 64: ...to record the number of reclosings SILG relay has a counter that registry the reclosing actions 8 2 Function 25 Synchronism check The synchro check function is designed to give a time window in which...

Страница 65: ...e 79 To close the circuit breaker when the reclosing device 79 is permitted when both line bar are alive it is necessary to achieve sync conditions Only when these sync conditions are achieved the rec...

Страница 66: ...tor the circuit breaker trip circuits This is performed verifying the continuity of the trip circuit in both circuit breaker positions open and closed To avoid spurious results it must be appropriatel...

Страница 67: ...tion function can be set by using the following parameters Function Description Minimum Maximum Step Unit Default 60VTS Phase VT Supervision Function Enable Yes No No Time Delay 0 020 300 000 0 001 s...

Страница 68: ...e following parameters Group Description Minimum Maximum Step Unit Default 50BF Circuit Breaker opening Failure Function Enable Yes No No Time Delay 0 020 1 000 0 001 s 0 2 When the logic signal 50BF...

Страница 69: ...www fanox com Rev 01 69 151 General trip...

Страница 70: ...setting allows to block this function if the fundamental current exceeds the value specified in the setting The SHB will only be applied in functions that have this feature When the Function Enable o...

Страница 71: ...t breaker state open or closed If the current is less than 0 8 of the rated level it is understood that the line is open with an extremely low usage level operating at night or on weekends In one case...

Страница 72: ...tartup These are the different statuses of the circuit breaker automatic control The function only is initialized on Start when the relay is switched on If the relay doesn t lose power supply the last...

Страница 73: ...s open and if more than 0 8 of rated current is available it is considered the breaker is closed If only the circuit breaker 52a contact is available it should be wired to the corresponding physical i...

Страница 74: ...ine If both circuit breaker contacts 52a and 52b are available they should be wired to the two physical inputs These physical inputs are then assigned to the corresponding logical inputs the circuit b...

Страница 75: ...installing this protection with a circuit breaker which was already working 8 9 3 Accumulated amperes I2 t counter There is also an Accumulated amperes counter This counter accumulates broken amperes...

Страница 76: ...www fanox com Rev 01 76 151 This alarm resets itself when the corresponding time is exceeded with less trips than those indicated...

Страница 77: ...l Voltage 100 480 1 V 110 VT Phase Ratio 1 0 3000 0 0 1 100 0 VT Neutral Ratio 1 0 3000 0 0 1 100 0 For the standard model the neutral current can be set to 1 amp or 5 amps 1 3VTs P N 3VTs P N Vr 3VT...

Страница 78: ...or position and this setting is used for said identification It is important to fill this field in correctly as the events and oscillography data is accompanied by this information This setting can on...

Страница 79: ...35 1 3 Port 1 65535 1 502 IP Address 192 168 200 100 Subnet 255 255 255 0 Modbus Port is read only setting When the relay is connected through wifi connection and the IP address is changed the relay m...

Страница 80: ...0 Modbus RTU Baudrate 4800 115200 4800 9600 19200 38400 57600 115200 bauds 19200 MODBUS RTU Function Description Minimum Maximum Step Unit Default MODBUS RTU Communications Slave address 1 247 1 2 DNP...

Страница 81: ...defined 00 This situation is defined by the active settings group 01 Settings group 1 10 Settings group 2 11 Settings group 3 In the zero position the active item is defined by the active settings gro...

Страница 82: ...al mathematical equation that defines the time in seconds as a function of the current K D B Q V D A t P Where adjusted I I V Parameters A P Q B K Long Time Inverse 120 1 1 0 0 Short Time Inverse 0 05...

Страница 83: ...www fanox com Rev 01 83 151 0 01 0 10 1 00 10 00 100 00 1000 00 1 10 100 t s I It IEC Inverse Dial 0 05 Dial 0 1 Dial 0 2 Dial 0 3 Dial 0 4 Dial 0 5 Dial 0 6 Dial 0 7 Dial 0 8 Dial 1...

Страница 84: ...www fanox com Rev 01 84 151 0 01 0 10 1 00 10 00 100 00 1000 00 1 10 100 t s I It IEC Very Inverse Dial 0 05 Dial 0 1 Dial 0 2 Dial 0 3 Dial 0 4 Dial 0 5 Dial 0 6 Dial 0 7 Dial 0 8 Dial 1...

Страница 85: ...www fanox com Rev 01 85 151 0 00 0 01 0 10 1 00 10 00 100 00 1000 00 1 10 100 t s I It IEC Extremely Inverse Dial 0 05 Dial 0 1 Dial 0 2 Dial 0 3 Dial 0 4 Dial 0 5 Dial 0 6 Dial 0 7 Dial 0 8 Dial 1...

Страница 86: ...ww fanox com Rev 01 86 151 0 01 0 10 1 00 10 00 100 00 1000 00 10000 00 1 10 100 t s I It IEC Long Time Inverse Dial 0 05 Dial 0 1 Dial 0 2 Dial 0 3 Dial 0 4 Dial 0 5 Dial 0 6 Dial 0 7 Dial 0 8 Dial 1...

Страница 87: ...eral mathematical equation that defines the time in seconds as a function of the current B V A TD t P 1 Where adjusted I I V Parameters A P B Ext Inverse 28 2 2 00 0 1217 Very Inverse 19 61 2 00 0 491...

Страница 88: ...www fanox com Rev 01 88 151...

Страница 89: ...www fanox com Rev 01 89 151...

Страница 90: ...www fanox com Rev 01 90 151...

Страница 91: ...rrent I B Phase C Current I C Measured neutral Current I N Calculated neutral current 3I 0 Positive Sequence Current I 1 Negative sequence current I 2 Positive Sequence Current Negative sequence curre...

Страница 92: ...Calculated neutral current 3 V0 Positive Sequence Current V 1 Negative sequence current V 2 Maximum Voltage V Max Phase A voltage angle Ang V A Phase B voltage angle Ang V B Phase C voltage angle Ang...

Страница 93: ...Phase A Reactive power Q A Phase A Apparent power S A Phase B Active power P B Phase B Reactive power Q B Phase B Apparent power S B Phase C Active power P C Phase C Reactive power Q C Phase C Appare...

Страница 94: ...n a circular memory buffer with a capacity for up to 3072 events The memory timestamp is accurate to 1 millisecond The events will be registered in non volatile FRAM memory and the events are conserve...

Страница 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...

Страница 96: ...Error WIFI ON Communication ON General Trip Trip Activation Deactivation Ready Ready Activation Deactivation Wrong Password Set date time Set date time Activation Local Control Local Control Activati...

Страница 97: ...tral Pickup Neutral Pickup Activation Deactivation Phase A Trip Phase A Trip Activation Deactivation Phase B Trip Phase B Trip Activation Deactivation Phase C Trip Phase C Trip Activation Deactivation...

Страница 98: ...on Opening Time 52 Closed 52 Closed Activation Deactivation Closing time 52 Closing Time 52 Closing time Activation 52 Closing Error 52 Closing error Activation Deactivation Closing time 52 Excessive...

Страница 99: ...tivation Output 2 Output 2 Activation Deactivation Output 3 Output 3 Activation Deactivation Output 4 Output 4 Activation Deactivation Output 5 Output 5 Activation Deactivation Output 6 Output 6 Activ...

Страница 100: ...tivation Deactivation Output 4 Output 4 Activation Deactivation Output 5 Output 5 Activation Deactivation Output 6 Output 6 Activation Deactivation Output 7 Output 7 Activation Deactivation Output 8 O...

Страница 101: ...nal 26 Activation Deactivation Logic Signal 27 Logic Signal 27 Activation Deactivation Logic Signal 28 Logic Signal 28 Activation Deactivation Logic Signal 29 Logic Signal 29 Activation Deactivation L...

Страница 102: ...ctivation Deactivation 79 N1 Start 79 N1 Start Activation Deactivation 79 N2 Start 79 N2 Start Activation Deactivation 79 N3 Start 79 N3 Start Activation Deactivation 79 N4 Start 79 N4 Start Activatio...

Страница 103: ...Alarm 2 Alarm 3 Alarm 4 Alarm 5 Alarm 6 Alarm 7 Alarm 8 Alarm 9 Alarm 10 Alarm 11 Alarm 12 Alarm 13 Alarm 14 Alarm 15 Alarm 16 Alarm 17 Alarm 18 Alarm 19 Alarm 20 Alarm 20 Alarm 21 Alarm 22 Alarm 23...

Страница 104: ...Level 1 Instantaneous phase overcurrent 50 1 50 1 Phase A pickup 50 1 Phase A pickup Activation Deactivation Phase A Current 50 1 Phase B pickup 50 1 Phase B pickup Activation Deactivation Phase B Cu...

Страница 105: ...ckup Activation Deactivation Phase C current 67 2 pickup 67 2 pickup Activation Deactivation 67 2 Phase A trip 67 2 Phase A trip Activation Phase A current 67 2 Phase B trip 67 2 Phase B trip Activati...

Страница 106: ...nstantaneous ground overcurrent 50N 50N Neutral pickup 50N Neutral pickup Activation Deactivation Neutral Current 50N Neutral Trip 50N Neutral Trip Activation Deactivation Neutral Current Level 1 inve...

Страница 107: ...trip Activation Phase A current 37 Phase B trip 37 Phase B trip Activation Phase B current 37 Phase C trip 37 Phase C trip Activation Phase C current 37 Trip 37 Trip Activation Level 1 Definite time p...

Страница 108: ...quence undervoltage 27V1 27V1 Pickup 27V1 Pickup Activation Deactivation Positive sequence voltage 27V1 Trip 27V1 Trip Activation Positice sequence voltage Definite time line undervoltage 27L 27L Pick...

Страница 109: ...overvoltage 59N 1 59N 1 Neutral pickup 59N 1 Neutral pickup Activation Deactivation Neutral voltge 59N 1 Neutral Trip 59N 1 Neutral Trip Activation Neutral voltage Level 2 Definite time neutral overv...

Страница 110: ...C trip 32 3 Phase C trip Activation 32 3 Phase trip 32 3 Phase trip Activation Level 4 directional overpower or underpower 32 4 32 4 Phase A pickup 32 4 Phase A pickup Activation Deactivation 32 4 Ph...

Страница 111: ...tion Deactivation Reclose Time Reclose Time Activation Auto reclosing N Is 52 Open Is 52 Open Activation Deactivation Reclose N Hold Time Hold Time Activation Deactivation Auto reclosing N Closing Tim...

Страница 112: ...tion Command identifier Closing Command Closing Command Activation Deactivation Command identifier 79Blck Command 79Blck Command Activation Deactivation Command identifier 79Unblock Command 79Unblock...

Страница 113: ...sing Command Activation Deactivation Command identifier 79Block Command 79Block Command Activation Deactivation Command identifier 79Unblock Command 79Unblock Command Activation Deactivation Command i...

Страница 114: ...nts in the relay However the user can mask and unmask the events distinguishing if the action applies to the activation or deactivation reasons A brief description of the general states is given below...

Страница 115: ...IEEE C37 111 1991 It is possible to configure the reason of the start of the fault report through the DFR Start in the PGC It must be considered that if there is no trip of a protection function the...

Страница 116: ...Trip 79 32 3 Pickup 16 37 Trip 48 60VTS Trip 80 32 4 Pickup 17 27 1 Trip 49 50BF Trip 81 General Pickup 18 27 2 Trip 50 SHB Block 82 AFD Input 1 19 27V1 Trip 51 CLP 83 AFD Input 2 20 27L Trip 52 Gener...

Страница 117: ...ry to switch the relay off and to switch it on again to ensure that the new setting is recorded correctly 12 6 Counters The following counters are provided 1 Number of openings of the circuit breaker...

Страница 118: ...be configured from the HMI or through the SICom program The inputs are configured by associating the logical inputs with the required physical or logical input or to none if the logical input is not u...

Страница 119: ...odel These inputs are translated to internal binary states which later can be assigned to logical signal to get a specific operation SIL G is provided with 32 outputs Physical outputs are the real out...

Страница 120: ...eactivated same time on off BLINKING Period Time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated OR BL Period and Time up Period It is the period of the s...

Страница 121: ...activated and deactivated same time on off BLINKING Period time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated NOR BL Period and Time up Period It is the...

Страница 122: ...activated and deactivated same time on off BLINKING Period time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated AND BL Period and Time up Period It is the...

Страница 123: ...activated and deactivated same time on off BLINKING Period time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated NAND BL Period and Time up Period It is th...

Страница 124: ...activated and deactivated same time on off BLINKING Period time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated XOR BL Period and Time up Period It is the...

Страница 125: ...th RSFF PS Time up The time the pulses are activated and deactivated same time on off BLINKING Period time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated...

Страница 126: ...th SRFF PS Time up The time the pulses are activated and deactivated same time on off BLINKING Period time up Period Repetitive time between each pulse Tme up Time during which each pulse is activated...

Страница 127: ...h the pulse is activated R EDGE 1P Time up The time the pulse lasts LOGIC GATE OPERATION SETTABLE PARAMETERS HMI SYMBOL SICOM SYMBOL APPLICABLE EXTRA PARAMETERS F_EDGE4 F EDGE NA 1 PULSE Time up Time...

Страница 128: ...UP The configured signal will make a pulse of the adjusted time in time up parameter once the input signal is activated The configured signal waits the adjusted time in time up parameter to activate...

Страница 129: ...www fanox com Rev 01 129 151 TIMER DOWN Once the configured signal is activated it waits the adjusted time in time up parameter to deactivate itself...

Страница 130: ...ority for set signals RS FLIP FLOP priority for reset signals The configured signal will be activated once the bits in s position are activated set position The signal is maintained activated until th...

Страница 131: ...www fanox com Rev 01 131 151 PULSES Same time on and time off The configured signal will make pulses of the adjusted milliseconds while the input signal is activated Input Output T T T...

Страница 132: ...132 151 BLINKING different time on T and time off T2 The configured signal will be activated the time set in time up parameter and will be switched off the time set in period parameter less the set i...

Страница 133: ...finally pressing the right key the PGC signals will be placed Once the output is found press left key to find the correct operation press OK to assign the operation Then the configuration is finished...

Страница 134: ...vate it if it is deactivated and to deactivate it if it is activated Press C to leave the test menu Once the relay is in test menu mode all the LEDs will be activated simultaneously In case of the out...

Страница 135: ...upply The unit s power consumption is less than 4 watts SIL G is designed to be powered with an auxiliary voltage of 24 230 Vac dc Power supply is guaranteed between 20 10 of auxiliary voltage The rel...

Страница 136: ...tantaneous deactivation Timing accuracy 0 5 or 35 ms greater of both Function 67 1 Function 67 2 Function 67 3 Function 67 4 Function enable No Alarm Trip SHB Trip Curve Type IEC 60255 151 and IEEE cu...

Страница 137: ...vel 100 Voltage deactivation level 95 Instantaneous deactivation Timing accuracy for IEC and IEEE curves selection 30 ms or 5 greater of both Timing accuracy for de ned time curve selection 35 ms or 0...

Страница 138: ...30 000xIn step 0 001xIn Activation level 100 Deactivation level 95 Temporized deactivation Function CLP Function enable Yes No Settings group 1 to 4 step 1 No load time 0 020 to 300 000 s step 0 001 s...

Страница 139: ...ivation level 105 Temporized deactivation Timing accuracy 0 5 or 30 ms greater of both Function 27V1 Function enable No Alarm Trip Voltage tap 0 15 to 2 00 xUn step 0 01xUn Minimum level 0 00 to 1 00...

Страница 140: ...of both Function 32 1 Function 32 2 Function 32 3 Function 32 4 Function enable No Alarm Trip Activation level 0 08 to 2 00 xSn step 0 01xSn Operating angle 0 to 359 step 1 Time delay 0 020 to 300 000...

Страница 141: ...tep 0 001 s Reset Time 0 020 to 300 000 s step 0 001 s Curve current activation level 110 Curve current deactivation level 100 Defined time current activation level 100 Defined time current deactivati...

Страница 142: ...ample Function 86 It allows to latch lock out the contact trip due to programmable logic PGC RSFF Function 68 Available through con gurable inputs and outputs thanks to the programmable logic PGC Prog...

Страница 143: ...the range With VTs 3 250 V Direct connection Up to 1000 V Angle measurements Current Angles IA IB IC IN and 3I0 Voltage Angles VA VB VC VR VL 3V0 UAB UBC and UCA Accuracy 2 Power measurements Total an...

Страница 144: ...in a system of menus A keypad is fitted to the relay front panel which can be used to access the information shown on the LCD screen and to navigate through the menu system This membrane keyboard has...

Страница 145: ...Status reading Measurement reading Read and change settings Read and change configuration Read and delete events Read and delete DFR Configure and check the demand LDP Date time synchronisation Set Co...

Страница 146: ...ecessary drivers depending on the operative system can be downloaded from this page The update of the software does not require any user s action this is if the computer is connected to Internet SICom...

Страница 147: ...ssible to perform the operations shown on the table below HMI ACCESS LEVEL PASSWORD Permission to Change settings Set date Time Permission to Execute Commands Set Counters Delete Events Delete DFR Del...

Страница 148: ...R Set Date Time Permission to Change user s Configuration Delete user s configuration Permission to Upgrade the FW flashing process Permission to Read and change access levels Permission to Change man...

Страница 149: ...COM and up to 4 characters if HMI is used By default the equipment is programmed with the following passwords and their associated levels HMI PASSWORDS SICOM PASSWORDS ACCESS LEVEL Fanox 0000 0 1111 2...

Страница 150: ...www fanox com Rev 01 150 151 NOTES...

Страница 151: ...www fanox com Rev 01 151 151...

Отзывы: