± 30 ms or ± 5% (greater of both)
Timing accuracy for defined time curve selection:
± 35 ms or ± 0.5% (greater of both)
Function
SOTF (*)
Function enable: No/Alarm/Trip/SHB
Trip
Current tap: 0.010 to 30.000 xIn
(step 0.001xIn)
Time delay: 0.000 to 300.000 s (step
0.001 s)
Safe Time: 0.000 to 300.000 s (step
0.001 s)
Activation level: 100%
Deactivation level: 95%
Instantaneous deactivation
Timing accuracy: ±0.5% or ±35 ms (greater
of both)
Function 49
Function enable: No/Alarm/Trip
Current tap: 0.100 to 2.400 In (step 0.001xIn)
ζ
heating: 3 to 600 min (step 1 min)
ζ
cooling: 1 to 6 xζ heating (step 1)
Alarm: 20 to 99% (step 1%)
Trip level: 100%
Deactivation level: 95% of alarm level
Timing accuracy: ± 5% respect of theorical value.
Function SHB
Function enable: No/Yes
Current Tap: 5- 50% (step 1%)
Reset Time: 0.000-300.000 (step 0.001 s)
Block Threshold: 0.010-30.000xIn (step 0.001xIn)
Activation level: 100%
Deactivation level: 95%
Temporized deactivation
Function CLP
Function enable: Yes/No
Settings group: 1 to 4 (step 1)
No load time: 0.020 to 300.000 s (step 0.001 s)
Cold load time: 0.020 to 300.000 s (step 0.001 s)
Function 46
Function enable: No/Alarm/Trip/SHB Trip
Curve Type: IEC 60255-151 and IEEE curves.
IEC (Definite time, standard inverse, very inverse, extremely inverse, long time inverse, short
time inverse and IEEE (Moderately inverse, very inverse, extremely inverse.
Time delay: 0.000 to 300.000 s (step 0.001 s)
Time dial (TMS): 0.05 to 25.00 (step 0.01)
If Curve type IEC: 0.05 to 1.00 (step 0.01)
If Curve type IEEE: 0.10 to 25.00 (step 0.01)
Current tap: 0.010 to 20.000 xIn (step 0.001xIn)
Curve, current activation level: 110%
Curve, current deactivation level: 100%
Defined time, current activation level: 100%
Defined time, current deactivation level: 95%
Instantaneous deactivation
Timing accuracy for IEC and IEEE curves selection:
± 30 ms or ± 5% (greater of both)
Timing accuracy for defined time curve selecti
on:
Содержание SIL-G
Страница 1: ...USER S MANUAL USER S MANUAL SIL G Feeder Relay...
Страница 8: ...www fanox com Rev 01 8 151 2 3 Connection diagrams 2 3 1 Analog current connections...
Страница 10: ...www fanox com Rev 01 10 151 3 VT configuration phase neutral...
Страница 11: ...www fanox com Rev 01 11 151 3 VT configuration phase neutral residual voltage...
Страница 12: ...www fanox com Rev 01 12 151 3VT configuration phase phase residual voltage...
Страница 13: ...www fanox com Rev 01 13 151 2VT configuration phase phase residual voltage...
Страница 14: ...www fanox com Rev 01 14 151 3 VT configuration phase neutral phase B line voltage...
Страница 27: ...www fanox com Rev 01 27 151 Dimensions 175x175x150 3 3 Functional diagram...
Страница 28: ...www fanox com Rev 01 28 151...
Страница 46: ...www fanox com Rev 01 46 151 4 10 4 Thermal protection curves This is the thermal curve for 3 minutes...
Страница 69: ...www fanox com Rev 01 69 151 General trip...
Страница 88: ...www fanox com Rev 01 88 151...
Страница 89: ...www fanox com Rev 01 89 151...
Страница 90: ...www fanox com Rev 01 90 151...
Страница 95: ...www fanox com Rev 01 95 151 Time Minutes Seconds Milliseconds...
Страница 150: ...www fanox com Rev 01 150 151 NOTES...
Страница 151: ...www fanox com Rev 01 151 151...